Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
INSTALL SMOKE DETECTORS | BOILER ROOM MISSING SMOKE DETECTOR | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | BOILER ROOM MISSING CARBON MONOXIDE DETECTOR | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | STAIR SYSTEM GRADE TO BASEMENT WEST ELEVATION VERY LOOSE METAL HANDRAIL | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
TEST G & S FRT ELE | 5 YEAR TEST. EV003034. | 1832 W JUNEWAY TER | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SEAL ALL PENETRATIONS IN MACHINE ROOM. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING PHONES REQUIRED IN BOTH ELEVATOR CABS. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | LABEL ALL DISCONNECT SWITCHES WITH VOLTAGE AND USE. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE AUXILLARY CONTACTS FOR BATTERY LOWERING. TEST SAME. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ADD MORE MACHINE ROOM LIGHTING WITH GUARDS. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL A DRIP PAN UNDER PIPES PASSING OVER #2 PUMP UNIT. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CHECK PIT LIGHTING. | 1832 W JUNEWAY TER | PERMIT | PASSED | View |
REPAIR EXTERIOR WALL | ADDITIONAL INFORMATION: EXTERIOR WALL,BRICKS SPALLED,MORTAR WASHED OUT,MORTAR EROSION,MORTAR FRACTURED JOINTSCOMMENTS: FRACTURES ALL AROUND BUILDING, FROM GRADE TO PARRAPET. | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
PARAPET & COPING | MORTAR WASHED OUT AT VARIOUS LOCATIONS, COPING MISSING AT EAST BY NORTH END. | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | ADDITIONAL INFORMATION: WINDOW PANE,BROKEN,MISSINGCOMMENTS: WEST ELEVATION VARIOUS LOCATIONS. | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | ADDITIONAL INFORMATION: ARRANGE INSPECTION,INTERIORCOMMENTS: ARRANGE FOR INTERIOR INSPECTION. | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: CATEGORY 5 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. | 1832 W JUNEWAY TER | PERIODIC | FAILED | View |