Chicago Building Violations Data: 41 Violations
Violation Inspector Comments Address Category Status View
ARRANGE PREMISE INSPECTION ENGINEER NOT AVAILABLE FOR COMPLETE INPECTION ON 8/30/10. ARRANGE FOR INSPECTION. 5320 N SHERIDAN RD PERIODIC FAILED View
ARRANGE PREMISE INSPECTION ENGINEER NOT AVAILABLE FOR COMPLETE INPECTION ON 8/30/10. ARRANGE FOR INSPECTION. 5320 N SHERIDAN RD PERIODIC FAILED View
MAINTAIN MECH. VENT SYSTEM MAINTAIN MECHANICAL VENTILATION SYSTEM IN GOOD REPAIR AND OPERATE TO PROVIDE ADEQUATE VENTILATION DURING HOURS OF OCCUPANCY 18-28-102.3 (1) EXHAUST FAN #4 NOT OPERABLE (MAY BE BELT) ROOF (2) KEEP FILTERS CLEAN IN MAKE AIR UNITS (2) ROOF (3) REPAIR SCREENS ON MAKE UP AIR UNITS ROOF (4) EXHAUST FAN FOR GARAGE (LOWER LEVEL) NOT OPERATING AT TIME OF INSPECTION 5320 N SHERIDAN RD PERIODIC PASSED View
SELF-CLOSE DOOR >4 STORY RES. NO ACCESS TO ALL UNIT DOORS - UNABLE TO DETERMINE SELF CLOSING DEVICE OPERATION AND DOOR LATCHING HARDWARE. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 18-27-700.5 EMERGENCY EGRESS LIGHTING AND EXIT SIGN ON-SITE AUXILIARY SOURCE OF CURRENT SUPPLY - EXIT SIGNS MISSING BATTERY BACKUP WHERE NO EMERGENCY GENERATOR HAS BEEN INSTALLED. 5320 N SHERIDAN RD PERIODIC FAILED View
CARB MONOX DETECT IN RESID 1. 26TH FLOOR PENTHOUSE BOILER ROOM - MISSING CARBON MONOXIDE DETECTOR.2. MEZZANINE LEVEL LAUNDRY ROOM - MISSING CARBON MONOXIDE DETECTOR. 3. GROUND FLOOR BOILER ROOM - MISSING CARBON MONOXIDE DETECTOR. 5320 N SHERIDAN RD PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED 1. ELEVATOR MACHINE ROOM - EXIT SIGN NOT ILLUMINATED AT TIME OF INSPECTION. 2.MEZZANINE LEVEL LAUNDRY ROOM - EXIT SIGN NOT ILLUMINATED. 3. SUNDECK NORTHWEST CORNER - EXIT SIGN BROKEN. 4. GROUND FLOOR - EXIT SIGN NOT ILLUMINATED AT TIME OF INSPECTION. 5. PARKING GARAGE - MULTIPLE EXIT SIGNS NOT ILLUMINATED AT TIME OF INSPECTION. 5320 N SHERIDAN RD PERIODIC FAILED View
EXPOSED WIRING 1. 25TH FLOOR ELECTRICAL ROOM - MULTIPLE ELECTRICAL PANELS MISSING COVER PLATES - EXPOSED WIRES. 2. GROUND FLOOR BOILER AND PUMP ROOM - EXPOSED WIRES. 5320 N SHERIDAN RD PERIODIC FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY 4TH, 5TH, 22ND AND ROOF LEVEL NORTH STAIR, MEZZANINE LEVEL, 10TH AND 25TH FLOOR SOUTH STAIR, GROUND FLOOR LOBBY LEVEL VESTIBULE TO GARAGE - OPENINGS AROUND PIPE PENETRATIONS IN WALLS AND FLOOR MISSING FIRE SEAL MATERIALS OR NON-COMBUSTIBLE MATERIALS. *SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 13-76-075 STAIRWELL IDENTIFICATION - PROPER PERMANENT STAIRWELL IDENTIFICATION MISSING AT EACH FLOOR ON CORRIDOR SIDE OF STAIR. NORTH MEZZANINE STAIRWELL MISSING IDENTIFICATIONS AT EACH FLOOR ON BOTH CORRIDOR AND STAIRWELL SIDE. 5320 N SHERIDAN RD PERIODIC FAILED View
1HR ENCL FLR TO FLR SHAFT/DUCT ALL FLOORS AT TRASH CHUTE ROOMS, AND 3RD, 5TH, 6TH, 8TH,12TH, 14TH AND 15TH FLOOR ELECTRICAL ROOMS - OPENINGS AROUND PIPE PENETRATIONS IN WALLS AND FLOOR MISSING PROPER FIRE SEAL MATERIALS OR NON-COMBUSTIBLE MATERIALS.**FOAM NOT ALLOWED - *SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 13-76-020 FIRE SAFETY - COMPARTMENTATION - 1. 6TH, 8TH, 9TH, 11TH, 12TH, 13TH, 14TH, 15TH, 21ST, 22ND, AND 24TH FLOORS, CENTER COMPARTMENTATION DOORS DOOR NOT PROPERLY CLOSE AND LATCH SHUT. 2. PARKING GARAGE COMPARTMENT DOORS - NO TEST DOCUMENTATION ON SITE AT TIME OF INSPECTION. 5320 N SHERIDAN RD PERIODIC FAILED View
SELF-CLOSE CLASS B FIRE DOOR 1. 3RD, 5TH, 6TH, 9TH, 11TH, 12TH AND 25TH FLOOR CORRIDORS - ELECTRICAL ROOM DOORS DO NOT PROPERLY CLOSE AND LATCH SHUT. 2. 4TH, 11TH AND 19TH FLOOR TRASH CHUTE DOORS DO NOT PROPERLY CLOSE AND LATCH SHUT. 3. 6TH, 13TH AND 14TH FLOOR TRASH CHUTE DOORS MISSING SELF CLOSING DEVICES. 4. MEZZANINE LEVEL SOUTH STORAGE ROOM - DOOR TO STORAGE ROOM MISSING FIRE RATING TAG. 5320 N SHERIDAN RD PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL 1. 18TH FLOOR NORTH STAIR - DOOR DOES NOT PROPERLY CLOSE AND LATCH SHUT. 2. NORTH MEZZANINE LEVEL STAIR ACCESS TO GARAGE. -STAIR DOOR DOES NOT CLOSE AND LATCH SHUT. 3. GROUND FLOOR LOBBY LEVEL - GARAGE ACCESS STAIRWELL - DOOR MISSING FIRE RATED TAG. 4. PARKING GARAGE NORTH EXIT STAIR AND SOUTHWEST EXIT STAIR - MULTIPLE DOORS DO NOT CLOSE AND LATCH SHUT. 5320 N SHERIDAN RD PERIODIC FAILED View
RESTORE EXIT AND EM 1. 12TH FLOOR SOUTH STAIR - EMERGENCY LIGHT NOT WORKING WHEN TESTED. 2. MEZZANINE LEVEL SOUTH STORAGE ROOM - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 3. MEZZANINE LEVEL NORTH BUSINESS ROOM ¿ EMERGENCY LIGHT NOT WORKING WHEN TESTED. 4. STAIRWELL TO POOL - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 5. GROUND FLOOR ENGINEERS OFFICE - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 5320 N SHERIDAN RD PERIODIC FAILED View
1HR PUB.CORRIDOR IN MULT. D.U. 1. MEZZANINE LEVEL LAUNDRY ROOM - DOOR MISSING FIRE RATED TAG AND HAS HOLD OPEN DEVICE. 2. MEZZANINE LEVEL CORRIDOR - FIRE SHUTTERS SEPARATING 1ST FLOOR LOBBY AND MEZZANINE CORRIDOR MISSING DOCUMENTATION OF OPPERATION. UNABLE TO DETERMINE FUNCTION OF SHUTTERS. 5320 N SHERIDAN RD PERIODIC FAILED View
2HR SEP FOR STORAGE >100SF MEZZANINE LEVEL SOUTH STORAGE ROOM - OLD LANUNDRY ROOM NOW BEING USED FOR STORAGE - FIRE SEPARATION NOT COMPLETE, HOLES IN WALLS AND DRYWALL MISSING AT WEST WALL. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE CLASS A FIRE DOOR B AND D PARKING GARAGE LEVELS BUILDING ACCESS - VESTIBULE DOORS ONLY B-LABEL 1 ½ HOUR RATED. PROVIDE (2) 3 HOUR A-LABEL DOORS AT EACH VESTIBULE. 5320 N SHERIDAN RD PERIODIC FAILED View
NO KEY TO USE EXIT DOOR PARKING GARAGE ACCESS AND EXIT STAIR TO BUILDING - EXIT DOORS ON GARAGE LEVELS B, D, AND F REQUIRE A KEY OR FOB TO EXIT INTO BUILDING FROM EGRESS SIDE. NO FAIL-SAFE SYSTEM INSTALLED. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 13-56-280 AND 13-56-090 ¿ 1 HOUR SEPARATION REQUIRED BETWEEN RESIDENTIAL AND BUSINESS USE. 1ST FLOOR OFFICE SPACE - WEST INTERIOR WALL HAS A LARGE CRACK ALONG A COLUMN CLEAR TO RESIDENTIAL MAINTENANCE ROOM. SEAL ALL PENETRATIONS BETWEEN OCCUPANCIES. 5320 N SHERIDAN RD PERIODIC FAILED View
I-A I-B I-C AND II FIRE RESIST 1ST FLOOR NORTH MAINTENANCE ROOM - WOOD PARTITION WALLS CONSTRUCTED TO CREATE A VESTUBULE ¿ COMBUSTIBLE MATERIALS NOT ALLOWED. REMOVE STRUCTURE AND RETURN TO ORIGNAL STATE OR PROVIDE PLANS AND OBTAIN A PERMIT FOR REPAIRS. 5320 N SHERIDAN RD PERIODIC FAILED View
H.P 2 HR ENCLOSURE 1ST FLOOR BOILER ROOM - OPENINGS AROUND PIPE PENETRATIONS IN WALLS AND FLOOR MISSING FIRE SEAL MATERIALS OR NON-COMBUSTIBLE MATERIALS. *SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. 5320 N SHERIDAN RD PERIODIC FAILED View
DEBRIS, EXCESSIVE PARKING GARAGE - ITEMS BEING STORED ON PARKING LEVELS. 5320 N SHERIDAN RD PERIODIC FAILED View
RESTORE EXIT AND EM 1. 12TH FLOOR SOUTH STAIR - EMERGENCY LIGHT NOT WORKING WHEN TESTED. 2. MEZZANINE LEVEL SOUTH STORAGE ROOM - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 3. MEZZANINE LEVEL NORTH BUSINESS ROOM ¿¿ EMERGENCY LIGHT NOT WORKING WHEN TESTED. 4. STAIRWELL TO POOL - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 5. GROUND FLOOR ENGINEERS OFFICE - EMERGENCY LIGHTING NOT WORKING WHEN TESTED. 5320 N SHERIDAN RD PERIODIC FAILED View
INSTALL EXIT SIGN 1. MEZZANINE LEVEL NORTH BUSINESS ROOM ¿¿ MISSING EXIT SIGN. 2. GROUND FLOOR BOILER, PUMP ROOM AND TRASH COMPACTOR ROOM - MISSING EXIT SIGNS. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE CLASS A FIRE DOOR B AND D PARKING GARAGE LEVELS BUILDING ACCESS - VESTIBULE DOORS ONLY B-LABEL 1 ½ HOUR RATED. PROVIDE (2) 3 HOUR A-LABEL DOORS AT EACH VESTIBULE. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 13-56-280 AND 13-56-090 ¿¿ 1 HOUR SEPARATION REQUIRED BETWEEN RESIDENTIAL AND BUSINESS USE. 1ST FLOOR OFFICE SPACE - WEST INTERIOR WALL HAS A LARGE CRACK ALONG A COLUMN CLEAR TO RESIDENTIAL MAINTENANCE ROOM. SEAL ALL PENETRATIONS BETWEEN OCCUPANCIES. 5320 N SHERIDAN RD PERIODIC FAILED View
I-A I-B I-C AND II FIRE RESIST 1ST FLOOR NORTH MAINTENANCE ROOM - WOOD PARTITION WALLS CONSTRUCTED TO CREATE A VESTUBULE ¿¿ COMBUSTIBLE MATERIALS NOT ALLOWED. REMOVE STRUCTURE AND RETURN TO ORIGNAL STATE OR PROVIDE PLANS AND OBTAIN A PERMIT FOR REPAIRS. 5320 N SHERIDAN RD PERIODIC FAILED View
INSTALL EXIT SIGN 1. MEZZANINE LEVEL NORTH BUSINESS ROOM ¿ MISSING EXIT SIGN. 2. GROUND FLOOR BOILER, PUMP ROOM AND TRASH COMPACTOR ROOM - MISSING EXIT SIGNS. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PER SECTION CODE 13-196-206 (D) FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN 5320 N SHERIDAN RD COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A FIREMAN'S KEY BOX AT THE ELEVATOR LOBBY CONTROL PANEL 5320 N SHERIDAN RD PERMIT PASSED View
SELF-CLOSE CLASS B FIRE DOOR 1. 26TH FLOOR PENTHOUSE BOILER ROOM AND MISSING SELF CLOSING DEVICES. 2. 25TH AND 26TH FLOOR PENTHOUSE ELECTRICAL ROOMS MISSING SELF CLOSING DEVICES. 5320 N SHERIDAN RD PERIODIC FAILED View
PROVIDE PROVIDE PER CODE SECTION 18-27-700.6 EMERGENCY LIGHTING - EMERGENCY LIGHTING MISSING IN BOILER ROOM AND IN PARKING GARAGE. 5320 N SHERIDAN RD PERIODIC FAILED View
FIRE EXTNGSHR RECHARGE & TAG MEZZANINE LEVEL SOUTH STORAGE ROOM - FIRE EXTINGUISHER RECHARGE TAG EXPIRED. 5320 N SHERIDAN RD PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA OBTAIN ADMINISTRATIVE RELIEF (VARIANCE) FOR NON- COMPLIANT TOE GUARD. 5320 N SHERIDAN RD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RETEST DOWN CARTOP INSPECTION LIMIT 5320 N SHERIDAN RD PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA TEST AUTO FIRE RECALL AND AUTO EVACUATION SYSTEMS PRIOR TO FINAL. 5320 N SHERIDAN RD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR OR REPLACE CANT ON LEDGE AT FIRST FLOOR. 5320 N SHERIDAN RD PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA UPDATE FIRE SERVICE TO 2016 CODE PRIOR TO FINAL. 5320 N SHERIDAN RD PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA TEST COMMUNICATION FAILURE WHEN FIXTURE IS INSTALLED. 5320 N SHERIDAN RD PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE AN ETCHED DIAGRAMATIACAL DEPICTION OF THE BUILDING WITH THE LOCATION OF THE ELEVATORS ON THE ELEVATOR LOBBY CONTROL PANEL 5320 N SHERIDAN RD PERMIT PASSED View