Chicago Building Violations Data: 26 Violations
Violation Inspector Comments Address Category Status View
OBTAIN PERMIT BEFORE SIGN WORK 1' X 20' SIGN AGE ON DUCTWORK "TAQUERIA ATOTONILCO NO.1" 13-20-520 13-20-550 3916 W 26TH ST COMPLAINT FAILED View
OPEN TYPE VIOLATION (VT 6015) COMMERICAL KITCHEN MAKE UP AIR 2.1 MAKE UP AIR TEMPERATURE- THE TEMPERATURE DIFFERENTIAL BETWEEN MAKE UP AIR & THE AIR IN THE CONDITION SPACE BE OPERABLE 3916 W 26TH ST COMPLAINT FAILED View
OPEN TYPE VIOLATION (VT 2031) 13-16-070 WORKMANSHIP TO MEET INTENT OF BUILDING PROVISIONS OF THE CODE (NEED TO LEAK TEST ALL BLACK IRON KITCHEN EXHAUST DUCT) NEED TO PROVIDE 2 LAYERS OF FIRE WRAP FOR ALL INTERNAL KITCHEN EXHAUST DUCT / NEED TO REMOVE EXTERNAL SHEET METAL GALVANIZED SHROUD SCREWED ONTO BLACK IRON DUCT NEED TO CLEAN EXCESSIVE GREASE ACCUMULATION ON THE ROOF, NEIGHBORS ROOF & SIDE OF BUILDING 3916 W 26TH ST COMPLAINT FAILED View
PROVIDE SUPPLY 18-28-40.3 VENTILATION REQUIREMENT PROVIDE MECHANICAL SUPPLY VENTILATION AT CUBIC FEET PER MINUTE EQUAL TO SQUARE FEET OF FLOOR AREA TIMES FACTOR BASED ON USE NEED TO PROVIDE ECONOMIZERS TO ALL ROOF TO UNITS 3916 W 26TH ST COMPLAINT FAILED View
SUBMIT PLANS/GET VENT PERMIT 13-32-010 PERMIT REQUIRED SUBMIT PLANS AND OBTAIN VENTILATION SYSTEM PERMITS NEED TO SUBMIT AS BUILT DRAWINGS & OBTAIN A VENTILATION REPAIR PERMIT 3916 W 26TH ST COMPLAINT FAILED View
OPEN TYPE VIOLATION (VT 6015) COMMERCIAL KITCHEN MAKEUP AIR -2.1 MAKE UP AIR TEMPERATURE THE TEMPERATURE DIFFERENTIAL BETWEEN MAKE UP AIR & THE AIR IN THE CONDITIONS SPACE SHALL NOT EXCEED 10-MAKE UP AIR UNIT MUST BE OPERABLE . A MINIMUM OF THE 1ST FOUR FEET OF MAKE UP AIR DUCT STARTING AT THE HOOD SHALL BE THE SAME GAUGE AS THE EXHAUST DUCT 2.6 A FIRE DAMPER SHALL BE INSTALLED BETWEEN THE HEAVIER AND LIGHTER GAUGE DUCT WORK 3916 W 26TH ST COMPLAINT FAILED View
PROVIDE MINIMUM VENT QUANTITY 18-28-403 MECHANICAL VENTILATION PROVIDE VENTILATION NO VENTILATION FOR THE DINING AREA 3916 W 26TH ST COMPLAINT FAILED View
OPEN TYPE VIOLATION 18-28-711 CARBON MONOXIDE DETECTORS NEED TO PROVIDE CARBON MONOXIDE DETECTORS FOR DINING AREA 3916 W 26TH ST COMPLAINT FAILED View
ARRANGE COMPLETED PERMIT INSP. 18-28-106.1 INSPECTION REQUIRED ARRANGE FOR COMPLETE PERMIT & OBTAIN PERMITS FOR WARM AIR HEATING SYSTEM & VENTILATION SYSTEMS WHEN WORK ID COMPLETE INSPECTION 3916 W 26TH ST COMPLAINT FAILED View
GIVE VENT OPENINGS % FL. AREA 18-28-40. VENTILATION REQUIREMENT PROVIDE MECHANICAL EXHAUST CUBIC FEET PER MINUTE EQUAL TO SQUARE FEET OF OF FLOOR AREA TIMES FACTOR BASED ON USE-NEED TO PROVIDE 3916 W 26TH ST COMPLAINT FAILED View
CLOSE BOX OPENINGS CLOSE OPENINGS IN PANELS 3916 W 26TH ST COMPLAINT FAILED View
INSTALL COVERS CLOSE OPENING IN BOXES ABOVE CEILINGS. D&H 3916 W 26TH ST COMPLAINT FAILED View
DEFECTIVE SERVICE SERVICE CONDUCTOR ARE TO LOW NEAR 2ND REAR DOOR 3916 W 26TH ST COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE PVC TRAP AND TAIL PIECE ON KITCHEN HAND SINK. 3916 W 26TH ST COMPLAINT HOLD View
UNAPPROVED CORDS REMOVE UNAPPROVED CORDS ABOVE DROP CEILING USED TO SPLICE LIGHT TOGETHER D&H 3916 W 26TH ST COMPLAINT FAILED View
STOP LEAKING WATER ON THE GALVANIZED PIPE IN THE BASEMENT. 3916 W 26TH ST COMPLAINT HOLD View
PANEL SCHEDULES LABEL ALL PANELS & CIRCUITS. D&H 3916 W 26TH ST COMPLAINT FAILED View
PROV HOT WTR TO ALL FIXTURES 3916 W 26TH ST COMPLAINT HOLD View
SYSTEM III INSTALL SYSTEM 3EM IN BASEMENT D&H 3916 W 26TH ST COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE AT LAVATORY, WATER CLOSET IN THE WOMENS AND MENS BATHROOM 3916 W 26TH ST COMPLAINT HOLD View
SECURE RACEWAY SUPPORT CONDUCTS IN BASEMENT AND ABOVE DROP CEILING. D&H 3916 W 26TH ST COMPLAINT FAILED View
RESTORE EXIT AND EM SYSTEM 3EM NOT WORKING ON 1ST FL D&H 3916 W 26TH ST COMPLAINT FAILED View
ARMORED CABLE EXCESS ARMORED CABLE IN CEILING. D&H 3916 W 26TH ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT FAILED TO MAINTAIN FIRE RESISTANCE OF HOT LESS THAN 1 HOUR TO FLOOR CONSTRUCTION OVER BASEMENT 13-60-200 3916 W 26TH ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT FAILED TO MAINTAIN 1-HOUR SEPERATION BETWEEN FLOORS IN EXISTING 2-STORY MASONRY MIXED OCCUPANCY BUILDING (F/A1) - PORTION OF LATH AND PLASTER CEILING MISSING AT 1ST FLOOR CEILING 13-56-280 3916 W 26TH ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT PROVIDE GUARDRAIL AT 2ND FLOOR EXTERIOR LANDING AT NORTH ELEVATION 13-124-330 3916 W 26TH ST COMPLAINT FAILED View