Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PROPER SIZE GRD ELECTRODE COND | GROUNDING ELECTRODE CONDUCTOR IS NOT PROPERLY TERMINATED TO THE COLD WATER SERVICE AND IS EMBEDDED WITHIN THE CONCRETE NO BOND STRAP INSTALLED AT WATER SERVICE REMOVE BRANCH CIRCUIT FROM GEC CONDUIT BEING USED FOR BASEMENT FEED D&H | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | REMOVE CORD FEEDING FRONT POWER SECURITY SHADES WHICH IS FED THROUGH THE STRUCTURE AND NOT WIRED ACCORDING TO THE CITY OF CHICAGO RECOGNIZED WIRING METHODS D&H | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
DEFECTIVE SERVICE | RELOCATE COM ED SERVICE DROP SO THAT IS NOT WITHIN REACH FROM THE 2ND FLOOR REAR DECK (14E-2-230.24) AND RAISE SERVICE DROP SO THAT IT IS NOT LAYING DIRECTLY ON ROOF OF GARAGE (14E-2-230.24(A) D&H | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE ELECTRICAL PERMIT IN ORDER TO CORRECT ELECTRICAL VIOLATIONS (14A-4-404.6) | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View | |
PANEL SCHEDULES | INSTALL PANEL SCHEDULES FOR ALL SERVICE PANELS | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE | NO TEMPERATURE CONTROL VALVES INSTALLED ON COMMERCIAL LAVATORY, OR HAND SINKS THROUGHOUT COMMERCIAL SPACE 18.29.607.1.1 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
INSPECT CONSTRUCTION WORK | PROVIDE PERMITS AND CITY APPROVED PLANS FOR BUILDING WORK PERFORMED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PRV FLOOR DRAIN WITH METAL STR | NO FLOOR DRAINS WITH METALLIC GRADE LOCATED IN BASEMENT | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
REMOVE | UNSANITARY CONDITIONS DETRIMENTAL TO HEALTH THROUGHOUT 7.28.060 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
SWING JOINT FOR HOTWATER PIPE | ELEVATED HOT WATER TANK DOES NOT HAVE PRESSURE TANK INSTALLED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PERMIT NOT POSTED AT SITE | INTERIOR REHABBING AT TIME OF INSPECTION; MULTIPLE PERMITS NOT POSTED AT TIME OF INSPECTION. | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
INSPECT CONSTRUCTION WORK | RECENTLY REPLACED REAR PORCH (PERMIT #100752849, ISSUED 3/27/2018); NEWLY BUILT GARAGE (PERMIT #100758428, ISSUED 4/24/2018); FRONT FACADE REPLACEMENT (PERMIT #100765623, ISSUED 6/5/2018); AND INTERIOR AND EXTERIOR RENOVATIONS PER PERMITS #100751853, ISSUED & #100751750, ISSUED 3/14/2018). SUBJECT TO FIELD INSPECTIONS AND FINAL APPROVAL. | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, BASEMENT, AND STOREFRONT. UNVERIFIED DETECTORS AND CONDITIONS. | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN PLUMBING PERMIT FOR PLUMBING WORK TO BE PERFORMED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
DWELLING CLEAN AND SANITARY | EXCESSIVE OVER STOCKING OF MERCHANDISE/GOODS IN GARAGE CAUSING A FIRE HAZARD 14X-1-103 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE | AISLES REDUCED IN COMMERCIAL SPACE BELOW THE REQUIRED MINIMUM OF 36" 14B-10-1018.1 DANGEROUS AND HAZARDOUS | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | THERE IS A TOTAL LACK OF FIRE SEPARATION IN THE BASEMENT CEILING AND COLUMNS AND BEAMS 14B-6-605.4 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PROVIDE PLANS AND PERMITS FOR THE FOLLOWING 1.THERE IS NEW STRUCTURAL (NEVER JOISTS AND STEEL COLUMNS) IN BASEMENT 2.THERE IS A NEW BUILDOUT OF THE 2ND FLOOR DWELLING UNIT SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO BASEMENT AND 2ND FLOOR DWELLING UNIT OR RESTORE THE BUILDING TO THE ORIGINAL STATE 14A-4-401.1 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | REPLACE ALL FITTINGS ON THE FRONT EXTERIOR FIXTURES WHICH ARE NOT LISTED FOR DAMP AND WET LOCATIONS (TAKE ALL FITTINGS) | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | INSTALL ALL REQUIRED ILLUMINATION THROUGHOUT THE PROPERTY SPECIFICALLY AT THE SIDE EGRESS OF THE GARAGE | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE INCREASE PROPER SIZE | THREE COMPARTMENT SINK IN REAR WASTE PIPING IS UNDERSIZED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE | SUMP CATCH BASIN LID IN REAR OF BASEMEN T NOT SEALED 18.29.712.3.2 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PROVIDE INDIRECT WASTE CONNECT | NO DRIP PAN FOR IS INSTALLED FOR OVERHEAD HOT WATER TANK | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
PRV DISCHARGE PIPE FROM PRV | NO DISCHARGE PIPE FROM HOT WATER TANK EMERGENCY TEMPERATURE CONTROL RELIEF VALVE IS INSTALLED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
INSTALL GFCI'S | INSTALL GFCI PROTECTION TO ALL REQUIRED RECEPTACLES THROUGHOUT THE BUILDING SPECIFICALLY IN THE UNFINISHED BASEMENT IN THE GARAGE AND IN THE 2ND FLOOR BATHROOM FOR SHOWER LIGHTS D&H | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | EMPLOY LICENSED AND BONDED PLUMBING CONTRACTOR FOR PLUMBING WORK TO BE PERFORMED TO ADDRESS PLUMBING VIOLATIONS | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
REPAIR FENCE | REAR STEEL FENCE OVER 5' (ROUGHLY 10FT) REMOVE, REDUCE HEIGHT OR OBTAIN PERMIT TO KEEP AS IS 14A-4-404.7 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD ADDITIONAL RE RECEPTACLES WHERE REQUIRED BY CODE SPECIFICALLY ON 2ND FLOOR UNIT IN THE KITCHEN FOR COUNTER TOP AND ISLAND RECEPTACLES | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
INDIRECT CONN.FOR WATER SUPPLY | ELEVATED HOT WATER TANK HAS NO WATER CHECK VALVE INSTALLED | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | REPAIR OR REPLACE ALL INOPERABLE LIGHTING FIXTURES THROUGHOUT THE PROPERTY SPECIFICALLY FIXTURE AT TOP OF BASEMENT STAIRS AND IN 2ND FLOOR UNIT BATHROOM | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
OPEN | ELEVATED INSTALLED HOT WATER TANK DOES NOT HAVE VACUUM BREAKER 18.29.504.2 | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | PROVIDE PLANS, PERMITS AND REQUIRED INSPECTIONS FOR WORK PERFORMED THROUGHOUT THE BASEMENT 1ST FLOOR COMMERCIAL UNIT AND 2ND FLOOR BUILD OUT OF RESIDENTIAL SPACE WHICH HAS BEEN PERFORMED WITHOUT PROPER AND PLANS PERMITS WITHOUT INSPECTIONS (14A-4-401/14A-4-404.1/ 14A-5-502.1/ 14A-5-502.3.3) D&H | 3814 W CHICAGO AVE | COMPLAINT | FAILED | View |