The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
DEFECTIVE SERVICE | DEFECTIVE SERVICE 7 UNITS BUIDING SEVICE CONDUCTORS IN SE CABLE CONTRARY TO 14 E 338.10. BUILDING SERVICE DISCONNECTS EXCEED MAXIMUM OF 6 ALLOWABLE DISCONNECTS AS PER 14E 230.40 | 8131 S KINGSTON AVE | COMPLAINT | PASSED | View |
DEFECTIVE OUTLETS | DEFECTIVE OUTLETS WITH BURN MARKS IN BEDROOM OF 2N ALSO DEFECTIVE 240 VOLT OUTLET FOR STOVE IN UNIT 2N AND DEFECTIVE OUTLET IN LIGHT OVER BATHROOM SINK | 8131 S KINGSTON AVE | COMPLAINT | PASSED | View |
UNAPPROVED EM | REMOVE UNAPPROVED EMERGENCY LIGHTING SYSTEM INSTALLED WITH CORD WIRING | 8131 S KINGSTON AVE | COMPLAINT | PASSED | View |
GROUNDING RECEPTACLES | INSTALL GROUNDED OUTLET IN CABINET OF WASHROOM OF UNIT 2N | 8131 S KINGSTON AVE | COMPLAINT | PASSED | View |
ADD BRANCH CIRCUITS | PROVIDE AT LEAST 1 CIRCUIT FOR EVERY 500 SQURE FEET TO COMPLY WITH 14E 570.10 | 8131 S KINGSTON AVE | COMPLAINT | PASSED | View |