Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEAL DRAIN OPENING UNUSD FIXTR | 2" WASTE PIPE OPENINGS ARE NOT SEALED AT WALL BEHIND WASHING BOWL SINKS D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SOIL/WASTE,VENT PIPE MATRL | CORRIGATED WASTE PIPE IS INSTALLED AT BOTH LAVATORIES IN BATHROOMS | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PRV DISCHARGE PIPE FROM PRV | DRAIN PIPE FOR T&P VALVE AT HOT WATER HEATER IS NOT INSTALLED D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
OBTAIN PERMIT BEFORE SIGN WORK | SIGN READS' SAGA REMY HAIR, ETC SOUTH ELEVATION APPROXIMATE SIZE 20'X 6' 13-20-520 | 72 E 75TH ST | COMPLAINT | FAILED | View |
REPAIR DEFECTIVE DOWNSPOUT | DOWNSPOUT IS NOT CONNECTED AT REAR OF COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
DEFECTIVE OUTLETS | REPAIR OR REPLACE DEFECTIVE RECEPTACLES THROUGHOUT THE PROPERTY SPECIFICALLY IN REAR STORAGE ROOM | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PROVIDE | NO TEMPERATURE MIXING CONTROL VALVES AT LAVATORIES 18.29.607.1.1 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
FIRE EXTNGSHR RECHARGE & TAG | 72 E 75TH ST | COMPLAINT | FAILED | View | |
CORRODED CONDUIT & EQUIP | REMOVE ALL CORRODED AND DETERIORATED CONDUITS BOXES AND EQUIPMENT SPECIFICALLY IN REAR STORAGE AREA | 72 E 75TH ST | COMPLAINT | CLOSED | View |
ADD RECEPTACLES | ADD ADDITIONAL RECEPTACLES IN ORDER TO ELIMINATE OVER USE OF EXTENSION CORDS D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
RESET LOOSE FIXTURE | PVC LAUNDRY TUB IS NOT ANCHORED SECURELY IN COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
REPAIR INTERIOR WALLS/CEILING | VARIOUS CEILING TILES ARE STAINED 14X-3-304.3 | 72 E 75TH ST | COMPLAINT | CLOSED | View |
WORKING SPACE | PROVIDE PROPER WORKING SPACE IN FRONT OF ALL ELECTRICAL EQUIPMENT SPECIFICALLY IN ELECTRICAL CLOSET | 72 E 75TH ST | COMPLAINT | CLOSED | View |
INSTALL COVERS | INSTALL COVERS ON ALL OPEN JUNCTION BOXES AND ON DEVICES WHERE COVERS ARE MISSING SPECIFICALLY AT SWITCH FOR THE REAR STORE ROOM D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN PLUMBING PERMIT FOR PLUMBING WORK TO BE PERFORMED | 72 E 75TH ST | COMPLAINT | CLOSED | View |
OBSTRUCTIONS IN EXIT WAY | REAR MARKED EXIT-30" DOOR LEADING TO A 32" DOOR MINIMUM 36" DOOR REQUIRED 14X-5-505.1.2 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PROPER SIZE OCP | PROVIDE PROPER OVER CURRENT PROTECTION FOR ALL PANELS AND BRANCH CIRCUITS D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SOIL/WASTE,VENT PIPE MATRL | 2" PVC DRAIN PIPE IS INSTALLED AT ALL HAIR WASHING BOWL SINKS THROUGHOUT COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
RESTORE EXIT AND EM | REPAIR OR REPLACE ALL INOPERABLE EXIT SIGNS AND EMERGENCY LIGHTING FIXTURES THROUGHOUT ENTIRE PREMISES D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
NO GASOLINE(LPG) STORAGE | REMOVE CAR TIES AND GAS CAN FROM CMU ADDITION AT NE ELEVATION 15-26-540 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
DEFECTIVE FIXTURES | REPAIR OR REPLACE ALL DEFECTIVE LIGHTING FIXTURES THROUGHOUT SPECIFICALLY ALL GENERAL LIGHTING WHICH IS FLICKERING AND EXTERIOR LIGHTING FIXTURES ALONG ROOF LINE WHERE COVERS OPEN TO THE ENVIRONMENT AND COMPROMISING THE LISTING OF THE FIXTURE D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
WORK NOT ALLOWED | REMOVE ALL PARTITIONS AND FIXTURES INSTALLED IN COMMERCIAL SPACE WITH OUT A PERMIT 14A-4-401 | 72 E 75TH ST | COMPLAINT | CLOSED | View |
LISTED FOR USE TEMP & LOCATION | REPLACE ALL BRANCH CIRCUIT BREAKERS WHICH ARE NOT LISTED FOR USE BY SERVICE PANEL MANUFACTURE D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SECURE RACEWAY | SECURE AND SUPPORT ALL SURFACE MOUNTED CONDUITS THROUGHOUT THE ENTIRE STORE D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
CLOSE BOX OPENINGS | INSTALL KO FILLERS IN ALL UNUSED OPENINGS IN JUNCTION BOXES THROUGHOUT SPECIFICALLY IN REAR STORAGE AREA | 72 E 75TH ST | COMPLAINT | CLOSED | View |
REPAIR EXTERIOR WALL | EXTERIOR MASONRY WALL-WASHED OUT MORTAR JOINTS/STEP FRACTURES IN VARIOUS AREAS AT ALL ELEVATIONS 14X-3-303.1.1 | 72 E 75TH ST | COMPLAINT | CLOSED | View |
CARB MONOX DETECT IN RESID | MISSING CARBON MONOXIDE BY HOT WATER TANK AT NW ELEVATION 14X-5-504.9 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
NO KEY TO USE EXIT DOOR | FRONT (SOUTH EGRESS IS LOCKET AT ALL TIMES AND HAS AN ELECTRONIC DOOR RELEASE IN CASE OF EMERGENCY OR POWER LOSS DOOR MUST OPEN WITHOUT KEY OR SPECIAL KNOWLEDGE IN LIEU OF A PANIC BAR OR HANDLE 14X-5-505.1.2.2 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS NOT PROPERLY TAGGED 14X-5-504.5 D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PLANS & PERMITS REQ - CONTRCTR | SUBMIT PLANS AND OBTAINS PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO COMMERCIAL SPACE OR RESTORE THE BUILDING TO THE ORIGINAL STATE THERE WAS AN INTERIOR BUILDOUT TO FORM OFFICES RESTROOMS AND HAIR SALON STATIONS THE ORIGINAL SECONDARY MEANS OF EGRESS AT NORTH ELEVATION WAS BRICKED IN AND A CMU ADDITION WAS ERECTED AT NE ELEVATION THAT HAS AN UNDERSIZED SECONDARY MEANS OF EGRESS 14A-4-401.1 | 72 E 75TH ST | COMPLAINT | CLOSED | View |
LICENSED BONDED PLMBG CONTRCTR | EMPLOY LICENSED AND BONDED PLUMBING CONTRACTOR FOR PLUMBING WORK TO BE PERFORMED TO ADDRESS PLUMBING VIOLATIONS | 72 E 75TH ST | COMPLAINT | CLOSED | View |
INDIRECT CONN.FOR WATER SUPPLY | NO IN LINE CHECK VALVE IS INSTALLED AT WATER SUPPLY AT HAIR WASHING BOWLS THROUGHOUT COMMERCIAL LOCATION D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SEAL DRAIN OPENING UNUSD FIXTR | PVC WASTE DRAIN PIPE IS NOT CONNECTED AT HAIR WASHING BOWL ON EAST SIDE OF BUILDING IN COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SOIL/WASTE,VENT PIPE MATRL | PVC WASTE PIPE IS INSTALLED AT LAUNDRY TUB IN COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PRV BALLCOCK,VB,OR AIR GAP | NO VACUUM BREAKER IS INSTALLED AT LAUNDRY TUB SINK IN COMMERCIAL LOCATION D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
PROVIDE OPEN FRONT TOILET SEAT | NO OPEN FRONT TOILET SEATS ARE INSTALLED AT BOTH BATHROOMS AT COMMERCIAL LOCATION | 72 E 75TH ST | COMPLAINT | CLOSED | View |
DEFECTIVE SERVICE | SUPPORT SERVICE RISER AND MAST ON THE NORTH EXTERIOR ELEVATION/PROVIDE I-LINE DIAGRAMS AND LOAD CALCULATIONS FOR ALL PANELS AND SUB PANELS TO INSURE PROPER OVER CURRENT PROTECTION OF PANELS AND BRANCH CIRCUITS D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
REMOVE MINI-BREAKERS | REMOVE MINI BREAKERS FROM ALL PANELS AND SUB PANELS D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
EXPOSED WIRING | REMOVE EXPOSED WIRING FROM REAR STORAGE ROOM FEEDING THE BELL TRANSFORMER AND AT THE REAR EXTERIOR CAMERA FEED ON THE EAST ELEVATION D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
UNAPPROVED CORDS | REMOVE ALL EXTENSION CORDS TO PERMANENT ELECTRICAL EQUIPMENT THROUGHOUT INCLUDING CORD FEEDING EXTERIOR REAR CAMERA WHERE CORD IS DAMAGED SEVERELY DUE TO RUNNING THROUGH DOOR AND JAMB REMOVE CORD FROM RECEPTACLE THAT HAS AN OPEN SPLICE OF CLASS I WIRING FOR BELL TRANSFORMER D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
INSTALL GFCI'S | PROVIDE REQUIRED GFCI PROTECTION FOR ALL REQUIRED AREAS INCLUDING NEAR SINKS AND FOR EXTERIOR RECEPTACLES D&H | 72 E 75TH ST | COMPLAINT | CLOSED | View |
OUTDOOR ARMORED CABLE | REMOVE ARMORED CABLE ON THE FRONT EXTERIOR OF THE PROPERTY UNDER CANOPY | 72 E 75TH ST | COMPLAINT | CLOSED | View |
SEE INSPECTOR COMMENTS | PROVIDE ELECTRICAL PERMIT IN ORDER TO CORRECT ALL ELECTRICAL VIOLATIONS (14A-4-404.6) | 72 E 75TH ST | COMPLAINT | CLOSED | View |