The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
WORKING SPACE | DEBRIS,STORAGE, CLUTTER IN FRONT OF MAIN SERVICE DISCONNECT AND PANELS THROUGHOUT VARIOUS ELECTRICAL PANELS COMPLETELY INACCESSIBLE DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAYS | CONDUITS NOT CONNECTED TO BOXES OR FITTINGS VARIOUS AREAS REAR AREA ENSURE GROUND CONTINUITY THROUGHOUT DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
PROVIDE ALL REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES,WIRE,DEVICE AND EQUIPMENT NEW SERVICE NO INSPECTIONS NEW ELECTRICAL THROUGHOUT PREMISES NO PERMITS INSUFFICIENT PERMITS NO INSPECTIONS (14A-5-505.2) | 5812 S STATE ST | COMPLAINT | FAILED | View | |
RESTORE EXIT AND EM | UNAPPROVED BROKEN, UNMAINTAINED, INSUFFICIENT BATTERY LIGHTS AND EXIT SIGNS THROUGHOUT DANGEROUS AND DANGEROUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
CORD WIRED EQUIPMENT | DAMAGED SPLICED EQUIPMENT CORDS AT PORTABLE CAR WASH VACCUMS AND VARIOUS AREAS REMOVE WHERE REQUIRED DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
CORD TO FIXTURE | UNAPPROVED CORD WIRED LIGHT FIXTURES AT CEILING AREAS REMOVE WHERE REQUIRED | 5812 S STATE ST | COMPLAINT | FAILED | View |
PROVIDE DROP CEILING INSPECTION OFFICE AREA AND WHERE REQUIRED (14A-5-505.2) | 5812 S STATE ST | COMPLAINT | FAILED | View | |
EXPOSED WIRING | OPEN WIRING VARIOUS AREAS THROUGHOUT REMOVE WHERE REQUIRED DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
PANEL SCHEDULES | INSUFFICIENT PANEL SCHEDULES | 5812 S STATE ST | COMPLAINT | FAILED | View |
EXPOSED WIRING FIXTURES | OPEN WIRING VISIBLE AT VARIOUS CEILING LIGHT FIXTURES AT WASH AREA AND VARIOUS AREAS THROUGHOUT DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLE OUTLETS TO ELIMINATE EQUIPMENT AND EXTENSION CORDS THROUGH CEILING TILES TO PREVENT EXCESSIVE EXTENSION CORDS DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
ALL INTERIOR EXTERIOR LIGHT FIXTURES LIGHT FIXTURE RETROFITS AND SIGNS MUST BE LISTED AND IDENTIFIED FOR USE (14E-1-110.3) | 5812 S STATE ST | COMPLAINT | FAILED | View | |
DEFECTIVE SERVICE | MAIN SERVICE DISCONNECT OVER 5' FROM POINT OF ENTRY ENSURE SERVICE IN APPROVED CONDITION | 5812 S STATE ST | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | INSUFFICIENT SUPPORTED LIGHT FIXTURES THROUGHOUT OPEN CEILING AREAS SECURE FIXTURES IN APPROVED MANNER WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
LIGHT SWITCHES OVER 6'7' AT FRONT CAR WASH AREA (14E-4-404.8) | 5812 S STATE ST | COMPLAINT | FAILED | View | |
INTERIOR FINISH FIRERESISTANCE | REMOVE ALL WALLS CONSTRUCTED OF PLYWOOD MATERIAL AT REAR OF PROPERTY WHICH IS CURRENTLY USED AS WORKSHOP (14B-8-803.1.1) | 5812 S STATE ST | COMPLAINT | FAILED | View |
UNAPPROVED DAMAGED SPLICED EXTENSION CORDS VARIOUS AREAS CORDS THROUGH CEILING AT FRONT OFFICE AREA DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View | |
INSTALL GFCI'S | MISSING GFCI PROTECTION AT WET LOCATIONS AND THROUGHOUT GARAGE AREA INSTALL WHERE REQUIRED | 5812 S STATE ST | COMPLAINT | FAILED | View |
OBTAIN PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES,WIRE,DEVICES AND EQUIPMENT NEW SERVICE NO INSPECTIONS NEW ELECTRICAL THROUGHOUT PREMISES NO PERMITS INSUFFICIENT PERMITS, NO INSPECTIONS (14A-4-404.6) | 5812 S STATE ST | COMPLAINT | FAILED | View | |
PROPER SIZE GRD ELECTRODE COND | NO VISIBLE WATER GROUND ENSURE SERVICE GROUNDED IN APPROVED NO VISIBLE WATER GROUND ENSURE SERVICE GROUNDED IN APPROVED MANNER | 5812 S STATE ST | COMPLAINT | FAILED | View |
INSTALL COVERS | OPEN BOXES VARIOUS AREAS THROUGHOUT PREMISES CLOSE WHERE REQUIRED DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
NO GASOLINE(LPG) STORAGE | EXCESSIVE STORAGE OF PROPANE TANKS AT REAR OF PROPERTY WORK SHOP AREAS (14X-5-505.1.2.1) | 5812 S STATE ST | COMPLAINT | FAILED | View |
DEFECTIVE DISTRIBUTION | LOOSE PANEL COVERS AT MAIN SERVICE DISCONNECT AREA ENSURE DISTRIBUTION IN APPROVED CONDITION THROUGHOUT DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR REQ, NONRESDNTL | UNABLE TO VERIFY WORKING FIRE EXTINGUISHERS THROUGHOUT PROPERTY (14X-5-504.5) | 5812 S STATE ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | LIGHT FIXTURES, BOXES,FITTINGS, RACEWAYS, DEVICES, EQUIPMENT AT CAR WASH AREAS MUST BE IDENTIFIED FOR USE AND SUITABLE FOR WET LOCATIONS (14E-1-110.3) DANGEROUS AND HAZARDOUS | 5812 S STATE ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS AND PERMITS REQUIRED FOR CONSTRUCTION OF OFFICE SPACES AND REAR WORKSHOP WHICH HAS BEEN CONSTRUCTED OF PLYWOOD NONE LOAD BEARING WALLS BUT NOT LIMITED TO CORRECTION OF ALL BUILDING CODE VIOLATIONS (14A-4-401.1) | 5812 S STATE ST | COMPLAINT | FAILED | View |