DEFECTIVE FEEDER | ES CABLE SEVERELY DETERIORATED & IMPROPERLY ATTACHED | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
PROPER SIZE GRD ELECTRODE COND | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View | |
CIRCUIT ONE UNIT ONLY | 2 METER SERVICE FOR 3 DU'S- INTERMINGLING AND LACK OF PUBLIC PANEL | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
ADD BRANCH CIRCUITS | 2ND FLOOR TENANT PANEL HAS 1-20 AMP CIRCUITS ONLY | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
PROPER SIZE OCP | 1ST FLOOR PANEL 25 ADD 30 AMP BRANCH CIRCUITS #12 WIRE (D & H) | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
EXPOSED WIRING FIXTURES | BASEMENT | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
INSTALL COVERS | BASEMENT OPEN BOXES & RECEPTACLE COVERS MISSING | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
CLOSE BOX OPENINGS | PANELS | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
SEC FEEDER/BRANCH | BASEMENT FEEDS | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
MULTIPLE CONDUCTOR TERM | 2 CONDUCTOR TERMINATED UNDER SINGLE FUSE | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
REMOVE EXPOSED CABLE | ROMEX IN KITCHENS | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
DEFECTIVE DISTRIBUTION | B-PHASE JUMPERED OUT - (NO B-PHASE) NEUTRAL TAPPED NO GROUND (D & H) | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI KITCHENS & BATHS | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |
DEFECTIVE LIGHTING SERVICE | 8602 S EXCHANGE AVE | COMPLAINT | PASSED | View |