Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR EXTERIOR WALL | MISSING SECTIONS OF SIDING. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | 1. 6X6 COLUMNS RESTING ON CONCRETE BLOCKS SET ON TOP OF CONCRETE SLAB.2. FOUNDATION STATUS UNKNOWN.3. 6X6 COLUMNS OVER NOTCHED.4. LOOKOUT BEAMS OVER SPANNED.5. LOOKOUT BEAMS MISSING TIE STRAPS.6. INADEQUATE BEAM TO COLUMN CONNECTION.7. STRINGERS INADEQUATELY SUPPORTED.8. STAIR TREADS TOO SMALL.9. 2X8 JOIST OVER SPANNED.10. GUARD RAILS TOO LOW, LOOSE AND DEFLECT.11. PLANS AND PERMIT REQUIRED. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | MISSSING GUARDRAIL. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | 1ST FLOOR - BROKEN WINDOW PANE. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO RESPONSE, UNVERIFIED DETECTORS, CONDITIONS AND OCCUPANCY. UNABLE TO VERIFY COMPLAINT OF DEBRI BLOCKING EGRESS. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | NO OWNER'S / MANAGEMENT SIGN POSTED. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | NORTH BASEMENT EXTERIOR DOOR FRAME; BROKEN. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | NORTH EXTERIOR DOOR FRAME TRANSOM PANE; BROKEN. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
PROVIDE DEADLOCK FOR ENTRANCE | NORTH EXTERIOR DOOR; NO LOCK. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | POST OWNERSHIP ON BUILDING. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
EXPOSED WIRING | 1ST FLR.BED ROOM CEILING; EXPOSED WIRING. BASEMENT APARTMENT KITCHEN CEILING; EXPOSED WIRING | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 1ST FLR.BATHROOM CEILING DRYWALL BUCKLING,KITCHEN STUCCO CEILING BUCKLING. BASEMENT APARTMENT, BATHROOM WALL; DRYWALL MILDEW AND WATER DAMAGE. REAR AREA OF BASEMENT PARTITION WALL EXPOSED WOOD STUDS. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR FLOOR | 1ST FLR.KITCHEN FLOOR TILES; BROKEN. BASEMENT APARTMENT FLOOR AND SUB-FLOOR; BROKEN AND BUCKLING UP. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
MICE/RODENTS | BUILDING INFESTED WITH MICE. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | BASEMENT BOILER AREA; JUNK AND DEBRIS. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR GUTTER & DOWNSPOUT | NORTH PORCH GUTER RUSTED,DOWNSPOUT MISSING. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | SOUTH BASEMENT STAIR; GUARD RAIL MISSING. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCH; NO FOOTINGS,HEADER BOARD ROTTED,DECK BOARDS BROKEN AND ROTTED,LOOKOUTS ROTTED,LOOKOUT AND UPRIGHT BUTT JOINTS,GUARD RAILS UNDER SIZE,ROOF AND ROOF LOOKOUT ROTTED,TREADS WORN AND SPLIT,STRINGER PULLING AWAY FROM THE WALL. [SUBMIT PLANS AND PERMITS TO REPLACE]. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | ENCLOSE PORCH EXTERIOR WALLS WOOD FRAMING AND WOOD SIDING; ROTTED AND BROKEN. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 3539 W./ 1ST FLOOR / BATHROOM - CEILING BUBBLING, WATER DAMAGE ALONG WALL, VANITY MIRROR LOOSE WITH WATER DAMAGE. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR STAIR | MISSING HANDRAILS. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | MISSING HANDLE. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO 2ND AND 3RD FLR. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | 1ST FLR.BEDROOM DOOR KNOB; STRIP. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPLACE D&H PORCH | 3539 W./ REAR OF HOUSE / 3 STORY PORCH SYSTEM - COLUMNS ERECTED ON SERVICE WALK (WITH NO BASES) FOUNDATION STATUS UNKOWN. COLUMNS ARE ONLY 4 X 4 WITH INADEQUTE HALF-LAP (OR BUTT) JOINTS. LEDGER BOARD ATTACHED WITH NAILS AND SCREWS TO EXTERIOR WALL ONLY. FLOOR BOARDS ROTTING. STRINGERS ARE INADEQUATLEY SUPPORTED AT COLUMNS. RAIL SECTIONS ARE LOOSE, PULLING AND OR BROKEN. PORCH ROOF EXPOSED SHEATHING WORN AND OR ROTTING. TREADS ARE CRACKED, WORN OUT. ENTIRE PORCH STRUCTURE IS UNSTABLE. PLANS AND PERMITS REQUIRED TO REPLACE. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |
REPAIR BALCONY | 3539 W./ FRONT OF BUILDING / BALCONY - ROOF & EAVES - ROTTING SHEATING AND FACIA, SUPPORT COLUMNS WORN WITH PAINT CHIPPING. | 3539 W GRENSHAW ST | COMPLAINT | FAILED | View |