Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PRV RECEIVER | 450 PSIG FOR THREE 1-1/2 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR ONE 2-1/2 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR THREE 1-TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR ONE 3-3/4 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
TERMINATE VENT LINE | FOR ALL ABOVE UNITS. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PRV HIGH SIDE | FOR ONE TECUMSEH 1/2 HP COMPRESSOR LOCATED IN FRONT BASEMENT, FOR ONE COPELAND 1 HP COMPRESSOR LOCATED IN FRONT BASEMENT | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
RECONNECT VENT LINE | FOR ONE COPELAND 5 HP COMPRESSOR LOCATED IN BASEMENT | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PRV HIGH SIDE | FOR ONE COPELAND 2 HP COMPRESSOR LOCATED IN FRONT PART OF BASEMENT-6" X 12" RECEIVER. FOR TWO COPELAND 3 HP. COMPRESSORS LOCATED ON NORTHSIDE MIDDLE AND REAR BASEMENT-6" X 18" RECEIVERS. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
RECONNECT VENT LINE | FOR ONE COPELAND 5 HP COMPRESSOR LOCATED IN BASEMENT | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450 PSIG FOR THREE 1-1/2 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR ONE 2-1/2 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR THREE 1-TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. 450 PSIG FOR ONE 3-3/4 TON COPELAND REMOTE REFRIGERATION UNIT LOCATED IN BASEMENT. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
TERMINATE VENT LINE | FOR ALL ABOVE UNITS. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PROVIDE | PROVIDE PANIC HARDWARE ON ALL EXIT LOCATIONS. (13-100-260) | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
ILLUMINATE PUBLIC STAIR/HALL | REPAIR AL DEFECTIVE EXIT SIGNS (NO LAMPS). | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
COVER OUTLETS AND JBS | PROVIDE COVERS ON ALL OPEN ELECTRICAL BOXES. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
REPLACE DEFECTIVE WASTE PIPING | REPAIR BROKEN PLUMBING PIPE IN THE BASEMENT. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
REMOVE STAGNANT WATER BSMT | REMOVE STAGNANT WATER FROM BASEMENT FLOOR. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | PROVIDE A STORAGE ENCLOSER 5/8 DRYWALL ON ALL WALLS/CEILING. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
CLASS B DOOR IN STAIRWELL | PROVIDE A CLASS B DOOR WITH FRAME & CLOSER AT THE TOP OF THE BASEMENT STAIRS (ALL DOORS MUST BE 11/2 OR 90 MIN - FIRE RATED. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
MAINTAIN EXIT SIGN ILLUMINATED | EXIT SIGN BULBS ARE DEFECTIVE. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | BASEMENT CEILING DRYWALL HAS MISSING SECTIONS FIRE RATING BREACHES. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
PLANS & PERMITS REQ - CONTRCTR | AQUIRE PLANS AND PERMITS FOR BUT NOT LIMITED TO INTERIOR ALTERATION AT BASEMENT, NEW WOOD BEAM (LOAD BEARING) WITH STEEL SUPPORTING (ADJUSTABLE) COLUMNS. | 9027 S COMMERCIAL AVE | PERIODIC | CLOSED | View |
MAINTAIN EXIT SIGN ILLUMINATED | EXIT SIGNS BULBS ARE DEFECTIVE. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | ACQUIRE PLANS AND PERMITS FOR BUT NOT LIMITED TO INTERIOR ALTERATION AT BASEMENT, NEW WOOD BEAM (LOAD BEARING) WITH STELL SUPPORTING (ADJUSTABLE) COLUMNS. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR ONE COPELAND 2 HP AND TWO COPELAND 3 HP COMPRESSORS LOCATED IN BASEMENT FRONT ,MIDDLE NORTH AND REAR NORTH. | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PRV HIGH SIDE | FOR ONE COPELAND 2 HP COMPRESSOR LOCATED IN FRONT PART OF BASEMENT-6" X 12" RECEIVER. FOR TWO COPELAND 3 HP. COMPRESSORS LOCATED ON NORTHSIDE MIDDLE AND REAR BASEMENT-6" X 18" RECEIVERS. | 9027 S COMMERCIAL AVE | PERIODIC | PASSED | View |
CONNECT VENT LINE | FOR ONE COPELAND 2 HP AND TWO COPELAND 3 HP COMPRESSORS LOCATED IN BASEMENT FRONT ,MIDDLE NORTH AND REAR NORTH. | 9027 S COMMERCIAL AVE | PERIODIC | PASSED | View |
OUTDOOR ARMORED CABLE | REPAIR OR REPLACE HANGING SEALTIGHT, AT THE BUSINESS | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE | AISLE REDUCED NEAR CASHIER AREA 17" STORE SIDE AND RESTAURANT SIDE 22" AT CASHIER OPENING DANGEROUS AND HAZARDOUS 14-B-10-1018.1 14B-10-1018.4 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN PERMIT FOR PLUMBING WORK TO BE PERFORMED | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE | BATHROOM LAVATORY SINK DOES NOT HAVE HOT WATER SCOLDING PREVENTIVE DEVICE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | COVER IS MISSING ON THE PANEL IN THE FIRST FLOOR KITCHEN AREA BEHIND THE SHELVING UNIT AND IN THE MEZZANINE AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SPLICE IN CORD | REMOVE CORDS THAT ARE PLUGGED IN THROUGHOUT THE ENTIRE BUILDING WITH SPLICES DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | ARMORED CABLE IS BEING USED IN THE FREEZER AREA ON THE FIRST FLOOR NEAR THE OFFICE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE SOIL PIPING | GREASE BASIN DOES NOT VENTING SYSTEM PIPING AT BASEMENT REAR STOP USING ILLEGAL VENTING FITTING | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO BUILDING 14A-4-401.1 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE INDIRECT WASTE CONNECT | OVERHEAD 3/4 PVC CONDENSATION DRAIN PIPING IN BASEMENT DIRECTLY TIED INTO WASTE PIPING | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
NEED TO REMOVE CORDS GOING THROUGHOUT THE ENTIRE DROP CEILING TILES ON THE FIRST FLOOR OF THE STORE 14E-400.12 (2) (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View | |
PROVIDE | PROVIDE PANIC HARDWARE ON ALL EXIT LOCATION(13-100-260) | 9027 S COMMERCIAL AVE | PERIODIC | FAILED | View |
PROVIDE | REMOVE CEILING TILES TO PROVIDE ACCESS FOR FULL INSPECTION 2-22-020, 2-22-040 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO INTERIOR TO 2ND FLOOR UNABLE TO VERIFY OCCUPANCY AND DETECTORS | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL FRONT STRESS FRACTURES AT STUCCO WALL 14X-3-303.6 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REPAIR ROOF | FRONT CLAY TILE FRONT MISSING SECTIONS 14X-3-303.8 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS MISSING UPDATED TAGS DANGEROUS AND HAZARDOUS 14X-5-504.5 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | MISSING CARBON MONOXIDE DETECTORS THROUGH-OUT DANGEROUS AND HAZARDOUS 14X-5-504.9 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE | LIQUOR SIDE PLATFORM 11 1/2" HIGH TRIP HAZARD AND APPROXIMATE 10'X30' UNKNOWN FIRE RATING PLANS AND PERMIT REQUIRED DANGEROUS AND HAZARDOUS 14A-4-401.1 14X5-505.9.1.1 14X-5-502.3.3 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | ALL SECONDARY MEANS OF EGRESS CHAIN PAD LOCK UNABLE TO ACCESS REAR, DANGEROUS AND HAZARDOUS 14X-5-505.1.2.2 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | 1ST FLOOR DOOR TO BASEMENT MISSING CLOSURE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | BASEMENT CEILING SOME SECTIONS-PLYWOOD COVERING ON JOIST, WATER DAMAGED HOLES AND EXPOSED JOIST FIRE SEPARATION COMPROMISED MUST BE INCLUDED IN PLANS AND PERMIT 14X-5-502.3.3 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
STRUCTURAL MEMBER, PIER BLOCK | BASEMENT CEILING JOIST SOME AREAS WATER DAMAGE,FRACTURED AND SPILT JOIST TEMP 4X4 COLUMNS AT NORTH-WEST PORTION OF BASEMENT PROVIDE STRUCTURAL ENGINEER REPORT PLANS AND PERMIT REQUIRED FOR REPAIRS 14X-3-304.2 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUBMIT STRUCT. ENG. RPT (INT.) | PROVIDE STRUCTURAL ENGINEER REPORT WITH PLANS AND PERMIT FOR ALL STRUCTURAL REPAIRS 14X-1-104 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | REMOVE ALL PARTIONS AND FIXTURES (INCLUDING PLUMBING AND ELECTRIC) INSTALLED IN THE BUILDING WITH-OUT PLANS AND PERMIT LOFT AREA REAR OF LIQUOR STORE WITH STORAGE AND MECHANICAL RESTAURANT LIQUOR STORE COMBINATION SOUTH SPACE ENTRY THROUGH LIQUOR STORE CASHIER AREA COMPLETE GUT-OUT 14A-4-401.1 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | EMPLOY LICENSED BONDED PLUMBING CONTRACTOR | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | BATHROOM LAVATORY AND TOILET WATER SUPPLY LINES ARE OF FLEXIBLE TUBING | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | NO OPEN FRONT TOILET SEAT USED ON TOILET IN BATHROOM | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PRV BALLCOCK,VB,OR AIR GAP | HOSE BIB AND HOSE DIRECTLY CONNECTED TO WATER SUPPLY SYSTEM IN BASEMENT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | FLEXIBLE WATER SUPPLY LINES AT HAND SINK LOCATED IN REAR OF STORE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | PVC WASTE AND VENT PIPING USED THROUGHOUT BASEMENT OVERHEAD | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
RMV DFT PIPE,FITTING,FIXTURE | RUBBER FERNCO USED TO CONNECT WASTE PVC PIPING IN BASEMENT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE ADEQUATE SUPPORT | SUSPENDED PLUMBING WATER AND WASTE PIPE THROUGHOUT BASEMENT HANGING AND UNSECURED TO STRUCTURE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PROVIDE INDIRECT WASTE CONNECT | 2" WASTE PIPE FOR CONDENSATION OF COOLERS OPEN TO AIR WITH NO P-TRAP CAUSING SEWER GAS TO ESCAPE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REMOVE | FLEXIBLE WATER SUPPLY LINES AT HOT WATER TANK IN BASEMENT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
STOP LEAKING WATER | LEAKING WATER COMING FROM CEILING IN BASEMENT FROM 1ST FLOOR COOLER IN REAR EAST EAST OF BUILDING | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WASTE PIPING | 4" CAST IRON WASTE PIPE HUBS ARE BROKEN AND CRACKED IN BASEMENT REAR AT STACK | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | 2" PVC AND RUBBER FERCO COUPLING ARE USED AT GREASE BASIN IN BASEMENT REAR AND FRONT OF BASEMENT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CLEAN CATCH BASIN | GREASE BASIN NEED CLEANING IN BASEMENT REAR AND FRONT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
STOP ODORS RPR DFT SEWAGE SYS | STOP SEWER AND BAD ODORS THROUGHOUT LOCATION | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PRV DISCHARGE PIPE FROM PRV | NO PIPING INSTALLED FOR HOT WATER TANK TMP VALVE LOCATED IN BASEMENT | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
OPEN | CORROSIVE ELEMENTS AT HOT WATER TANK IN BASEMENT WATER SUPPLY | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CLEAN CATCH BASIN | SUMP PIT BASIN NEED CLEANING AT GREASE BASIN | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
KEEP FIXTUR CLEAN AND SANITARY | UNSANITARY CONDITIONS THROUGHOUT LOCATION | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PRV CAST IRON COVER FOR BASIN | PLASTIC CATCH BASIN COVER NOT SEALED IN BASIN REAR FRONT CATCH BASIN | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
REMOVE | REMOVE CONDITIONS DETRIMENTAL TO HEALTH BEHIND WHERE FOOD IS BEING PREPARED AND SERVED IN FRONT RESTAURANT AND REAR OF STORE FREEZER | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUBMIT PLANS FOR PLUMBING PRMT | APPROVED PLUMBING PLANS FROM THE CITY OF CHICAGO BUILDINGS DEPARTMENT SHOULD BE ON SITE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | PLUMBING FIXTURES AND FOUNTAINS INSTALLED WITHOUT PERMIT OR PLANS THROUGHOUT LOCATION | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
RMV WATER,SOIL,WASTE,VENT | WATER SUPPLY WASTE, AND VENTING SYSTEMS ARE INSTALLED WITHOUT PERMIT OR PLANS THROUGHOUT LOCATION | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT TO CORRECT ELECTRICAL VIOLATIONS 14A-4-404.6 & 14A-4-404.6.1 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View | |
NEED CEILING TILE REMOVE IN THE FIRST FLOOR LIQUOR STORE FOR FULL INSPECTION OF THE ELECTRICAL SYSTEM IN THE CEILING 14A-5-501.2 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View | |
UNAPPROVED CORDS | EXCESSIVE USE OF EXTENSION CORDS THROUGHOUT THE STORE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CLOSE BOX OPENINGS | CLOSE HOLES IN THE BOXES AND PANELS THROUGHOUT THE ENTIRE STORE AND BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | INSTALL COVERS ON BOXES PROPERLY AND ONES THAT ARE MISSING ON BOXES THROUGHOUT THE ENTIRE STORE AND BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | INSTALL ADDITIONAL RECEPTACLES ON THE CEILING TILES TO EASE THE USE OF CORDS GOING THROUGH THE TILES | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
THE SERVICE SWITCH GEAR, PANELS AND METER BANKS IS ON THE MEZZANINE IN THE REAR OF THE LIQUOR STORE THAT CAN ONLY BE ACCESSED WITH A PORTABLE LADDER ( DANGEROUS AND HAZARDOUS) 14E-2-230,70 (2) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View | |
RESTORE EXIT AND EM | RESTORE THE EM SYSTEM TO WORKING CONDITION IN THE STORE AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SYSTEM III | INSTALL ADDITIONAL EM LIGHTS IN THE BASEMENT AREA OF THE LIQUOR STORE AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | BURNED AND DAMAGED RECEPTACLES THROUGHOUT THE ENTIRE STORE OF 9029 COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUPPORT OUTLET AND BOX | SUPPORT BOXES THROUGHOUT THE ENTIRE STORE AND BASEMENT AREA THAT ARE NOT SUPPORTED PROPERLY SUPPORT DISCONNECT IN THE THE FIRST FLOOR FREEZER AREA IN THE KITCHEN (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | EXPOSED WIRING IN THE FLOOR FREEZER AREA IN THE KITCHEN OF THE STORE AND THROUGHOUT THE BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
WORKING SPACE | PANEL IS BLOCKED BY SHELVING UNIT IN THE FIRST FLOOR KITCHEN AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PANEL SCHEDULES | MISSING LABELS FOR THE PANEL ON FIRST FLOOR IN THE KITCHEN AREA BEHIND THE SHELVING UNIT (DANGEROUS AND HAZARDOUS | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | NEED TO REPLACE PAINTED SWITCHES AND RECEPTACLES THROUGHOUT THE FIRST FLOOR LIQUOR STORE AND IN THE BASEMENT (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
INSTALL GFCI'S | MISSING GFCI RECEPTACLES IN THE REQUIRED LOCATIONS OF THE STORE AND BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | LIGHT FIXTURES IN THE FREEZER AREA ON THE FIRST FLOOR NEAR THE OFFICE ARE FILLED WITH WATER (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
ACCESS TO JBS | JUNCTION BOX ON THE MEZZANINE IS HALFWAY IN HALLWAY AND IN THE MECHANICAL ROOM (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAYS | ARMORED CABLE AND PIPE IS DISCONNECTED FROM BOXES THROUGHOUT THE BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
BOND AROUND FITTINGS | MISSING COLD WATER GROUND FOR THE SERVICE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
ABANDONED EQUIPMENT | REMOVE ABANDONED PIPE, WIRING AND ELECTRICAL APPARTUES IN THE BASEMENT AREA | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CORRODED CONDUIT & EQUIP | THERE IS RUSTED PIPES AND BOXES THROUGHOUT THE BASEMENT OF THE LIQUOR STORE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
DETERIORATED CONDUCTORS | CONDUCTORS IN THE BASEMENT AREA IS DETERIORATED AND NEEDS TO BE REPLACED (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | INSTALL ILLUMINATION IN THE BASEMENT AREA OF THE LIQUOR STORE | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | SUPPORT LIGHT FIXTURES PROPERLY TO THE BOXES IN THE BASEMENT OF THE LIQUOR STORE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
ARMORED CABLE | RUSTED AND DISCONNECTED ARMORED CABLE IN THE BASEMENT AREA OF THE LIQUOR STORE (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
GAP AT BOX WALL FINISH | BOXES IN THE BASEMENT HAVE GAPS BETWEEN THE CEILING AND THE WALL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
UNAPPROVED EM | PLASTIC EXIT SIGNS IN 9029 FIRST FLOOR RESTAURANT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SECURE RACEWAY | SUPPORT PIPE AND ARMORED CABLE PROPERLY IN THE BASEMENT AREA (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
NEED TO OBTAIN ELECTRICAL PLANS AND PERMITS FOR THE RENOVATION OF THE RESTAURANT AREA AT 9029 S COMMERCIAL 14A-4-404.6 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View | |
UNAPPROVED CORDS | EXCESSIVE USE OF EXTENSION CORDS IN THE ENTIRE AREA OF 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | NEED TO RESTORE EM LIGHTS TO WORKING CONDITION THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | MISSING COVERS THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | SUPPORT THE LIGHT FIXTURES THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
CORRODED CONDUIT & EQUIP | RUSTED BOXES THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
DETERIORATED CONDUCTORS | DETERIORATED WIRING THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SUPPORT OUTLET AND BOX | SUPPORT BOXES THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SPLICE IN CORD | CORDS THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL HAVE SPLICES (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
SECURE RACEWAY | PIPES THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL ARE NOT SUPPORTED PROPERLY (DANGEROUS AND HAZARDOUS) . | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
PANEL SCHEDULES | PANELS THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL ARE MISSING LABELS (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
TENANT ACCESS TO SERVICE | THE DISCONNECTS AND PANELS FOR THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL IS LOCATED ON AN INACCESSIBLE MEZZANINE IN THE LIQUOR STORE AT 9027 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | EXPOSED WIRING THROUGHOUT THE ENTIRE RESTAURANT AT 9029 S COMMERCIAL (DANGEROUS AND HAZARDOUS) | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | REMOVE ALL PARTIONS AND FIXTURES (INCLUDING PLUMBING AND ELECTRIC) INSTALLED IN THE BUILDING WITH-OUT PLANS AND PERMIT LOFT AREA REAR OF LIQUOR STORE STORAGE AND MECHANICAL RESTAURANT LIQUOR STORE COMBINATION SOUTH SPACE ENTRY THROUGH LIQUOR STORE CASHIER AREA COMPLETE GUT-OUT 14A-4-401.1 | 9027 S COMMERCIAL AVE | COMPLAINT | FAILED | View |