The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CARB MONOX DETECT IN RESID | THIS ROOMING HOUSE HAS NO CARBON MONOXIDE DETECTORS. DANGEROUS AND HAZARDOUS.SECTIN 14X-5-504.9 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PROVIDE | IF THIS RECOVERY HOUSE CAN ACQUIRE A LICENSE THEN A FIRE ALARM SYSTEM TIED TO THE CFD IS REQUIRED. PLANS AND PERMITS REQUIRED.SECTION 14B-7-701 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | THERE ARE NO PLANS, PERMITS OR ZONING CERTIFICATE, LICENSE FOR THIS ROOMING HOUSE / RECOVERY HOUSE.TO REMAIN A RECOVERY HOUSE A LICENSE MUST BE ACQUIRED AND UPGRADES BASED ON THE CITY'S BUILDING CODE MUST BE COMPLETED.SECTION 14A-401.1 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
DOOR SWING IN DIR. OF TRAVEL | THE REAR STAIRWELL AT THE 1ST FLOOR HAS A DOOR THAT SWINGS AGAINST THE DIRECTION OF EGRESS. DANGEROUS AND HAZARDOUS.SECTION 14X-5-505 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
ADDITIONAL EXIT | THE ATTIC STORAGE AREA HAS BEEN ALTERED INTO AN OCCUPIED BUNK HOUSE CONTAINING 12 BUNK BEDS ... ALL OCCUPIED. THERE IS ONLY 1 EXIT (REAR INTERIOR STAIRS) FROM THIS OVERCROWDED BUNK AREA. DANGEROUS AND HAZARDOUS.SECTION 14X-5-505.1.1 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | THERE ARE HOLES IN THE REAR INTERIOR STAIRWELL PLASTER WALLS.SECTION 14X-3-304.3 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR REQ, RESDNTL | THIS ROOMING HOUSE HAS NO FIRE EXTINGUISHERS. DANGEROUS AND HAZARDOUS.SECTION 14X-5-504.5 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
OVERCROWDING | THIS UNLICENSED RECOVERY HOUSE, IN ADDITION TO THE TWO-1ST FLOOR SLEEPING ROOMS, HAS 12 BUNK BEDS IN THE NON-DORMERED ATTIC SPACE. IT IS EXTREMELY OVERCROWING IN THIS ATTIC SPACE THAT HAS ONLY 1 MEANS OF EGRESS (RREAR). DANGEROUS AND HAZARDOUS.SECTION 14X-4-402.3 | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PROVIDE | INSTALL EXIT SIGNAGE FOR FRONT AND REAR EXITS ON THE 1ST FLOOR. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | INSTALL A CARBON MONOXIDE DETECTOR IN THE 1ST FLOOR KITCHEN. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
1ST FLOOR ... INTALL A SMOKE DETECTOR IN EVERY BEDROOM AND THE KITCHEN. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
CARB MONOX DETECT IN RESID | 1ST FLOOR ... NO CARBON MONOXIDE DETECTOR. | 2436 S ALBANY AVE | COMPLAINT | PASSED | View |
INSTALL SMOKE DETECTORS | 1ST FLOOR ... NO SMOKE DETECTORS. | 2436 S ALBANY AVE | COMPLAINT | PASSED | View |
PROVIDE | 1ST FLOOR ... NO EXIT SIGNS FOR FRONT / REAR EXITS. SECTION 10(13-160-750). | 2436 S ALBANY AVE | COMPLAINT | PASSED | View |
REQUIRED FIRE ALARM SYSTEM NOT INSTALLED. PREMISES USED FOR TRANSIENT RESIDENTIAL. (14E-7-760.180) DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
SYSTEM II | REQUIRED EMERGENCY LIGHTING SYSTEM NOT INSTALLED. OCCUPANCY USED FOR TRANSIENT RESIDENTIAL. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PROPER SIZE GRD ELECTRODE COND | NO VISIBLE WATER GROUND. ENSURE SERVICE GROUNDED IN APPROVED MANNER. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
VENT SYSTEM TO PRVNT BACK PRES | UNAPPROVED -S- TRAP WITH NO VENT AT 1ST FLOOR KITCHEN SINK. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | EXTERIOR LIGHT FIXTURES, BOXES, FITTINGS, RACEWAYS MUST BE SUITABLE FOR WET LOCATIONS. INTERIOR LIGHT SWITCH USED AT REAR EXTERIOR. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
INSTALL FIXTURES PROPERLY | TOILET AT 2ND FLOOR BATHROOM HAS A CLEARANCE OF ONLY 8" FROM WALL TO CENTER OF TOILET. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PERFRM STRUCT ENGINEER REPAIRS | MAJOR DEFLECTION IN ATTIC FLOOR. D&H | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
WORKING SPACE | DEBRIS, CLUTTER, STORAGE IN FRONT OF MAIN ELECTRICAL PANEL. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PRV DISCHARGE PIPE FROM PRV | MISSING WATER HEATER TEMPERATURE AND PRESSURE RELIEF VALVE DISCHARGE PIPING. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
UNAPPROVED OPEN LAMP LIGHT FIXTURE LOCATED IN BATHROOM SHOWER ZONE. (14E-4-410.10) DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
REPAIR PORCH SYSTEM | REAR WOODEN DECK WITH ROOF STRUCTURE- ENTIRE DECK FLEXES UNDER LIVE LOAD. STAIRS WITH INCORRECT RISER HEIGHTS. 4X4 COLUMNS RESTING ON CONCRETE BLOCKS, FOUNDATION STATUS IS UNKNOWN. NO PLANS OR PERMITS ON FILE | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
SEAL DRAIN OPENING UNUSD FIXTR | OPEN DRAIN AT ABANDONED KITCHEN SINK AT 2ND FLOOR. DANGEROUS AND HAZARDOUS. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
ADD RECEPTACLES | ADD RECEPTACLES WHERE REQUIRED THROUGHOUT PREMISES TO ELIMINATE THE VISIBLE EXCESSIVE USE OF EXTENSION CORDS. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANEOUS ELECTRICAL MODIFICATIONS THROUGHOUT. NO PERMITS. (14A-4-404.6) | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
PROVIDE | MISSING SAFE PAN TO WATER HEATER AT 2ND FLOOR. (18-29-504.8 THRU 504.8.2) | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | LIGHT FIXTURES MISSING COVERS, DAMAGED LIGHT FIXTURES VARIOUS AREAS. REPAIR / REPLACE WHERE REQUIRED. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | HAPHAZARDLY INSTALLED, INSUFFICIENTLY SUPPORTED FLEXIBLE METAL CONDUIT AT MAIN ELECTRICAL PANEL AREA. (14E-3-348.10) | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | CARBON MONOXIDE DETECTORS INOPERABLE. D&H | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | EXCESSIVE EXTENSION CORDS THROUGHOUT INTEROR AND EXTERIOR. SPLICED EXTENSION CORDS. CORDS BEHIND CABINETS. REMOVE WHERE REQUIRED. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS AND PERMITS REQUIRED FOR THE FOLLOWING:1. REAR WOODEN DECK WITH ROOF STRUCTURE2. THIS BUILDING WAS ORIGINALLY RESIDENTIAL, NOW IS AN UNLICENSED ALCOHOLICS ANONYMOUS/ HALFWAY HOUSE. PROVIDE PLANS AND PERMITS PENDING ZONING APPROVAL OR RESTORE TO ORIGINAL CONSTRUCTION.3. ATTIC WAS CONVERTED TO LIVING SPACE WITH 5 BUNK BEDS AND 2 TWIN BEDS.4. MAJOR DEFLECTION IN ATTIC FLOOR. D&H | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PROVIDE ALL REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANEOUS ELECTRICAL MODIFICATIONS THROUGHOUT. NO PERMITS. (14A-5-505.2) | 2436 S ALBANY AVE | COMPLAINT | FAILED | View | |
SUBMIT PLANS FOR PLUMBING PRMT | SPECIFICALLY ENTIRE PLUMBING SYSTEM HAS BEEN MODIFIED FROM ORIGINAL STATE WITHOUT PLANS PERMITS OR INSPECTIONS. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | SMOKE DETECTORS INOPERABLE. D&H | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | UNAPPROVED FLEXIBLE COPPER PIPING TO 2ND FLOOR WATER HEATER. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | OPEN BOX AT MAIN ELECTRICAL PANEL CEILING AREA. CLOSE WHERE REQUIRED. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
NO ENTRY | NO ACCESS TO 1ST FLOOR BATHROOM AT TIME OF INSPECTION. | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | BURNDT RECEPTACLES, DAMAGED RECEPTACLES, LOOSE RECEPTACLES VARIOUS AREAS. REPLACE DEVICES WHERE REQUIRED. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
DEFECTIVE SERVICE | SERVICE ENTRANCE CABLE UNSUPPORTED, FALLING OFF REAR EXTERIOR, POSSIBLY DAMAGED. DEBRIS AND CLUTTER LAYING ON TOP OF METER ENCLOSURE. METER ENCLOSURE POSSIBLY DAMAGED. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIRS FROM 1ST FLOOR TO ATTIC- STAIR TREADS AND INTERMEDIATE LAND IS LOOSE AND WEAK AND FLEXES UNDER LIVE LOAD. D&H | 2436 S ALBANY AVE | COMPLAINT | FAILED | View |