The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | FAID'S NOT TESTED | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A FIRE EXTINGUISHER IN MACHINE ROOM | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | I.D. FEED LOCATION FOR MAIN LINE DISCONNECT | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COVER OPENING'S IN MACHINE ROOM CEILING | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR/REPLACE EMERGENCY PHONE | 5700 S CICERO AVE | PERMIT | FAILED | View |
ARRANGE PERMIT INSP. | 5700 S CICERO AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MACHINE ROOM FAID TO OBTAIN A FLASHING HAT WHEN INITIATED. | 5700 S CICERO AVE | PERMIT | PASSED | View |
POST CURRENT CERTIF ESCALATOR | ALL ESCALATORS. | 5700 S CICERO AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | INSTALL PROPER COMB PLATES AT THE ENTRANCE AND EXIT OF THE ESCALATOR.(ALL ESCALATORS) EV018888. | 5700 S CICERO AVE | PERIODIC | PASSED | View |
TEST G & S PASS ELE | AND CWTS SAFTIES. (EV018889) | 5700 S CICERO AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | 1. PERFORM PRESSURE RELIEF TEST DATE W/TAG. 2. REPAIR OIL LEAK UNDER TANK. 18-30-010,13-20-120. (93269) | 5700 S CICERO AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | INSTALL SMOKES. | 5700 S CICERO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | REPLACE DISCONNECT ON CAR IN AREA 208 & 207. | 5700 S CICERO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PUT CAR IN PROPER SERVICE. 18-30-010, 13-20-120 100307735 | 5700 S CICERO AVE | PERMIT | FAILED | View |
ARRANGE PERMIT INSP. | 5700 S CICERO AVE | PERMIT | FAILED | View | |
HOLDOPEN DEVICE, STAIR 3+ FLRS | 1ST FLOOR SHIPPING AND RECEIVING DOORS, REMOVE HOLDING DEVICES FROM FIRE RATED DOORS.BASEMENT LEVEL, SMG OFFICE AND RESTAURANT STORAGE AREA, REMOVE HOLDING DEVICES FROM FIRE RATED DOORS | 5700 S CICERO AVE | PERIODIC | FAILED | View |
COVER OUTLETS AND JBS | BASEMENT LEVEL, RESTAURANT STORAGE AREA, INSTALL COVER ON JUNCTION BOX | 5700 S CICERO AVE | PERIODIC | FAILED | View |
ILLUMINATE EXIT AREAS | BASEMENT LEVEL, AT CORRIDOR SERVICING OFFICES AND OUTSIDE VENDORS, PROVIDE EMERGENCY LIGHTS TO ILLUMINATE PATH LEADING TO EMERGENCY EXITS (ONLY IF) EXISTING LIGHTS NOT CONNECTED TO BACK UP GENERATOR | 5700 S CICERO AVE | PERIODIC | FAILED | View |
ARRANGE PERMIT INSP. | 5700 S CICERO AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ESCALATOR | COMPLETE EGRESS TOP AND BOTTOM PLATES SECURELY | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE CAUTION SIGNS TOP AND BOTTOM OF ESCALATOR | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE CODE DATA PLATE ON OUTSIDE OF UNIT | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE OUTER DECKING TO ESCALATOR AND ANTI SLIDE DEVICE. | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE FED FROM INFORMATION ON CONTROLLER/MAINLINE DISCONNECT | 5700 S CICERO AVE | PERMIT | PASSED | View |
OPEN | 5700 S CICERO AVE | PERMIT | FAILED | View | |
MAINTAIN OR REPAIR ESCALATOR | FINISH LOBBY ENTERANCES AND EGRESS ENDS. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | FINISH ADJACENT FLOOR SURFACES TO ESCALATOR AND ELEVATOR. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | FINISH ALL DECK BARRICADES | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE AND INSTALL ESCALATOR CAUTION SIGNS | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE CODE DATA PLATES ON CONTORLLER AND ESCALATOR. REF.: A17.1-8.9 | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE ANTI-SLIDE DEVICES ON ALL ESCALATORS | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE CERTIFICATE FRAMES FOR ALL ESCALATORS | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | PROVIDE CONVEYANCE DESIGNATIONS ON ALL ESCALATORS | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | ESCALATOR NO. 4. UPPER IMPACT DEVICE NOT TESTED. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FINISH ELEVATOR LOBBYS AND FLOORS. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A DRAIN IN ELEVATOR PIT. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL PIT LIGHTS. LIGHTING TO PRODUCE 10 FOOT CANDLES OF ILLUMINATION THROUGHOUT PIT. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A GFI - OUTLET IN ELEVATOR PIT. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A FIRE EXTINGUISHER IN MACHINE ROOM. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | IDENTIFY ALL DISCONNECTS AND THEIR FEED LOCATION, IN MACHINE ROOM. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CANTER ALL LEDGES IN HOISTWAY. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FILL IN ALL OPENINGS IN HOISTWAY. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A GFI - OUTLET AT TOP OF HOISTWAY. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL LIGHTS AT THE TOP OF THE HOISTWAY. LIGHTING TO PRODUCE 19 FOOT CANDLES OF ILLUMINATION THROUGHOUT THE TOP OF THE HOISTWAY. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PHASE I & II NOT TESTED. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FAID'S TO BE TESTED WHEN ELEVATOR IS TIED INTO BUILDINGS FIRE SERVICE RECALL. | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS; FIRE RECALL KEYS TO BE KEYED THE SAME. FEO K1. | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ESCALATOR | CLEAR FLOOR AREA AROUND ESCALATORS | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH HOLES IN MACHINE ROOM WALL TO PIT | 5700 S CICERO AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | I.D. MACHINE ROOM DOOR | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FAID'S NOT TESTED. ALL SIX ELEVATOR'S FIRE SERVICE SWITCHES TO BE KEYED A LIKE. | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLOSE OUT PERMIT NO. 100768560 FOR ELEVATOR 2-6 | 5700 S CICERO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FINISH MACHINE ROOM FLOOR | 5700 S CICERO AVE | PERMIT | PASSED | View |