Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | PERFORM ANNUAL PRESSURE RELEIF AND HYDRALIC SYSTEM TEST. TAG VALVE AND SUBMIT RESULTS TO THE ELEVATOR BUREAU. (A17.1A-1997 RULE 1005.2A) BOTH ELEVATORS. NO COMPLIANCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | 1. BOTH CARS: A) PERFORM PRESSURE RELIEF AND HYDRAULIC SYSTEM TEST. TAG VALVE AND SEND TEST RESULTS TO THE ELEVATOR BUREAU (A17.1A-1997 RULE 1005.2A) B) CLEAN ELEVATOR PIT AND MACHINE ROOM C) REPAIR DOOR RESTRICTOR TO OPERATE PROPERLY 2. REPLACE DEFECTIVE SIGHT GUARD ON 1ST FLOOR LANDING DOOR-NORTH CAR. 3. PIN ESCAPE HATCH-BOTH CARS. 18-30-010,13-20-120. EV004722 | 1515 W MORSE AVE | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REMOVE OLD DOOR RESTRICTOR PARTS THAT ARE NO LONGER IN USE. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | CLEAN ELEVATOR CARTOPS AND INSTALL COVERS ON CARTOP EQUIPMENT, BOTH ELEVATORS. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | CLEAN ELEVATOR PITS- BOTH ELEVATORS. NO COMPLIANCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | CLEAN ELEVATOR MACHINE ROOMS-BOTH ELEVATORS. NO COMPLAINCE 5/15/06. | 1515 W MORSE AVE | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | REPAIR DOOR RESTRICTORS TO OPERATE PROPERLY-BOTH ELEVATORS. NO COMPLIANCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | PROPERLY SECURE CANOPY ACCESS PANEL (ESCAPE HATCH) BOTH ELEVATORS. NO COMPLAINCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | CLEAN ELEVATOR CARTOPS AND INSTALL COVERS ON CARTOP EQUIPMENT, BOTH ELEVATORS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | INSTALL CERTIFICATE FRAMES AND CAPACITY TAGS IN ELEVATOR CABS, BOTH ELEVATORS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | REPAIR/REPLACE DEFECTIVE 5TH FLOOR HALL BUTTON/ACCESS FIXTURE-NORTH ELEVATOR. 18-30-010, 13-20-120. EV004722 | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | REPAIR DOOR RESTRICTORS TO OPERATE PROPERLY-BOTH ELEVATORS. NO COMPLIANCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | PROPERLY SECURE CANOPY ACCESS PANEL (ESCAPE HATCH) BOTH ELEVATORS. NO COMPLAINCE FROM 5/15/06. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | INSTALL CAPACITY TAGS IN ELEVATOR CABS, BOTH ELEVATORS. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | REPAIR IN CAR POSITION INDICATORS, SOUTH ELEVATOR. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | REPAIR/REPLACE DEFECTIVE 5TH FLOOR HALL BUTTON/ACCESS FIXTURE-NORTH ELEVATOR. 18-30-010, 13-20-120. EV004722 | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | 1. REPLACE DEFECTIVE FIRST FLOOR SIGHT GUARD NORTH ELEVATOR. 2. REPLACE DEFECTIVE UNDER CAR PIPING NORTH ELEVATOR. 3. REPLACE DEFECTIVE FOURTH FLOOR HALL BUTTON FIXTURE SOUTH ELEVATOR. 18-30-010, 13-20-120. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | PERFORM ANNUAL PRESSURE RELIEF AND HYDRAULIC SYSTEM TEST. TAG VALVE AND SUBMIT RESULTS TO THE ELEVATOR BUREAU. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
DEFECTIVE FIXTURES | ALL STAIRWAYS AND CORRIDORS OF BUILDING FLOORS 1-5 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
SYSTEM III | PROVIDE BATTERY BACK UP EXIT SIGNS FLOORS 1-5 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | EMERGENCY LITES NOT WORKING FLOOR 1-5 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION FOR PERSONNEL FOR RECEPTACLES IN ALL REQUIRED LOCATIONS KITCHEN,BATHROOM AREA'S 18-27-210.8 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
EXIT AND EMERGENCY LITES NO PLASTIC ENCLOSURES ALLOWED 18-27-700.66(3) | 1515 W MORSE AVE | COMPLAINT | FAILED | View | |
ADD BRANCH CIRCUITS | TO EASE OVERLOAD USE FROM APPLIANCES IN KITCHEN,BEDROOM,AND LIVING ROOM OF UNIT 312 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | TO EASE EXTENSION CORD USE IN KITCHEN,BEDROOM,AND LIVING ROOM OF UNIT 312 | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | UNIT 312 ALL OUTLETS AND SWITCHES HEAVILY PAINTED OVER DEVICES | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING TWO WAY COMMUNICATION (PHONES) REQUIRED IN BOTH ELEVATOR CABS.(PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING NO RESPONSE,UNABLE TO GAIN ENTRY TO VERIFY DETECTORS AND CONDITIONS. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR TO BUILDING TO APT. 508- NO ENTRY, UNABLE TO VERIFY COMPLAINT OF FLEAS AND TICKS. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
INSECTS | APARTMENTS 406, 408, 409, 307, 206- BED BUG INFESTATION. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
ROACHES | APARTMENTS 409 AND 206- ROACHES. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | APARTMENTS 408, 307, 206- SMOKE DETECTORS NOT OPERATING. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CATEGORY 1 TEST OVERDUE FOR BOTH ELEVATORS. TAG AND DOCUMENT AS REQUIRED. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR AND MAINTAIN SOUTH ELVATOR. OUT OF SERVICE AT TIME OF THIS 311 REQUESTED INSPECTION. | 1515 W MORSE AVE | PERIODIC | PASSED | View |
ARMORED CABLE | IN ENTRANCE AREA OF BUILDING | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TESTING, TAG AND DOCUMENT AS REQUIRED - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE WORKING 2-WAY COMMUNICATION (PHONE) IN ELEVATOR CAB - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MALFUNCTIONING DOOR RESTRICTORS - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR CARTOPS AND INSTALL COVERS ON CARTOP DEVICES - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR PITS - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH CHICAGO CODE 8.6.5.8 OF A17.1 -2007 (SAFETY BULKHEAD REQUIREMENTS) - BOTH ELEVATORS | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A CERTIFICATE FRAME IN ELEVATOR CAB - NORTH ELEVATOR | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE MISSING GIB ON CAR DOOR - SOUTH ELEVATOR | 1515 W MORSE AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF THE BUILDING - NO RESPONSE, UNVERIFIED DETECTORS AND CONDITIONS. 1515 W. / APARTMENT # 507 - NO ENTRY, UNABLE TO VERIFY COMPLAINT OF BED BUG INFESTAION. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE WORKING 2-WAY COMMUNICATION (PHONE) IN ELEVATOR CAB - BOTH ELEVATORS (PREVIOUSLY CITED). | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MALFUNCTIONING DOOR RESTRICTORS - BOTH ELEVATORS (PREVIOUSLY CITED). | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR CARTOPS AND INSTALL COVERS ON CARTOP DEVICES - BOTH ELEVATORS (PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR PITS - BOTH ELEVATORS (PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH CHICAGO CODE 8.6.5.8 OF A17.1 -2007 (SAFETY BULKHEAD REQUIREMENTS) - BOTH ELEVATORS (PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A CERTIFICATE FRAME IN ELEVATOR CAB - NORTH ELEVATOR (PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH CHICAGO CODE 8.6.5.8 OF A17.1 -2007 (SAFETY BULKHEAD REQUIREMENTS) - BOTH ELEVATORS (PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING PIT LIGHTS AND SWITCHES REQUIRED IN BOTH ELEVATOR PITS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE DEFECTIVE CAR SILL ON SOUTH ELEVATOR. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | IDENTIFY BOTH ELEVATORS AT CAR OPERATING PANELS AND AT ALL LANDINGS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING TWO WAY COMMUNICATION (PHONES) REQUIRED IN BOTH ELEVATOR CABS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAKE NECESSARY MODIFICATIONS TO PROVIDE ADEQUATE BOTTOM RUNBY ON NORTH ELEVATOR.(CAR LANDS ON SPRINGS WHEN LEVEL AT 1ST FLOOR) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
USE SANITARY REFUSE CONTAINERS | REAR AT ALLEY - TRASH OUTSIDE CONTAINERS. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | NORTH ELEVATION 3RD FLOOR - BROKEN GLASS PANE. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE, UNVERIFIED DETECTORS AND CONDITIONS. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPAIR SCREENS | NORTH ELEVATION - TORN WINDOW SCREENS. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE. UNVERIFIED DETECTORS AND CONDITIONS. UNVERIFIED COMPLAINT OF PARKING GARAGE SUPPORT COLUMNS CHIPPED AND CRACKED. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING PIT LIGHTS AND SWITCHES REQUIRED IN BOTH ELEVATOR PITS.(PREVIOUSLY CITED) | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL APPROVED PIT LADDERS IN BOTH PITS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN BOTH ELEVATOR PITS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING PIT LIGHTING REQUIRED IN BOTH ELEVATOR PITS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING TWO WAY COMMUNICATION (PHONES) REQUIRED IN BOTH ELEVATOR CABS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | REPAIR IN CAR POSITION INDICATORS, SOUTH ELEVATOR. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSCRIBED CODE DATA TAGS REQUIRED ON CONTROLLERS. | 1515 W MORSE AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING /MOST APARTMENTS - NO ENTRY. UNVERIFIED DETECTORS AND CONDITIONS. UNVERIFIED COMPLAINT OF BED BUGS IN 316. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | REAL ELEVATION - ABOVE GARAGE ENTRY /MASONRY - CRACKED AND CHIPPED WITH EXPOSED REBAR. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPAIR/REBUILD GARAGE OR SHED | FIRST FLOOR PARKING GARAGE /CEILINGS - WARPED WITH HOLES THROUGHOUT AND SECTIONS OF DRYWALL MISSING. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |
REPAIR LINTELS | REAR ELEVATION AND COURTYARDS - 3RD AND 4TH FL - WINDOWS /LINTELS - WARPED AND RUSTED WITH LARGE GAPS PACKED WITH MORTAR. PERMITS REQUIRED FOR LINTEL REPAIR. PLANS REQUIRED FOR LINTELS GREATER THAN 6 FT. | 1515 W MORSE AVE | COMPLAINT | FAILED | View |