The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | 1. REPAIR DOOR RESTRICTORS ON BOTH PASSENGER ELEVATORS. PERFORM PRESSURE RELIEF AND HYDRAULIC SYSTEM TEST. TAG VALVES AND SEND RESULTS TO ELEVATOR BUREAU (BOTH ELEVATORS) (A17.1A-1997 RULE 1005.2A) 3. PROVIDE CERTIFICATE FRAME IN EAST ELEVATOR CAB. 18-30-010,13-20-120. EV000507 | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR MACHINE ROOMS, CARTOPS, AND PITS. (BOTH) | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE ABC RATED FIRE EXTINGUISHER IN ELEVATOR MACHINE ROOMS. (BOTH) | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY I TEST. TAG AND DOCUMENT AS REQUIRED. (BOTH) | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR DOOR RESTRICTORS. (BOTH) | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR EMERGENCY CAB LIGHTING (BOTH). | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A FIREMAN'S SERVICE TEST LOG ON SITE. | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A FIREMAN'S SERVICE KEY BOX WITH 2 KEYS NEAR PHASE I KEY SWITCH (WEST). | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR FIRE SERVICE JEWEL IN ELEVATOR CAB (WEST). | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL AS APPROVED SUMP COVER IN ELEVATOR PIT. EV000507 | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
FRIREMAN'S DUMP | FOR TWO 110 TON COPELAND CHILLERS LOCATED IN MECH RM. | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
TERMINATE VENT LINE | ABOVE UNITS. | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |
FRIREMAN'S DUMP | FOR TWO 110 TON COPELAND CHILLERS LOCATED IN MECH RM. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH A17.1-2007 SECTION 8.6.5.8 (BULKHEAD REQUIREMENTS)-BOTH ELEVATORS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED-BOTH ELEVATORS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE ADEQUATE LIGHTING WITH GUARDS IN BOTH ELEVATOR MACHINE ROOMS,PITS, AND CARTOPS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR ALL DOOR RESTRICTORS-BOTH ELEVATORS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN PITS AND CARTOPS, INSTALL COVERS ON CARTOP DEVICES-BOTH ELEVATORS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR PHASE 1 OPERATION-EAST ELEVATOR. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR CARTOP INSPECTION TO WORK PROPERLY-WEST ELEVATOR. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED-WEST ELEVATOR. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
CONNECT VENT LINE | USE 5/8 TYPETYPE K COPPER OR ACR TUBING ALL CONNECTION MUST BE BRAZED | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
REMOVE | ALL SOLDER FROM VENT LINE ... VENT LINE MUST BE BRAZED | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL/INSCRIBE CODE DATA PLATES - BOTH CARS | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR WEST ALARM BELL AND PHONE | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
TERMINATE VENT LINE | ABOVE UNITS. | 1426 W BIRCHWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: IN CAR STOP SWITCHES: MUST BE TIED TO ALARM BELL OR CHANGED TO KEYED STOP SWITCHES (BOTH). | 1426 W BIRCHWOOD AVE | PERIODIC | PASSED | View |