Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-25 @ 11:51 PM
PIN: 20024000010000
Property Address: 4301 S LAKE PARK AVE
City - Zip: CHICAGO - 60653
2023 Property Class: 530
2023 Township: 70 - Hyde Park
2023 Neighborhood: 70010
2023 Tax District: 70131
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 49 Violations
Violation Inspector Comments Address Category Status View
REPLACE DEFECTIVE SOIL PIPING CLOGGED HAND SINK AT REAR. DANGEROUS AND HAZARDOUS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
NO KEY TO USE EXIT DOOR NORTH EGRESS BY MANAGEMENT OFFICE LOCKED DURING BUSINESS HOURS OF OPERATION. D&H 4301 S LAKE PARK AVE COMPLAINT FAILED View
DWELLING CLEAN AND SANITARY ABATE EXCESSIVE AMOUNTS OF MOLD IN BASMENT AREAS BELOW THE MANAGEMENT OFFICE AND OTHER TYPICAL AREAS. UNSANITARY 4301 S LAKE PARK AVE COMPLAINT FAILED View
PROVIDE OPEN FRONT TOILET SEAT UNAPPROVED ROUND BOWL TOILETS WITH CLOSED FRONT SEATS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
REPL DEFECTIVE BATHROOM FLOOR BROKEN AND CRACKED FLOOR TILES THROUGHOUT BATHROOMS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
DEFECTIVE SERVICE MAIN SERVICE - EXTERIOR OVERHEAD SERVICE SPLICES AT REAR EXTERIOR DAMAGED AND MISSING INSULATION. OVERHEAD SERVICE HEAD DETERIORATED. SERVICE AND ASSOCIATED DISTRIBUTION EQUIOPMENT MISSING COVERS, MATS, BARRIERS. SERVICE AND ASSOCIATED DISTRIBUTION EQUIPMENT APPEAR MODIFIED FROM ORIGINAL CONDITION AND DAMAGED. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAYS LOOSE FITTINGS, DAMAGED CONDUITS VISIBLE VARIOUS AREAS. ENSURE GROUND CONTINUITY WHERE REQUIRED THROUGHOUT PREMISES. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
OPEN MISSING FLOOR DRAIN IN ROOM HOUSING WATER HEATER. (18-29-412.4) 4301 S LAKE PARK AVE COMPLAINT FAILED View
REPLACE DEFECTIVE PLBG FIXTURE MISSING LEG SUPPORT TO 3 COMPARTMENT SINK IN EAST PREP AREA. 4301 S LAKE PARK AVE COMPLAINT FAILED View
PRV PLUGGED/CAPPED FOR ONE COPELAND 3 HP. SEMI HERMETIC COMPRESSOR WITH DUAL RECEIVERS LOCATED ON ROOF. FOR ONE COPELAND 15 HP.SEMI HERMETIC COMPRESSOR SERVING BULK WALK-IN COOLER LOCATED ON ROOF. FOR ONE COPELAND 5 HP. SEMI HERMETIC COMPRESSOR SERVING 12' PRODUCE R-IN COOLER LOCATED ON BALCONY. ALL PRV'S ARE CAPPED . 4301 S LAKE PARK AVE PERIODIC FAILED View
PRV HIGH SIDE FOR ONE COPELAND 2 HP. HERMETIC COMPRESSOR IN LARKIN BOX ON ROOF ,SERVING REACH IN COOLER. FOR ONE CARLYLE 3 HP. SEMI HERMETIC COMPRESSOR SERVING MEAT PREP LOCATED ON ROOF(CENTER EAST). FOR ONE COPELAND 3 HP. SEMI HERMETIC COMPRESSOR IN LARKIN BOX LOCATED ON ROOF(CENTER WEST). 4301 S LAKE PARK AVE PERIODIC FAILED View
RECONNECT VENT LINE FOR ONE COPELAND 10 HP. SEMI HERMETIC COMPRESSOR SERVING WALK-IN MEAT COOLER LOCATED IN BASEMENT. FOR ONE COPELAND 7.5 HP. SEMI HERMETIC COMPRESSOR SERVING 32' R-IN COOLER. LOCATEDE IN BASEMENT. 4301 S LAKE PARK AVE PERIODIC FAILED View
CONNECT VENT LINE FOR BOTH COPELAND SEMI HERMETIC COMPRESSORS ONE AT 3 HP. AND ONE AT 5 HP. LOCATED ON BALCONY. 4301 S LAKE PARK AVE PERIODIC FAILED View
PRV PLUGGED/CAPPED FOR ONE COPELAND 3 HP. SEMI HERMETIC COMPRESSOR WITH DUAL RECEIVERS LOCATED ON ROOF. FOR ONE COPELAND 15 HP.SEMI HERMETIC COMPRESSOR SERVING BULK WALK-IN COOLER LOCATED ON ROOF. FOR ONE COPELAND 5 HP. SEMI HERMETIC COMPRESSOR SERVING 12' PRODUCE R-IN COOLER LOCATED ON BALCONY. ALL PRV'S ARE CAPPED . 4301 S LAKE PARK AVE PERIODIC PASSED View
PRV HIGH SIDE FOR ONE COPELAND 2 HP. HERMETIC COMPRESSOR IN LARKIN BOX ON ROOF ,SERVING REACH IN COOLER. FOR ONE CARLYLE 3 HP. SEMI HERMETIC COMPRESSOR SERVING MEAT PREP LOCATED ON ROOF(CENTER EAST). FOR ONE COPELAND 3 HP. SEMI HERMETIC COMPRESSOR IN LARKIN BOX LOCATED ON ROOF(CENTER WEST). 4301 S LAKE PARK AVE PERIODIC PASSED View
RECONNECT VENT LINE FOR ONE COPELAND 10 HP. SEMI HERMETIC COMPRESSOR SERVING WALK-IN MEAT COOLER LOCATED IN BASEMENT. FOR ONE COPELAND 7.5 HP. SEMI HERMETIC COMPRESSOR SERVING 32' R-IN COOLER. LOCATEDE IN BASEMENT. 4301 S LAKE PARK AVE PERIODIC PASSED View
CONNECT VENT LINE FOR BOTH COPELAND SEMI HERMETIC COMPRESSORS ONE AT 3 HP. AND ONE AT 5 HP. LOCATED ON BALCONY. 4301 S LAKE PARK AVE PERIODIC PASSED View
MAINT PLATFORM LIFT REPAIR STOP BUTTON ON LOWER LANDING. MATERIAL HOIST. 4301 S LAKE PARK AVE PERIODIC PASSED View
MAINT PLATFORM LIFT REPAIR GATE SWITCH ON LOWER LANDING. MATERIAL LIFT. 4301 S LAKE PARK AVE PERIODIC PASSED View
INSTALL SMOKE DETECTORS MISSING THROUGH-OUT. D&H 4301 S LAKE PARK AVE COMPLAINT FAILED View
CARB MONOX DETECT IN RESID MISSING THROUGH-OUT. D&H 4301 S LAKE PARK AVE COMPLAINT FAILED View
PROVIDE GUARD RAIL 42 IN HIGH SLIDING DOOR TO RECEIVE STOCK ON 2ND FLOOR OFF THE TRACK WHICH LEADS TO A ROUGHLY 12FT DROP. EITHER REPAIR AND MAINTAIN IN THE CLOSED POSITION WHEN NOT IN USE OR PERMANENTLY CLOSE OPENING IF NOT IN USE ANYMORE. D&H 4301 S LAKE PARK AVE COMPLAINT FAILED View
INDIRECT CONN.FOR WATER SUPPLY WATER SUPPLY TO SOAP DISPENSER AT 3 COMPARTMENT SINKS AND ICE MACHINE ARE DIRECTLY CONNECTED TO POTABLE WATER SYSTEM WITHOUT ANY MEANS OF CROSS CONTAMINATION PREVENTION. DANGEROUS AND HAZARDOUS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
REPLACE DEFECTIVE PLBG FIXTURE MENS BATHROOM LAVATORY IS MOUNTED ONTO WIRE CRATES. DANGEROUS AND HAZARDOUS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
REPAIR OR REPLACE SUMP PITS IN BASEMENT DEFECTIVE AND OR MISSING COVERS. DANGEROUS AND HAZARDOUS. (18-29-1111.3.2) 4301 S LAKE PARK AVE COMPLAINT FAILED View
REMOVE STAGNANT WATER BSMT SEWAGE PRESENT AT MENS BATHROOM FLOOR. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
PROVIDE MISSING SAFE PAN TO WATER HEATER AT 2ND FLOOR. (18-29-504.8 THRU 504.8.2) 4301 S LAKE PARK AVE COMPLAINT FAILED View
ENGAG LIC & BOND PLMBNG CNTRC 4301 S LAKE PARK AVE COMPLAINT FAILED View
OBTAIN PERMIT FOR PLUMBING 4301 S LAKE PARK AVE COMPLAINT FAILED View
DEFECTIVE SERVICE SMALL EMERGENCY SERVICE - EMERGENCY SERVCIE FUSED DISCONNECT DETERIORATED. EXTERIOR OVERHEAD SPLICES UNINSULTED AND DAMAGED. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
PROPER SIZE GRD ELECTRODE COND NO VISIBLE WATER GROUND(S). ENSURE SERVICE(S) GROUNDED IN APPROVED MANNER. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
DEFECTIVE DISTRIBUTION DISTRIBUTION PANELS DAMAGED, TAMPERED WITH, MISSING BREAKERS VARRIOUS AREAS. ENSURE DISTRIBUTION EQUIPMENT INCLUDING FEEDERS IN APPROVED CONDITION THROUGHOUT PREMISES. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
WORKING SPACE SERVICE DISCONNECTS, PANELS, ELECTRICAL EQUIPMENT THROUGHOUT PREMISES BLOCKED BY DEBRIS, CLUTTER, MATERIOA. ENSURE REQUIRED SPACE. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
INSTALL COVERS OPEN BOXES VARIOUS AREAS THROUGOUT PREMISES. COVER BOXES AND FITTINGS WHERE REQUIRED. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
EXPOSED WIRING OPEN WIRING VARIOUS AREAS THROUGHOUT PREMISES. REMOVE WHERE REQUIRED. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
RESTORE EXIT AND EM REQUIRED EMERGENCY LIGHTING SYSTEM DAMAGED, INOPERABLE, INSUFFICIENT, UNMAINTAINED THROUGHOUT PREMISES. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
DEFECTIVE FIXTURES BROKEN LIGHT FIXTURES VARIOUS AREAS THROUGHOUT PREMISES. REPAIR / REPLACE WHERE REQUIRED. 4301 S LAKE PARK AVE COMPLAINT FAILED View
DEFECTIVE OUTLETS DAMAGED CORRODED SWITCHES AND RECEPTACLES VARIOUS AREAS THROUGHOUT PRMEISES. REPLACE DEVICES WHERE REQUIRED. 4301 S LAKE PARK AVE COMPLAINT FAILED View
INSTALL GFCI'S INSTALL GFCI PROTECTION KITCHEN, BATHS, SINKS, BASEMENT, EXTERIOR, WET LOCATIONS. 4301 S LAKE PARK AVE COMPLAINT FAILED View
UNAPPROVED CORDS DAMAGED EXTENSION CORDS, SPLICED CORDS, EXCESSIVE CORDS VISIBLE VARIOUS AREA THROUGHOUT PREMISES. REMOVE WHERE REQUIRED. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION MISSING, LOOSE, BROKEN EQUIPOMENT COVERS VARIOUS AREAS THROUGHOUT PREMISES. INSTALL WHERE REQUIRED. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION LIGHT FIXTURES, BOXES, FITTINGS, RACEWAYS AT WALK IN COOLERS AND FREEZERS MUST BE IDENTIFIED FOR USE AND LISTED FOR WET LOCATION. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
SUPPORT FIXTURES UNSUPPORTED LIGHT FIXTURES, INSUFFICIENTLY SUPPORTED LIGHT FIXTURES VARIOUS AREAS THROUGHOUT PREMISES. SECURE IN APPROVED MANNER. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
CORRODED CONDUIT & EQUIP CORRODED CONDUIT, BOXES, EQUIPMENT VISIBLE VARIOUS AREAS THROUGHOUT PREMISES. REPLACE WHERE REQUIRED. 4301 S LAKE PARK AVE COMPLAINT FAILED View
DETERIORATED CONDUCTORS DAMAGED, DETERIORATED WIRING VISIBLE AT OPEN BOXES AND PANELS. REPLACE WHERE REQUIRED. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
ADD RECEPTACLES ADD RECEPCTACLES TO PREVENT VISIBLY UNAPPROVED EXTENSION CORD USAGE WHERE REQUIRED THROUGHOUT PREMISES. DANGEROUS AND HAZARDOUS 4301 S LAKE PARK AVE COMPLAINT FAILED View
PROVIDE FULL ACCESS TO ALL DROP CEILING AREAS FOR INSPECTIONS THROUGHOUT PREMISES. (14A-5-505.2) 4301 S LAKE PARK AVE COMPLAINT FAILED View
OBTIAN PERMIT TO CORRECT VIOLATIONS. (14A-4-404.6) 4301 S LAKE PARK AVE COMPLAINT FAILED View
DWELLING CLEAN AND SANITARY ABATE EXCESSIVE AMOUNTS OF MOLD IN BASMENT AREAS BELOW THE MANAGEMENT OFFICE AND OTHER TYPICAL AREAS. UNSANITARY 4301 S LAKE PARK AVE COMPLAINT FAILED View