The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REP/REPL CAR DR OR GATE FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
TEST G & S ALL ELE | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
REP/REPL CAR DR OR GATE FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
OPEN TYPE VIOLATION | 1. PERFORM ANNUAL PRESSURE RELIEF TEST W/DATED TAG (HYDRAULIC ELEVATOR ONLY) 2. DO NOT RUN ELEVATOR W/GATE BY-PASS. 3. LUBE HOIST ROPES ALL CARS. 18-30-010,13-20-120. EV005269. | 1935 W PERSHING RD | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR B-7 WAS NOT RUNNING UPON ARRIVAL AND UNABLE TO DO INSPECTION. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - CLEAN PIT | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL BUILDINGS (A-D) AND ALL ELEVATORS (1-10): GATE SWITCH NOR LANDING SWITCH IS NOTWORKING PROPERLY UPON ARRIVAL. ELEVATOR RUNS WITH BOTH HOISTWAY AND CAR DOORS OPEN. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE CODE COMPLIANT PIT LADDERS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATOR PITS: INSTALL ADEQUATE PIT LIGHTING WITH LIGHT SWITCH AT ENTRANCE ADJACENT TO PIT LADDERS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - SERVICE FIRE EXTINGUISHER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATOR PITS: INSTALL PIT STOP SWITCH IN EACH ELEVATOR PIT ADJACENT TO PIT LADDER PER CODE | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE CODE COMPLIANT PIT LADDER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE AUDIBLE IN-CAR ALARM BELL | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: SERVICE MACHINE ROOM FIRE EXTINGUISHERS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE IN-CAR AUDIBLE ALARM BELL | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1,2,3,4: INSTALL CODE COMPLIANT PIT LADDERS OR REQUEST A VARRIANCE. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAT1 HAS EXPIRED FOR A, B, AND C BUILDING | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BUILDING A/B: HOISTWAY DOORS ARE ABLE TO BE OPENED WITHOUT ELEVATOR BEING PRESENT | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #4 IN D-BUILDING IS IN SEVERE DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL BUILDINGS AND ALL ELEVATORS: THE GATE SWITCH NOR LANDING SWITCH IS NOT WORKING PROPERLY UPON ARRIVAL. ELEVATOR RUNS WITH BOTH, HOISTWAY AND CAR, DOORS OPEN. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - LABEL MACHINE ROOM EQUIPMENT, PIT EQUIPMENT AND INSIDE ELEVATOR CAR STATOION WITH ELEVATOR NUMBER. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: SERVICE MACHINE ROOM FIRE EXTINGUISHERS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: PATCH ALL HOLES IN MACHINE ROOM FLOOR THAT IS NOT NEEDED | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE CODE COMPLIANT PIT LADDERS. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #2 IN B-BUILDING IS IN SEVERE DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - SERVICE FIRE EXTINGUISHER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE KICK PLATES AROUND CABLE DROP IN MACHINE ROOM. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE AUDIBLE IN-CAR ALARM BELL. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE IN-CAR AUDIBLE ALARM BELL. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
REMOVE DEBRIS FROM PIT | B BUILDING: ELEVATOR #2 - CLEAN PIT | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATOR PITS: INSTALL ADEQUATE PIT LIGHTING WITH LIGHT SWITCH AT ENTRANCE ADJACENT TO PIT LADDERS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATOR PITS: PULL PERMIT TO INSTALL PIT STOP SWITCH IN EACH ELEVATOR PIT ADJACENT TO PIT LADDER PER CODE | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - LABEL MACHINE ROOM EQUIPMENT, PIT EQUIPMENT AND INSIDE ELEVATOR CAR STATION WITH ELEVATOR NUMBER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: PATCH ALL HOLES IN MACHINE ROOM FLOOR THAT ARE NOT NEEDED | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE KICK PLATES AROUND HOIST ROPE DROPS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #2: IN B BUILDING IS IN SEVER DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. PROVIDE CAT5 TEST SHEETS AND TAGS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE KICK PLATES AROUND CABLE DROPS IN MACHINE ROOM | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | C BUILDING: ALL ELEVATOR - PROVIDE CODE COMPLIANT PIT LADDER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | C BUILDING: ALL ELEVATORS - PROVIDE IN-CAR AUDIBLE ALARM BELL | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | C BUILDING: BRING NON OPERABLE ELEVATOR UP TO WORKING CONDITION TO MEET CITY OF CHICAGO'S CODES OR PULL PERMIT TO DECOMMISSION. PROVIDE CAT5 TEST SHEETS AND TAGS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D BUILDING: BRING NON OPERABLE ELEVATOR UP TO WORKING CONDITION TO MEET CITY OF CHICAGO'S CODES OR PULL PERMIT TO DECOMMISSION. PROVIDE CAT5 TEST SHEETS AND TAGS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D BUILDING: ALL ELEVATORS - PROVIDE CODE COMPLIANT PIT LADDER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D BUILDING: ALL ELEVATORS - PROVIDE IN-CAR AUDIBLE ALARM BELL | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | C BUILDING: ALL ELEVATORS - LABEL MACHINE ROOM EQUIPMENT, PIT EQUIPMENT AND INSIDE ELEVATOR CAR STATION WITH ELEVATOR NUMBER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D BUILDING: ALL ELEVATORS - LABEL MACHINE ROOM EQUIPMENT, PIT EQUIPMENT AND INSIDE ELEVATOR CAR STATION WITH ELEVATOR NUMBER | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL BUILDINGS (A-D) AND ALL ELEVATORS (1-10): GATE SWITCH NOR LANDING SWITCH IS NOT WORKING PROPERLY UPON ARRIVAL. ELEVATOR RUNS WITH BOTH HOISTWAY AND CAR DOORS OPEN. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #4 IN D BUILDING IS IN SEVER DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #2: IN B BUILDING IS IN SEVER DIS-REPAIR AND WAITING ON PARTS. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. PROVIDE CAT5 TEST SHEETS AND TAGS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL BUILDINGS (A-D) AND ALL ELEVATORS (1-9): GATE SWITCH IS NOT WORKING PROPERLY UPON ARRIVAL. ELEVATOR RUNS WITH HOISTWAY GATE | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #7: IS OPERATIONAL BUT ELEVATOR IS ABLE TO RUN WITH LANDING GATE OPEN | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BRING BOTH HYDRAULIC ELEVATORS UP TO RUNNING CONDITION AND BRING INTO FULL COMPLIANCE OR DECOMMISSION BOTH HYDRAULIC ELEVATORS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
POST CURRENT CERTIF FRT ELE | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
REP/REPL DEF H/W DR FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
CLEAN DEBRIS CAR TOP FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
INSTALL CAPACITY TAG FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
RESHACKLE DRUM ROPES FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
REMOVE DEBRIS FROM PIT FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #5: HOISTWAY DOORS ARE ABLE TO BE OPENED WITHOUT THE FREIGHT ELEVATOR IS AWAY FROM THE FLOOR | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #6: HOISTWAY DOORS ARE ABLE TO BE OPENED WITHOUT THE FREIGHT ELEVATOR IS AWAY FROM THE FLOOR | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | B BUILDING: ELEVATOR #2 - PROVIDE CODE COMPLIANT PIT LADDER. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
REMOVE WATER FROM PIT | A BUILDING: ALL ELEVATORS - REMOVE WATER FROM PIT AND PROVIDE WORKING SUMP PUMP. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #7: IN A BUILDING IS IN SEVER DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. PROVIDE CAT5 TEST SHEETS AND TAGS | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | HAVE ELEVATOR SERVICE COMPANY (ALL-TYPES) CHECK AND VERIFY THAT EVERY ELEVATOR HOISTWAY DOOR LOCKS AND CANNOT BE OPENED WHILE ELEVATOR IS OUT OF LOCKING ZONE AT EVERY LANDING. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #7: HOISTWAY DOORS ARE ABLE TO BE OPENED WITHOUT THE FREIGHT ELEVATOR IS AWAY FROM THE FLOOR | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR C14 (14) HAS NO ANNUAL TESTING PREFORMED ON THIS UNIT | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR # D12 IS IN SEVERE DIS-REPAIR AND NOT BEING USED. IT IS OUT OF SERVICE AND IN PROCESS OF BEING DECOMMISIONED. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR C9 THE GATE SWITCH WAS NOT WORKING PROPERLY UPON ARRIVAL. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | NO ANNUAL TESTING PREFORMED ON THIS UNIT | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | A BUILDING: ALL ELEVATORS - PROVIDE KICK PLATES AROUND HOIST ROPE DROPS. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #7 IN A-BUILDING IS IN SEVERE DIS-REPAIR AND NOT BEING USED. BRING ELEVATOR INTO COMPLETE COMPLIANCE OR PULL A PERMIT TO DECOMMISSION. | 1935 W PERSHING RD | PERIODIC | FAILED | View |
REMOVE WATER FROM PIT FRT | HYDRO-CAR PIT | 1935 W PERSHING RD | PERIODIC | CLOSED | View |
POST CURRENT CERTIF FRT ELE | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
TEST G & S ALL ELE | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
REMOVE FRT ELE FROM ACT SER | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
REP/REPL DEF H/W DR FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
CLEAN DEBRIS CAR TOP FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
INSTALL CAPACITY TAG FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
RESHACKLE DRUM ROPES FRT | DRUM MACHINES ONLY | 1935 W PERSHING RD | PERIODIC | CLOSED | View |
REMOVE DEBRIS FROM PIT FRT | 1935 W PERSHING RD | PERIODIC | CLOSED | View | |
OPEN TYPE VIOLATION | 1. PERFORM ANNUAL PRESSURE RELIEF TEST W/DATED TAG (HYDRAULIC ELEVATOR ONLY) 2. DO NOT RUN ELEVATOR W/GATE BY PASS 3. LUBE HOIST ROPES 18-30-010,13-20-120 (EV005267) | 1935 W PERSHING RD | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR B-6 THE HOISTWAY DOOR ON THE FIRST FLOOR WAS DAMAGED AND UNABLE TO OPEN. REPAIRS ARE UNDERWAY WITH THIS UNIT. | 1935 W PERSHING RD | PERIODIC | FAILED | View |