Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 1040 N KEELER AVE | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE SCOTCH MARINE BOILER BD# 51127. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE SCOTCH MARINE BOILER BD# 51128. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | PROVIDE OCCUPANCY CARDS AND DIAGRAMS FOR LIBRARY, AUDITORIUM BALCONY, AND GYMNASIUM (GYMNASIUM AND AUDITORIUM BALCONY MISSING DIAGRAMS) | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | PROVIDE OCCUPANCY CARDS AND DIAGRAMS FOR LIBRARY, AUDITORIUM BALCONY, AND GYMNASIUM (GYMNASIUM AND AUDITORIUM BALCONY MISSING DIAGRAMS) | 1040 N KEELER AVE | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | PROVIDE OCCUPANCY DIAGRAM FOR CAFETERIA | 1040 N KEELER AVE | PERIODIC | PASSED | View |
CONNECT VENT LINE | FOR THE FOLLOWING TWO (2) 1-TON REMOTE REFRIGERATION UNITS THAT SERVE THE REACH IN COOLER, THE UNITS ARE LOCATED IN THE BASEMENT. FOR THE FOLLOWING ONE (1) 1-1/2 TON REMOTE REFRIGERATION UNIT THAT SERVE THE FREEZER, THE UNIT IS LOCATED IN THE BASEMENT. USE 5/8 O.D. COPPER TYPE K OR ACR TUBING. ALL JOINTS MUST BE BRAZED. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
INTERNAL | #1 BOILER. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
INTERNAL | #2 BOILER. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 1040 N KEELER AVE | PERIODIC | PASSED | View | |
POST APPROVED OCCUPANCY CARD | PROVIDE OCCUPANCY DIAGRAM FOR CAFETERIA. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
CONNECT VENT LINE | 5/8 O.D. TYPE K COPPER OR ACR TUBING, ALL CONNECTIONS SHOULD BE BRAZED FOR ONE 2 HP AND ONE 3 HP COPELAND REMOTE REFRIGERATION UNITS LOCATED IN BASEMENT | 1040 N KEELER AVE | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR THE FOLLOWING TWO (2) 1-TON REMOTE REFRIGERATION UNITS THAT SERVE THE REACH IN COOLER, THE UNITS ARE LOCATED IN THE BASEMENT. FOR THE FOLLOWING ONE (1) 1-1/2 TON REMOTE REFRIGERATION UNIT THAT SERVE THE FREEZER, THE UNIT IS LOCATED IN THE BASEMENT. USE 5/8 O.D. COPPER TYPE K OR ACR TUBING. ALL JOINTS MUST BE BRAZED. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | PRV'S ARE CAPPED. FOR TWO SEMI HERMETIC COPELAND 2 HP. COMPRESSORS LOCATED IN BASEMENT MECHANICAL ROOM. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR ALL THREE COPELAND REFRIGERATION COMPRESSORS LOCATED IN BASEMENT MECHANICAL ROOM. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST O.C DIAGRAM FOR GYM, AUDITORIUM W/BALCONY | 1040 N KEELER AVE | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | POST O.C FOR LUNCHROOM. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY CARD FOR LUNCHROOM | 1040 N KEELER AVE | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 3/27/13. STICKER LEFT ON DOOR. NO ONE CONTACTED DEPT.OF BUILDINGS TO ALLOW ACCESS. TO ARRANGE INSPECTION PLEASE CALL 312-743-3610 | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY CARD FOR LUNCHROOM | 1040 N KEELER AVE | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 1040 N KEELER AVE | PERIODIC | PASSED | View | |
INTERNAL | KEWANEE SCOTCH MARINE BOILER #1. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
INTERNAL | KEWANEE SCOTCH MARINE BOILER #2. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
FLAKY INTERIOR PAINT | REMOVE PEELING PAINT AT THE AUDITORIUM BALCONY. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | PRV'S ARE CAPPED. FOR TWO SEMI HERMETIC COPELAND 2 HP. COMPRESSORS LOCATED IN BASEMENT MECHANICAL ROOM. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR ALL THREE COPELAND REFRIGERATION COMPRESSORS LOCATED IN BASEMENT MECHANICAL ROOM. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBSTAIN REVISED OCCUPANCY CARD FOR AUDITORIUM TO REFLECT ACTUAL NUMBER OF SEATS. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
ADDITIONAL EXIT | PROVIDE THIRD EXIT AT LUNCHROOM OR REDUCE CAPACITY BELOW 300. OCCUAPNCY CAPACITYOF 325 REQUIRES 3 EXITS. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHER RECHARGE TAGS EXPIRED. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 1040 N KEELER AVE | PERIODIC | CLOSED | View | |
REPAIR EXTERIOR STAIR | FRONT EAST ELEVATION--OPEN MORTAR JOINTS--LOOSE STONE BLOCKS--FRACTURED STAIRS--TOP LANDING. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 1040 N KEELER AVE | PERIODIC | PASSED | View | |
REPLACE BREECHING - HWH | AOS SMITH HOT WATER BOILER NB# 70982. | 1040 N KEELER AVE | PERIODIC | PASSED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHER RECHARGE TAGS EXPIRED. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | BOTH EXITS FROM AUDITORIUM STAGE ARE IBSTRUCTED BY CLEANING SUPPLIES AND OTHER MATERIALS. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
DOOR SWING IN DIR. OF TRAVEL | STAIR #5 ON FIRST FLOOR IS EXIT PATH FOR AUDITORIUM TO CORRIDOR. THE EXIT DOOR SWINGS INWARD AGAINST DIRECTION OF EXIT TRAVEL. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | REINSTALL FIRE DOOR ADJACENT TO THE AUDITORIUM. DOOR IS REQUIRED TO MAINTAIN FIRE SEPARATION. | 1040 N KEELER AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | FRONT MAIN ENTRANCE, EXITS 1,4&5 --OPEN MORTAR JOINTS--LOOSE STONE BLOCKS--FRACTURED STAIRS-DANGEROUS AND HAZARDOUS | 1040 N KEELER AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO 2ND FLOOR BALCONY | 1040 N KEELER AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBSTAIN REVISED OCCUPANCY CARD FOR AUDITORIUM TO REFLECT ACTUAL NUMBER OF SEATS. MISSING CARD AT LIBRARY | 1040 N KEELER AVE | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | 450# PSIG FOR ONE COPELAND 2 HP REMOTE REFRIGERATION UNIT LOCATED IN BASMENT SERVING VEGGIE COOLER | 1040 N KEELER AVE | PERIODIC | FAILED | View |
REPLACE BREECHING - HWH | 1040 N KEELER AVE | PERIODIC | CLOSED | View |