The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
COLLECT OIL LEAKING FR PACKING | 5116 N CICERO AVE | PERIODIC | FAILED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED. | 5116 N CICERO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH SECTION 8.6.5.8 OF A17.1-2007 (BUKLKHEAD REQUIREMENTS). | 5116 N CICERO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING DOOR RESTRICTOR REQUIRED. | 5116 N CICERO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL AN APPROVED PIT LADDER. | 5116 N CICERO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST AND PROVIDE DOCUMENTATION | 5116 N CICERO AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE DETAILED MAINTENANCE RECORDS | 5116 N CICERO AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | 1. PERFORM ANNUAL PRESSURE RELIEF TEST FOR PASSENGER ELEVATOR; SEAL & TAG VALVE; SUBMIT TEST REPORT TO CITY OF CHICAGO ELEVATOR BUREAU. 1005.2A. 2. CLEAN OIL FROM ELEVATOR PIT OF PASSENGER ELEVATOR. 3. RE-PACK CYLINDER FOR PASSENGER ELEVATOR. 18-30-010, 13-20-120. EV001027. | 5116 N CICERO AVE | PERIODIC | FAILED | View |