Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | CLOSED | View | |
LEAKING BOILER TUBES | #1 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LEAKING BOILER TUBES | #2 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LEAKING BOILER TUBES | #3 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPLACE | BOTTOM HALF OF BURNT OUT AND DISTORTED TUBE SHEET HOUSING REAR #1 BOILER HANGAR. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #1 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #2 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #3 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #4 BOILER. | 2100 E 87TH ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
LEAKING BOILER TUBES | #1 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LEAKING BOILER TUBES | #2 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPAIR | CASING #4 BOILER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | CLOSED | View | |
LEAKING BOILER TUBES | #3 KEWANEE 74 SM #9738.WORK DONE BY ANDEE BOILER | 2100 E 87TH ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #2 KEWANEE 74 SM #9738. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | #2 KEWANEE 74 SM #9738. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | #2 KEWANEE 74 SM #9738. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 73 SM #4739. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #3 KEWANEE 73 SM #9738. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #4 KEWANEE 73 SM #9788. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #45 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #3 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #31 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
DEFECTIVE SAFETY VALVE-BOILER | #2 KEWANEE 74 SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
ADJUST BOILER BURNER | #3 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | LEAKING DRAIN LINES #2 KEWANEE 74 SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
STOP OPERATING BOILER - UNSAFE | #1 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
STOP OPERATING BOILER - UNSAFE | #2 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
STOP OPERATING BOILER - UNSAFE | #3 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
STOP OPERATING BOILER - UNSAFE | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | #1 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
HYDROSTATIC TEST | #1 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
ADJUST BOILER BURNER | #1 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #2 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LEAKING HEADER VALVE | #1 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING HEADER VALVE | #2 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING HEADER VALVE | #3 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
LEAKING HEADER VALVE | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | ALL LOW WATER CONTROLS. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPLACE | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | MISSING STUDS ON BOILER DOORS #4 SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPAIR | BOILER JACKET #1 KEWANEE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPAIR | BOILER JACKET #3 KEWANEE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPAIR | BOILER JACKET #4 KEWANEE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
SEE INSPECTOR COMMENTS | EXCESSIVE SCALE IN BOILER #1 KEWANEE. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | EXCESSIVE SCALE IN BOILER #2 KEWANEE. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | EXCESSIVE SCALE IN BOILER #3 KEWANEE. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | REPAIR OR REPLACE ALL CONDENSATE RETURN PUMPS, WATER IS NOT RETURNING TO BOILER. | 2100 E 87TH ST | PERIODIC | PASSED | View |
MAINTAIN | PROPER CHEMICAL TREATMENTOF BOILER WATER. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REMOVE | BOILER BREECHING FROM BOILER ROOM WINDOWS IN VIOLATION OF CODE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPAIR | BOILER JACKET #2 KEWANEE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE LOW WATER CUTOFF #1 KEWANEE. | 2100 E 87TH ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #2 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #3 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #23 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | CLOSED | View | |
LEAKING BOILER TUBES | #4 KEWANEE SM 15 L. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
LEAKING MANHOLE GASKET | #3 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPLACE | ALL TUBES BOILER #1 KEWANEE. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
STOP OPERATING BOILER - UNSAFE | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | #1 OVERHEATED & DAMAGED TUBES DUE TO LOW WATER CONDITION. | 2100 E 87TH ST | PERIODIC | PASSED | View |
CORRODED CONDUIT & EQUIP | REPLACE NEWLY INSTALLED CONDUITS WHICH HAVE BEEN SANDBLASTED RESULTING IN SEVERE CORROSION AS PER 18-27-300.6(A) | 2100 E 87TH ST | PERMIT | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2100 E 87TH ST | PERIODIC | PASSED | View | |
LEAKING BOILER TUBES | #1 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | GASKETS #1 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
SEE INSPECTOR COMMENTS | WATER COLUMN LINES CLOGGED #2 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #2 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | LEAKING HEADERS ON ALL BOILERS. | 2100 E 87TH ST | PERIODIC | PASSED | View |
INTERNAL | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
ARRANGE PERMIT INSP. | 2100 E 87TH ST | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | SEE DEFECT NOTICE #12597 | 2100 E 87TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) REPAIR & MAINTAIN PASSENGER ELEVATOR #1 IN A SAFE OPERATING CONDITION. | 2100 E 87TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PROVIDE MAINTENANCE RECORD ON SITE IN ELEVATOR MACHINE ROOM AS REQUIRED. #1 CAR | 2100 E 87TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PROVIDE PROOF OF COMPLIANCE WITH SAFEFTY BULKHEAD REQUIREMENT ASME RULE 8.6.5.8 | 2100 E 87TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PROVIDE PIT LIGHTING WITH SWITCH NEAR PIT ACCESS. #1 CAR (PREVIOUSLY CITED) | 2100 E 87TH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PROVIDE PROOF OF COMPLIANCE WITH SAFEFTY BULKHEAD REQUIREMENT ASME RULE 8.6.5.8 (PREVIOUSLY CITED) | 2100 E 87TH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PHASE II OPERATION TO BE MADE IN COMPLIANCE WITH CITY OF CHICAGO MANDATE. | 2100 E 87TH ST | COMPLAINT | FAILED | View |
REPLACE | REAR DOOR REFACTORY HOUSING #1 BOILER HANGER. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INTERNAL | #5 BOILER. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPAIR | #3 BOILER BURNER REFRACTORY. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | #1 BOILER HANGAR-ENGAGE LICENSED BOILER CONTRACTOR TO PROPERLY INSTALL BASE ON #1 BOILER IN HANGAR | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INSTALL, REPAIR OR REPLACE EMERGENCY TELEPHONE IN ALL ELEVATION AND PROGRAM TO 24HR ANSWERING SOURCE. | 2100 E 87TH ST | PERIODIC | PASSED | View | |
INTERNAL | #45 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #1 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #3 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
SEE INSPECTOR COMMENTS | CHECK FOR GAS LEAK. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPLACE | #2 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | NO ENGINEER ON DUTY AT TIME OF INSPECTION. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
REPLACE | GASKETS #2 KEWANEE 73 SM. | 2100 E 87TH ST | PERIODIC | PASSED | View |
REPLACE | LEAKING BOILER FEED TANK. | 2100 E 87TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) CORRECT ISSUE OF EXCESSIVE OIL IN ELEVATOR PIT. | 2100 E 87TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | (AUDIT) PROVIDE PIT LIGHTING WITH SWITCH NEAR PIT ACCESS. #1 CAR | 2100 E 87TH ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | #4 KEWANEE SM. | 2100 E 87TH ST | PERIODIC | CLOSED | View |
INSTALL | BOILER DAMPER CONTROL ON MAIN INLET DUCT TO FULTON HOT WATER BOILERS. | 2100 E 87TH ST | PERIODIC | PASSED | View |