Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE FOR INSPECTION | CONTACT INSPECTOR ROBINSON AT 312-446-5589. | 3525 W PETERSON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MALFUNCTIONING DOOR RESTRICTORS. BOTH ELEVATORS. (PREVIOUSLY CITED) | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH SECTION 8.6.5.8 OF A17.1-2007 (BULKHEAD REQUIREMENTS) | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | 1) PERFORM ANNUAL PRESSURE RELIEF AND HYDRAULIC SYSTEM TEST.TAG VALVE AND SUBMIT RESULTS TO ELEVATOR BUREAU. (A17-1A-1997 RULE 1005-2A) BOTH CARS, 2) PROVIDE WORKING 2 WAY COMMUNICATION (TELEPHONE) BOTH CARS, 3) REPAIR DOOR RESTRICTOR TO OPERATE PROPERLY BOTH CARS, 4) REPAIR DOOR PHOTO CELLS TO OPERATE PROPERLY BOTH CARS, 5) CLEAN ELEVATOR PITS AND INSTALL A SUMP PUMP COVER. 13-20-120,18-30-010 | 3525 W PETERSON AVE | PERIODIC | PASSED | View |
SEND EX. METAL LETTER | 3525 W PETERSON AVE | COMPLAINT | FAILED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN DEBRIS FROM CARTOPS AND DIVIDER BEAMS. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | FIRE SERVICE KEY BOX WITH 3 FIRE SERVICE KEYS REQUIRED IN MAIN LOBBY. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR #1-PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED. | 3525 W PETERSON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | OBTAIN A PERMIT TO MAKE NECESSARY REPAIRS TO COMPLY WITH CITY OF CHICAGO 2017 FIRE SERVICE MANDATE. | 3525 W PETERSON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST AND SUBMIT RESULTS | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR/REPLACE DOOR RESTRICTORS | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR/REPLACE FIRE SERVICE LIGHTS IN CARS | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE BROKEN ROLLER FIRST FL. HOISTWAY DOOR-WEST ELEV. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE AND MAINTAIN ON-SITE MAINTENANCE AND FIRE SERVICE LOGS | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | IDENTIFY BOTH ELEVATORS AT CAR OPERATING PANELS AND AT ALL LANDING DOOR FRAMES. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ALL LIGHTING REQUIRES GUARDS- PITS, CARTOPS,UNDER CARS. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN BOTH ELEVATOR PITS. | 3525 W PETERSON AVE | PERIODIC | FAILED | View |
MAINTAIN MECH. VENT SYSTEM | REPAIR INSULATION THAT IS CRUMBLING AWAY IN MECHANICAL ROOMS WHERE NEEDED | 3525 W PETERSON AVE | COMPLAINT | PASSED | View |
MAINTAIN MECH. VENT SYSTEM | BASEMENT AIR HANDLER IN NEED OF REPAIR TO STOP WATER LEAKAGE & PIPE FREEZING | 3525 W PETERSON AVE | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 3525 W PETERSON AVE | PERMIT | FAILED | View | |
ARRANGE COMPLETED PERMIT INSP. | 3525 W PETERSON AVE | PERMIT | FAILED | View | |
FIRE & WATER DAMAGE | 6TH FLOOR FIRE DAMAGE, PERMIT REQUIRED FOR ALL WORK. | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |
SYSTEM III | INSTALL BATTERY BACK-UP TYPE. | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |
ACCESS TO ROOF | 3525 W PETERSON AVE | PERIODIC | PASSED | View | |
PROTECT METAL MEMBERS | 3525 W PETERSON AVE | COMPLAINT | FAILED | View | |
SEE INSPECTOR COMMENTS | REPLACE 480V SO CARD USED TO SUPPLY RTUS FOR OVER A YEAR! | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |
NO PERMIT WIRING | NO PERMIT FOR TEMP WIRING FEEDERS 480V SO CARD SUPPLYING RTUS DUE TO FIRE DAMAGE FROM BASEMENT | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | RESTORE THROUGHOUT BLDG | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |
WORKING SPACE | PROVIDE 3' CLEARANCE MAIN SWBD IN BSMT ELECTRICAL RM | 3525 W PETERSON AVE | COMPLAINT | FAILED | View |