Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-23 @ 9:06 PM
PIN: 13014280330000
Property Address: 2600 W BRYN MAWR AVE
City - Zip: CHICAGO - 60659
2023 Property Class: 529
2023 Township: 71 - Jefferson
2023 Neighborhood: 71041
2023 Tax District: 71053
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 62 Violations
Violation Inspector Comments Address Category Status View
SEND EX. METAL LETTER END REPORT 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR HANDRAILS BRING HAND RAIL UP TO CODE 42 INCH HEIGHT 2600 W BRYN MAWR AVE COMPLAINT PASSED View
ARRANGE PREMISE INSPECTION NO ENTRY MOSTS UNITS. 2600 W BRYN MAWR AVE PERIODIC FAILED View
MAINTAIN WINDOW SOUTH ELEVATION AT EAST END WINDOWS BOWED OUT AT CENTER. 2600 W BRYN MAWR AVE PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS SMOKE DETECTOR NOT OPERATING UNIT 220. 2600 W BRYN MAWR AVE PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS UNIT 214 - SMOKE DETECTOR OUT OF SERVICE. 2600 W BRYN MAWR AVE PERIODIC FAILED View
ARRANGE PREMISE INSPECTION MOST UNITS- NO RESPONSE, UNVERIFIED DETECTORS, AND CONDITIONS. UNVERIFIED COMPLAINT OF: RODENT AND BEDBUG INFESTATION. 2600 W BRYN MAWR AVE PERIODIC FAILED View
RESTORE EXIT AND EM EMERGENCY LIGHTING THRUOUT- OUT OF SERVICE. 2600 W BRYN MAWR AVE PERIODIC FAILED View
PROVIDE PERMIT(S) TO CORRECT VIOLATIONS. (13-12-360) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPLCE WINDOW PANES, PLEXGLAS 1ST FLOOR 2600 W BRYN MAWR AVE PERIODIC FAILED View
INT WALL/CEILING PEELING PAINT 104 BATHROOM CEILING WATER DAMAGE,103 BATHROOM WALL BUBBLES IN SURFACE. 206 WATER DAMAGE OUTSIDE OF BATHROOM AS WELL AS BATHROOM CEILING. 2600 W BRYN MAWR AVE PERIODIC FAILED View
REPAIR EXTERIOR WALL SOUTH ELEVATION CRUMBLING MORTAR, SKIM COAT ON BRICK, 2600 W BRYN MAWR AVE PERIODIC FAILED View
INT WALL/CEILING CHIP PLASTER UNDER SIDE OF CAT WALK AT NORTH STAIRWELL. 2600 W BRYN MAWR AVE PERIODIC FAILED View
FLAKY INTERIOR PAINT UNIT DOORS, UNDERSIDE OF CAT WALK, SOUTH ELEVATION SIGN BACKING. 2600 W BRYN MAWR AVE PERIODIC FAILED View
NO PERMIT FLAT SIGN PROVIDE SIGN PERMIT(S). 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR EXTERIOR WALL EXTERIOR MASONRY WITH STRESS FRACTURES AT SOUTHWEST ELEVATION. WASHED OUT MORTAR AT NORTH ELEVATION. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
FIRE EXTNGSHR RECHARGE & TAG FIRE EXTINGUISHER NOT PROPERLY HUNG AT FRONT DESK - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
INTERIOR FINISH FIRERESISTANCE BASEMENT STORAGE ROOM AND FRONT DESK WITH WOOD PANELING ON WALLS - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR EXTERIOR DOOR FRAME METAL DOOR FRAME AT SOUTH ELEVATION LEADING TO BASEMENT DETERIORATED, RUSTED, AND ROTTED. METAL DOOR FRAME AT ELECTRICAL ROOM DETACHED FROM BUILDING. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR EXTERIOR DOOR METAL DOOR AT SOUTH ELEVATION LEADING TO BASEMENT DETERIORATED, RUSTED, AND ROTTED. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR EXTERIOR DOOR HARDWARE METAL DOOR AT SOUTH ELEVATION LEADING TO BASEMENT MISSING DOOR KNOB/LOCK. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR DOOR HARDWARE SELF-CLOSING DEVICE MISSING AT ELECTRICAL ROOM, INOPERABLE AT LAUNDRY ROOM, MISSING AT VARIOUS DOORS AT BASEMENT, MISSING ON ALL SLEEPING ROOMS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PROPER MATRL WATER SUPPLY PIPE REMOVE ALL UNAPPROVED FLEXIBLE SUPPLY LINES AT LAVATORY, TOILET AND KITCHEN SINK THROUGHOUT PREMISES AND PIPE ALL FIXTURES WITH COPPER SUPPLY LINES, ALL FLOORS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PRV FLOOR DRAIN WITH METAL STR OUTSIDE DRAIN AT OFFICE ENTRANCE DO NOT HAVE GRATE FOR SITE DRAIN. PROVIDE STRAINER FOR SITE DRAIN. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PRV BALLCOCK,VB,OR AIR GAP NO VACUUM BREAKER AT OUTSIDE HOSE BIB SOUTHEAST ELEVATION. INSTALL VACUUM BREAKER AT ALL HOSE CONNECTIONS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REMOVE REMOVE ALL UNAPPROVED FERNCO COUPLINGS AT SUMP PIT IN BASEMENT, VARIES SIZES AT ALL LOCATIONS AND THROUGHOUT PREMISES. (18-29-705.12.1) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPLACE DEFECTIVE FAUCET BROKEN HANDLE AT TUB FAUCET IN ROOM 214. REPLACE BROKEN HANDLE AT THIS LOCATION AND THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PROVIDE NO BACKFLOW DEVICE OBSERVED AT WASHING MACHINE IN THE LAUNDRY ROOM. PROVIDE BACKFLOW DEVICE. (18-29-608.1) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
OBTN PERMIT FOR PLUMBING WORK OBTAIN PERMIT FOR PLUMBING VIOLATIONS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
LICENSED BONDED PLMBG CONTRCTR OBTAIN LICENSED PLUMBER FOR CORRECTIONS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PROPER SIZE GRD ELECTRODE COND NO VISIBLE WATER GROUND. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
SEE INSPECTOR COMMENTS PROVIDE DEDICATED EQUIPMENT SPACE FOR ELECTRICAL SERVICE EQUIPMENT. PIPING SYSTEM APPEARS TO HAVE LEAKED CAUSING DAMAGE TO SERVICE EQUIPMENT IN MAIN ELECTRICAL ROOM. (14E-1-110.26) DANGEROUS AND HAZARDOUS 2600 W BRYN MAWR AVE COMPLAINT PASSED View
LIVE FRONT SWITCHBOARD REPLACE LIVE FRONT DISTRIBUTION EQUIPMENT IN MAIN ELECTRICAL ROOM AND WHERE REQUIRED THROUGHOUT. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
DEFECTIVE FEEDER FEEDER CONDUIT FROM MAIN ELECTRICAL ROOM TO LAUNDRY IS DAMAGED AT EXTERIOR. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PROVIDE ONE-LINE DIAGRAM AND LOAD CALCULATION FOR ELECTRICAL SERVICE AND ALL FEEDERS. (14E-2-215.5, 14E-2-220.40) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
DEFECTIVE FIXTURES REPAIR BROKEN/INOPERABLE LIGHT FIXTURES IN LAUNDRY AND WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
INSTALL GFCI PROTECTION BATHROOM ROOM 105 AND WHERE REQUIRED THROUGHOUT PREMISES. (14E-2-210.8) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CONTINUITY OF RACEWAYS PROVIDE GROUND CONTINUITY TO LIGHT FIXTURE ROOM 105 AND WHERE REQUIRED THROUGHOUT PREMISES. DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
UNIT SWITCH WITH OFF POSITION REQUIRED FOR ROOM SPACE HEATER ROOM 105 AND WHERE REQUIRED THROUGHOUT PREMISES. (14E-4-424.19) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
SUPPORT OUTLET AND BOX SUPPORT UNSUPPORTED BOXES THROUGHOUT EXTERIOR AND WHERE REQUIRED THROUGHOUT. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
INSTALL COVERS CLOSE OPEN BOXES AT EXTERIOR AND WHERE REQUIRED THROUGHOUT PREMISES - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
EXPOSED WIRING REMOVE OPEN WIRES PROTRUDING FROM CONDUIT AT FRONT EXTERIOR AND WHERE REQUIRED THROUGHOUT PREMISES - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
SYSTEM II INSTALL TYPE II EM SYSTEM WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
UNAPPROVED EM REMOVE UNAPPROVED BATTERY LIGHT/EXIT IN BASEMENT AND WHERE REQUIRED THROUGHOUT. (14E-7-700.6) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
INSTALL SMOKE DETECTORS MISSING SMOKE DETECTORS AT BASEMENT MECHANICAL ROOM, APARTMENT BEHIND FRONT DESK, LAUNDRY ROOM - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CARB MONOX DETECT IN HOTEL MISSING CARBON MONOXIDE DETECTORS AT BASEMENT MECHANICAL ROOM AND APARTMENT BEHIND FRONT DESK - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
REPAIR EXTERIOR DOOR DOOR DE-LAMINATING IN UNITS 210, 212, AND 214. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
DEFECTIVE SERVICE WATER DAMAGED/RUSTED MAIN SERVICE DISCONNECTS. OVERHEAD SERVICE CONDUCTORS DETERIORATED - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
WORKING SPACE PROVIDE WORKING SPACE ELECTRICAL PANEL LAUNDRY AND WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CLOSE BOX OPENINGS INSTALL MISSING KO FILLERS VARIOUS LOCATIONS LAUNDRY AND WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
SECURE RACEWAY SECURE UNSUPPORTED CONDUITS LAUNDRY ROOM AND WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CONTINUITY OF RACEWAYS REPAIR CONDUIT PULLED APART AT FITTING LAUNDRY ROOM AND WHERE REQUIRED THROUGHOUT PREMISES - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
ADD RECEPTACLES ADD RECEPTACLES TO EASE CORD USAGE THROUGHOUT 1ST FLOOR OFFICE/APARTMENT. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CORD TO FIXTURE SPLICED CORD TO LIGHT FIXTURE 1ST FLOOR OFFICE/APARTMENT BEDROOM - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CORRODED CONDUIT & EQUIP REPLACE CORRODED CONDUITS/BOXES/FITTINGS THROUGHOUT EXTERIOR AND WHERE REQUIRED THROUGHOUT PREMISES. (14E-3-300.10) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
SECURE RACEWAY SUPPORT UNSUPPORTED CONDUITS THROUGHOUT EXTERIOR AND WHERE REQUIRED THROUGHOUT. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
ABANDONED/DETERIORATED SIGN. (13-96-041) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
DEFECTIVE OUTLETS REPLACE CORRODED/BROKEN RECEPTACLES AND DEVICES ROOM 218 AND WHERE REQUIRED THROUGHOUT PREMISES. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
PROVIDE WALL SWITCH CONTROLLED ILLUMINATION GUEST ROOM AND BATHROOM 218 AND WHERE REQUIRED THROUGHOUT PREMISES. (14E-2-210.70) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
CONTINUITY OF RACEWAYS SEALTIGHT CONDUIT PULLED AWAY FROM HEATER 1ST FLOOR OFFICE/APARTMENT - DANGEROUS AND HAZARDOUS. 2600 W BRYN MAWR AVE COMPLAINT PASSED View
ALL EXTERIOR LIGHT FIXTURES, BOXES, FITTINGS MUST BE SUITABLE FOR WET LOCATION. (14E-1-110.3) 2600 W BRYN MAWR AVE COMPLAINT PASSED View
INSTALL COVERS COVER MISSING MAIN PHONE BOX LAUNDRY. 2600 W BRYN MAWR AVE COMPLAINT PASSED View