Chicago Building Violations Data: 79 Violations
Violation Inspector Comments Address Category Status View
CLASS B DOOR IN STAIRWELL 1ST AND 2ND FLR CORRIDOR HOTEL DOORS NOT FIRE RATED B CLASS DOORS. 6219 S ASHLAND AVE PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL 1ST AND 2ND FLR CORRIDOR HOTEL DOORS NOT FIRE RATED B CLASS DOORS. 6219 S ASHLAND AVE PERIODIC PASSED View
GRADE AND DRAIN LOT ASPHALT PARKING LOT POTHOLES THROUGHOUT. 6219 S ASHLAND AVE PERIODIC FAILED View
PROVIDE GUTTER & DOWNSPOUT REAR OF BUILDING OFF THE ALLEY MISSING DOWNSPOUT. 6219 S ASHLAND AVE PERIODIC FAILED View
OBSTRUCTIONS IN EXIT WAY GATE CHAINED AND PADLOCKED. 6219 S ASHLAND AVE PERIODIC FAILED View
GRADE AND DRAIN LOT ASPHALT PARKING LOT POTHOLES THROUGHOUT. 6219 S ASHLAND AVE PERIODIC FAILED View
PROVIDE GUTTER & DOWNSPOUT REAR OF BUILDING OFF THE ALLEY MISSING DOWNSPOUT. 6219 S ASHLAND AVE PERIODIC FAILED View
REMOVE EXPOSED CABLE NM CABLE (ROMEX) SUPPLYING WATER HEATER IN GARAGE. REMOVE. 6219 S ASHLAND AVE PERIODIC FAILED View
INSTALL SMOKE DETECTORS SMOKE DETECTORS ARE MISSING AT TOP OF THE STAIRS FRONT AND REAR. 6219 S ASHLAND AVE PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED EMERGENCY LIGHTS BATTERY PACKS ARE NOT WORKING. 6219 S ASHLAND AVE PERIODIC FAILED View
REPLACE DEFECTIVE SOIL PIPING THE NORTH AND SOUTH BASEMENTS HAVE DETERIORATING DRAIN, WASTE, VENT AND WATER PIPING. 6219 S ASHLAND AVE PERIODIC FAILED View
INDIRECT CONN.FOR WATER SUPPLY THE WATER SUPPLY PIPES TO EACH OF 2 BOILERS HAS BEEN INSTALLED WITHOUT USING APPROVED INDIRECT CONNECTION METHODS. 6219 S ASHLAND AVE PERIODIC FAILED View
PROVIDE THERE ARE MISSING COVERS TO EACH OF 2 EJECTOR PITS IN THE SOUTH BASEMENT. SEWER GAS AND FALL HAZARDS. PROVIDE COVERS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
ALL EXTERIOR LIGHT FIXTURES, BOXES, FITTINGS AND RACEWAYS MUST BE SUITABLE FOR WET CONDITIONS. A PERMIT IS REQUIRED TO MAKE CORRECTIONS. 14E-1-1103. 6219 S ASHLAND AVE PERIODIC FAILED View
PROVIDE TRAP FOR FIXTURE THERE ARE NO FIXTURE TRAPS TO BOTH WASHING MACHINES IN GARAGE LAUNDRY ROOM AND NORTH BASEMENT LAUNDRY TUB ... A CONDITION OF DANGEROUS AND HAZARDOUS SEWER GAS EXISTS. 6219 S ASHLAND AVE PERIODIC FAILED View
RATS THIS HOTEL IS RAT INFESTED. HIRE A LICENSED EXTERMINATOR CONTRACTOR. 14X-3-308. 6219 S ASHLAND AVE PERIODIC FAILED View
WINDOW REPAIR FOR AIR SEEPAGE UNIT 15 / THROUGH WALL AC UNIT - DRAFTY WITH AIR SEEPAGE. CB104075 - WINDOW REPAIR FOR AIR SEEPAGE (14X-3-303.13 AND 14X-12-1202.4.3.3) 6219 S ASHLAND AVE COMPLAINT FAILED View
REPAIR/REPLACE SMOKE DETECTORS UNIT 15 / SMOKE DETECTOR - BATTERY REMOVED BY TENANT. CB197079 - SMOKE ALARMS / DETECTORS - REPAIR / REPLACE ( 14X-1-103.2, 14X-1-103.3, 14X-5-504.1.1, 14X-5-504.10 AND 14A- 3-314.1.4 ) 6219 S ASHLAND AVE COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 6219 S ASHLAND AVE PERIODIC FAILED View
OCCUPIED WITHOUT REQ'D C OF O THERE IS NO CERTIFICATE OF OCCUPANCY ON FILE FOR THE CONTRUCTION PROJECT THAT ALTERED 3 SEPARATE BUILDINGS INTO A 36 UNIT HOTEL THAT NOW EXISTS. THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 6219 S ASHLAND AVE PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS THE CORRIDORS AND ROOMINF UNITS HAVE NUMEROUS DEFECTIVE SMOKE DETECTORS. 6219 S ASHLAND AVE PERIODIC FAILED View
CARB MONOX DETECT IN HOTEL THIS INSPECTION NOTED NO CARBON MONOXIDE DETECTORS IN THIS HOTEL. 6219 S ASHLAND AVE PERIODIC FAILED View
HOLDOPEN DEVICE ON APT DOOR ALL OF THE STAIRWELL FIRE DOORS WERE PROPPED OPEN IN VARIOUS WAYS. 6219 S ASHLAND AVE PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL THERE ARE NUMEROUS STAIRWELL DOORS WITH INOPERABLE SELF CLOSING DEVICES. 6219 S ASHLAND AVE PERIODIC FAILED View
H.P 2 HR ENCLOSURE THERE IS A BOILER IN BOTH THE 6219 AND THE 6227 BUILDING'S BASEMENTS. THE FIRE SEPARATIONS IS DAMAGED AND AT BEST, A MAKE-SHIFT ATTEMPT AT FIRE SEPARATION. EACH BOILER ROOM MUST HAVE WALLS AND CEILINGS OF AT LEAST 2 HOUR FIRE RESISTIVE MATERIAL. 6219 S ASHLAND AVE PERIODIC FAILED View
HEATING PLANT/BOILER ROOM DOOR THE EXISTING BOILER ROOM DOORS ARE DAMAGED / INOPERABLE / UNLABELED. 6219 S ASHLAND AVE PERIODIC FAILED View
POST FLOOR PLAN DIAGRAM THERE ARE NO POSTED FLOOR PLANS ANYWHERE IN THIS 36 UNIT HOTEL. 6219 S ASHLAND AVE PERIODIC FAILED View
PLANS & PERMITS REQUIRED A MASONRY GARAGE HAS BEEN CONSTRUCTED THAT IS CONNECTED TO THE EXISTING 36 UNIT HOTEL. NO PLANS OR PERMIT ON FILE FOR THIS GARAGE. 6219 S ASHLAND AVE PERIODIC FAILED View
HEAT UNIT ADEQUATELY CB132016.; ROOM # 15 TEMP WAS 64F AT 2:30PM. (14X-8-802.2, 14X-8-802.2.1 AND 14X-8-802.2.2). 6219 S ASHLAND AVE COMPLAINT FAILED View
SAFE WORKING CONDITIONS CB132046.- BOILER WAS OFF AT TIME OF INSPECTION 2:30PM. (14X-3-305-.1, 14X-8-804.1 THRU 14X-8-804.4 AND 14X-8-804.5) 6219 S ASHLAND AVE COMPLAINT FAILED View
SUPPLY HOT WTR MIN TEMP 120DEG CB154027.; ROOM #15, HOT WATER PROVIDED AT 64F. (14X-9-905.2, 14X-9-905.2.1 AND 14X-9-905.5). 6219 S ASHLAND AVE COMPLAINT FAILED View
OBSTRUCTIONS IN EXIT WAY GATE CHAINED AND PADLOCKED. 6219 S ASHLAND AVE PERIODIC FAILED View
TIGHT GARBAGE COVERS THIS HOTEL IS SEVERELLY RAT INFESTED. 6219 S ASHLAND AVE PERIODIC FAILED View
OBTAIN PERMIT FOR PLUMBING IF COMPREHENSIVE PLANS ARE APPROVED, WORK CANNOT BE STARTED UNTIL A PERMIT IS ISSUED. ALSO, FOR ANY WORK THAT CAN BE PERFORMED WITHOUT PLANS, AN EPP PERMIT MUST BE OBTAINED. 6219 S ASHLAND AVE PERIODIC FAILED View
CARB MONOX DETECT IN HOTEL THIS INSPECTION NOTED NO CARBON MONOXIDE DETECTORS IN THIS HOTEL. 14X-1-103.2. 6219 S ASHLAND AVE PERIODIC FAILED View
REPAIR DOOR, INT. THE BASEMENT ENTRY DOORS ARE RUSTED. THESE DOORS DO NOT CLOSH AND LATCH SHUT. 14X-3-304.6. 6219 S ASHLAND AVE PERIODIC FAILED View
POST FLOOR PLAN DIAGRAM THERE ARE NO POSTED FLOOR PLANS ANYWHERE IN THIS 36 UNIT HOTEL. 14A-8-804.1. 6219 S ASHLAND AVE PERIODIC FAILED View
FOUNDATION FOR FURNACE/BOILER HEATING UNIT WITHIN GARAGE / LAUNDRY SPACE NOT PROPERLY SUSPENDED WITH PROPER MATERIAL AND UNABLE TO VERIFY CONNECTIONS. DANGEROUS AND HAZARDOUS. 18-28-1004. 6219 S ASHLAND AVE PERIODIC FAILED View
SECURE RACEWAY THERE ARE LOOSE RACEWAYS IN BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
ENGAG LIC & BOND PLMBNG CNTRC ALL PLUMBING WORK MUST BE PERFORMED BY A LICENSED / BONDED PLUMBING CONTRACTOR. 6219 S ASHLAND AVE PERIODIC FAILED View
PRV FLUE FOR HOT WATER HEATER THE WATER HEATER HAS A BACK PITCHED EXHAUST FLUE PIPE IN THE NORTH BASEMENT. DANGEROUS AND HAZARDOUS POTENTIAL FOR CARBON MONOXIDE EMMISIONS. 6219 S ASHLAND AVE PERIODIC FAILED View
INSTALL COVERS THERE ARE OPEN BOXES AT BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
INSTALL GFCI'S INSTALL GFCI OUTLETS IN ALL BATHROOMS AND KITCHEN AREAS AS WELL AS ANY AREAS WHERE THERE IS POTENTIAL MOISTURE. 6219 S ASHLAND AVE PERIODIC FAILED View
HOLDOPEN DEVICE ON APT DOOR ALL OF THE STAIRWELL FIRE DOORS WERE PROPPED OPEN IN VARIOUS WAYS. 14X-5-505.8.4.2. 6219 S ASHLAND AVE PERIODIC FAILED View
STOP/REMOVE NUISANCE THERE IS A MOLD LIKE SUBSTANCE THROUGHOUT THE BASEMENT WALLS. 7-28-060. 6219 S ASHLAND AVE PERIODIC FAILED View
DEFECTIVE DISTRIBUTION VARIOUS PANELS APPEAR DETERIORATED AND DAMAGED. ENSURE DISTRIBUTION THROUGHOUT IN GOOD CONDITION. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
DEFECTIVE FIXTURES THERE ARE DAMAGED LIGHT FIXTURES IN BOTH BASEMENTS. 6219 S ASHLAND AVE PERIODIC FAILED View
1HR FLR OVER BSMT, 1 OR 2 DU THE ARE MULTIPLE AREAS OF THE BASEMENT CEILING WITH MISSING FIRE SEPARATION MATERIAL. DANGEROUS AND HAZARDOUS. 14X-5-502.3. 6219 S ASHLAND AVE PERIODIC FAILED View
CORRODED CONDUIT & EQUIP AT BOTH BASEMNTS AND THROUGHOUT THE PROPERTY THERE ARE CORRODED RACEWAYS, BOXES AND ELECTRICAL EQUIPMENT. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
HEATING PLANT/BOILER ROOM DOOR THE EXISTING BOILER ROOM DOORS ARE DAMAGED / INOPERABLE / UNLABELED. 14B-7-716. 6219 S ASHLAND AVE PERIODIC FAILED View
RESTORE EXIT AND EM THE BATTERY BACK UP LIGHTS AND EXIT SIGNS ARE UNAPPROVED, NUMEROUS BACK UP LIGHTS AND EXIT SIGNS ARE INOPERABLE. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
ARRANGE PREMISE INSPECTION A FULL INTERIOR INSPECTION IS REQUIRED TO INSPECT AREAS NOT YET INSPECTED. 14A-1-104.7. 6219 S ASHLAND AVE PERIODIC FAILED View
PROVIDE ADEQUATE SUPPORT IN BOTH BASEMENTS, THE SUSPENDED CAST IRON PIING IS POORLY SUPPORTED WITH UNAPPROVED FASTENERS. 6219 S ASHLAND AVE PERIODIC FAILED View
TIGHT GARBAGE COVERS THIS HOTEL IS SEVERELLY RAT INFESTED. 14X-3-302.1. 6219 S ASHLAND AVE PERIODIC FAILED View
PLANS & PERMITS REQ - CONTRCTR THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 14A-4-401.1. 6219 S ASHLAND AVE PERIODIC FAILED View
SOIL/WASTE,VENT PIPE MATRL THERE IS UNAPPROVED PVC INSTALLED TO THE LAUNDRY ROOM (DRAINAGE) WASTE, THE LAVATORIES AND COMPRESSION CLEAN OUT PLUGS. 6219 S ASHLAND AVE PERIODIC FAILED View
PRV DISCHARGE PIPE FROM PRV ALL LAVATORIES HAVE UNAPPROVED FLEXIBLE WATER PIPING. 6219 S ASHLAND AVE PERIODIC FAILED View
PROPER SIZE GRD ELECTRODE COND NO VISABLE WATER GROUNDS. ENSURE BOTH SERVICES GROUNDED IN APPROVED MANNER. DANGEROUS AND HAZARDOUS.ALSO, THERE ARE NUMEROUS PANELS AND DISCONNECTS COMPLETELY BLOCKED BY CLUTTER AND DEBRIS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
THERE IS A DAMAGED SIGN WITH OPEN WIRING AT THE FRONT OF THE HOTEL. DANGEROUS AND HAZARDOUS. 14E-1-1103. 6219 S ASHLAND AVE PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL THERE ARE NUMEROUS STAIRWELL DOORS WITH INOPERABLE SELF CLOSING DEVICES. 14X-5-502.8. 6219 S ASHLAND AVE PERIODIC FAILED View
INTERIOR FINISH FIRERESISTANCE THE ARE MISSING SECTIONS OF CEILING FIRE SEPARATION MATERIAL IN THE UPPER FLOORS BEHIND THE "DROPPED CEILINGS". DANGEROUS AND HAZARDOUS. 14B-8-803.1.1. 6219 S ASHLAND AVE PERIODIC FAILED View
DETERIORATED CONDUCTORS THERE IS DETERIORATED WIRING VISABLE AT OPEN BOXES IN BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
SEE INSPECTOR COMMENTS REQUIRED FIRE ALARM INSTALLED OPEN AIR CABLE. DAMAGED, HANGING, MISSING DEVICES. MAIN FA PANEL OPEN. DANGEROUS AND HAZARDOUS. 14E-7-760-180. 6219 S ASHLAND AVE PERIODIC FAILED View
OCCUPIED WITHOUT REQ'D C OF O THERE IS NO CERTIFICATE OF OCCUPANCY ON FILE FOR THE CONTRUCTION PROJECT THAT ALTERED 3 SEPARATE BUILDINGS INTO A 36 UNIT HOTEL THAT NOW EXISTS. THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 14A-4-401.1 6219 S ASHLAND AVE PERIODIC FAILED View
REMOVE STAGNANT WATER BSMT THERE IS STANDING WATER IN THE SOUTH BASEMENT BOILER ROOM. THERE IS STANDING RAW SEWAGE IN BOTH THE NORTH AND SOUTH BASEMENTS. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
GRADE AND DRAIN LOT THE PARKING LOT HAS AREAS OF AN UNEVEN GRADIENT. 14X-3-302.2. 6219 S ASHLAND AVE PERIODIC FAILED View
STRUCTURAL MEMBER, PIER BLOCK THERE ARE NUMEROUS TEMPORARY SHORING [POSTS IN THE BASEMENT BEING USED AS PERMANENT STRUCTURAL MEMBERS SUPPORTING THE 1ST FLOOR. DANGEROUS AND NHAZARDOUS. 14B-8-803.1.1. 6219 S ASHLAND AVE PERIODIC FAILED View
PLANS & PERMITS REQUIRED A MASONRY GARAGE HAS BEEN CONSTRUCTED THAT IS CONNECTED TO THE EXISTING 36 UNIT HOTEL. NO PLANS OR PERMIT ON FILE FOR THIS GARAGE. 14A-4-401.1. 6219 S ASHLAND AVE PERIODIC FAILED View
1HR ENCL FLR TO FLR SHAFT/DUCT ALL PIPE PENETRATIONS IN THE BASEMENT ARE WITHOUT REQUIRED FIRE CAULKING. 14X-5-502.3. 6219 S ASHLAND AVE PERIODIC FAILED View
DEFECTIVE SERVICE NORTH SERVICE. THE OVERHEAD UTILITY SPLICE IS COMPLETELY UNINSULATED. THE MAIN DISCONNECT IS DAMAGED. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS.SOUTH SERVICE. THE MAIN DISCONNECT APPEARS WATER DAMAGED AND DETERIORATED. UNABLE TO DO A CLOSE UP INSPECTION DUE TO LARGE AMOUNTS OF RAW SEWAGE. ENSURE SERVICE IN GOOD CONDITION. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
H.P 2 HR ENCLOSURE THERE IS A BOILER IN BOTH THE 6219 AND THE 6227 BUILDING'S BASEMENTS. THE FIRE SEPARATIONS IS DAMAGED AND AT BEST, A MAKE-SHIFT ATTEMPT AT FIRE SEPARATION. EACH BOILER ROOM MUST HAVE WALLS AND CEILINGS OF AT LEAST 2 HOUR FIRE RESISTIVE MATERIAL. 14B-406.2.9.1. 6219 S ASHLAND AVE PERIODIC FAILED View
REPLACE DEFECTIVE WATER PIPING THE NORTH AND SOUTH BASEMENTS HAVE DETERIORATING OR UNUSED PIPING. 6219 S ASHLAND AVE PERIODIC FAILED View
RMV PLBFIX INSTALLD W/0 PERMIT REMOVE ALL PLUMBING FIXTURES, WATER SUPPLY, VENT, SOIL AND WASTE PIPING INSTALLED WITHOUT PERMIT. SPECIFICALLY THE GARAGE LAUNDRY ROOM. 6219 S ASHLAND AVE PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS THE CORRIDORS AND ROOMINF UNITS HAVE NUMEROUS DEFECTIVE SMOKE DETECTORS.14X-5-504.8. 6219 S ASHLAND AVE PERIODIC FAILED View
FIRE EXTNGSHR RECHARGE & TAG THE FIRE EXTINGUISHER CERTIFICATION TAGS ARE EXPIRED. 14X-5-504.5. 6219 S ASHLAND AVE PERIODIC FAILED View
SUPPORT OUTLET AND BOX THERE ARE LOOSE / FALLEN BOXES AT BOTH BASEMENTS AND THROUGHOUT THIS PROPERTY. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
SUBMIT PLANS FOR PLUMBING PRMT SUBMIT PLANS TO THE WATER, SEWER AND BUILDING DEPARTMENTS FOR REVIEW AND OBTAIN PERMIT IF APPROVED BEFORE DOING ANY FURTHER (CORRECTIVE) WORK. 6219 S ASHLAND AVE PERIODIC FAILED View
EXPOSED WIRING THERE IS OPEN WIRING AT BOTH BASEMENTS AND THE MECHANICAL ROOM. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View
UNAPPROVED CORDS IN BOTH BASEMENTS THERE ARE NUMEROUS DAMAGED EXTENSION CORDS IN USE. DANGEROUS AND HAZARDOUS. 6219 S ASHLAND AVE PERIODIC FAILED View