Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CLASS B DOOR IN STAIRWELL | 1ST AND 2ND FLR CORRIDOR HOTEL DOORS NOT FIRE RATED B CLASS DOORS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | 1ST AND 2ND FLR CORRIDOR HOTEL DOORS NOT FIRE RATED B CLASS DOORS. | 6219 S ASHLAND AVE | PERIODIC | PASSED | View |
GRADE AND DRAIN LOT | ASPHALT PARKING LOT POTHOLES THROUGHOUT. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PROVIDE GUTTER & DOWNSPOUT | REAR OF BUILDING OFF THE ALLEY MISSING DOWNSPOUT. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | GATE CHAINED AND PADLOCKED. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
GRADE AND DRAIN LOT | ASPHALT PARKING LOT POTHOLES THROUGHOUT. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PROVIDE GUTTER & DOWNSPOUT | REAR OF BUILDING OFF THE ALLEY MISSING DOWNSPOUT. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REMOVE EXPOSED CABLE | NM CABLE (ROMEX) SUPPLYING WATER HEATER IN GARAGE. REMOVE. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | SMOKE DETECTORS ARE MISSING AT TOP OF THE STAIRS FRONT AND REAR. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | EMERGENCY LIGHTS BATTERY PACKS ARE NOT WORKING. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REPLACE DEFECTIVE SOIL PIPING | THE NORTH AND SOUTH BASEMENTS HAVE DETERIORATING DRAIN, WASTE, VENT AND WATER PIPING. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
INDIRECT CONN.FOR WATER SUPPLY | THE WATER SUPPLY PIPES TO EACH OF 2 BOILERS HAS BEEN INSTALLED WITHOUT USING APPROVED INDIRECT CONNECTION METHODS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PROVIDE | THERE ARE MISSING COVERS TO EACH OF 2 EJECTOR PITS IN THE SOUTH BASEMENT. SEWER GAS AND FALL HAZARDS. PROVIDE COVERS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
ALL EXTERIOR LIGHT FIXTURES, BOXES, FITTINGS AND RACEWAYS MUST BE SUITABLE FOR WET CONDITIONS. A PERMIT IS REQUIRED TO MAKE CORRECTIONS. 14E-1-1103. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View | |
PROVIDE TRAP FOR FIXTURE | THERE ARE NO FIXTURE TRAPS TO BOTH WASHING MACHINES IN GARAGE LAUNDRY ROOM AND NORTH BASEMENT LAUNDRY TUB ... A CONDITION OF DANGEROUS AND HAZARDOUS SEWER GAS EXISTS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
RATS | THIS HOTEL IS RAT INFESTED. HIRE A LICENSED EXTERMINATOR CONTRACTOR. 14X-3-308. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
WINDOW REPAIR FOR AIR SEEPAGE | UNIT 15 / THROUGH WALL AC UNIT - DRAFTY WITH AIR SEEPAGE. CB104075 - WINDOW REPAIR FOR AIR SEEPAGE (14X-3-303.13 AND 14X-12-1202.4.3.3) | 6219 S ASHLAND AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | UNIT 15 / SMOKE DETECTOR - BATTERY REMOVED BY TENANT. CB197079 - SMOKE ALARMS / DETECTORS - REPAIR / REPLACE ( 14X-1-103.2, 14X-1-103.3, 14X-5-504.1.1, 14X-5-504.10 AND 14A- 3-314.1.4 ) | 6219 S ASHLAND AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
OCCUPIED WITHOUT REQ'D C OF O | THERE IS NO CERTIFICATE OF OCCUPANCY ON FILE FOR THE CONTRUCTION PROJECT THAT ALTERED 3 SEPARATE BUILDINGS INTO A 36 UNIT HOTEL THAT NOW EXISTS. THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | THE CORRIDORS AND ROOMINF UNITS HAVE NUMEROUS DEFECTIVE SMOKE DETECTORS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
CARB MONOX DETECT IN HOTEL | THIS INSPECTION NOTED NO CARBON MONOXIDE DETECTORS IN THIS HOTEL. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
HOLDOPEN DEVICE ON APT DOOR | ALL OF THE STAIRWELL FIRE DOORS WERE PROPPED OPEN IN VARIOUS WAYS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | THERE ARE NUMEROUS STAIRWELL DOORS WITH INOPERABLE SELF CLOSING DEVICES. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
H.P 2 HR ENCLOSURE | THERE IS A BOILER IN BOTH THE 6219 AND THE 6227 BUILDING'S BASEMENTS. THE FIRE SEPARATIONS IS DAMAGED AND AT BEST, A MAKE-SHIFT ATTEMPT AT FIRE SEPARATION. EACH BOILER ROOM MUST HAVE WALLS AND CEILINGS OF AT LEAST 2 HOUR FIRE RESISTIVE MATERIAL. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
HEATING PLANT/BOILER ROOM DOOR | THE EXISTING BOILER ROOM DOORS ARE DAMAGED / INOPERABLE / UNLABELED. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
POST FLOOR PLAN DIAGRAM | THERE ARE NO POSTED FLOOR PLANS ANYWHERE IN THIS 36 UNIT HOTEL. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PLANS & PERMITS REQUIRED | A MASONRY GARAGE HAS BEEN CONSTRUCTED THAT IS CONNECTED TO THE EXISTING 36 UNIT HOTEL. NO PLANS OR PERMIT ON FILE FOR THIS GARAGE. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
HEAT UNIT ADEQUATELY | CB132016.; ROOM # 15 TEMP WAS 64F AT 2:30PM. (14X-8-802.2, 14X-8-802.2.1 AND 14X-8-802.2.2). | 6219 S ASHLAND AVE | COMPLAINT | FAILED | View |
SAFE WORKING CONDITIONS | CB132046.- BOILER WAS OFF AT TIME OF INSPECTION 2:30PM. (14X-3-305-.1, 14X-8-804.1 THRU 14X-8-804.4 AND 14X-8-804.5) | 6219 S ASHLAND AVE | COMPLAINT | FAILED | View |
SUPPLY HOT WTR MIN TEMP 120DEG | CB154027.; ROOM #15, HOT WATER PROVIDED AT 64F. (14X-9-905.2, 14X-9-905.2.1 AND 14X-9-905.5). | 6219 S ASHLAND AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | GATE CHAINED AND PADLOCKED. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
TIGHT GARBAGE COVERS | THIS HOTEL IS SEVERELLY RAT INFESTED. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
OBTAIN PERMIT FOR PLUMBING | IF COMPREHENSIVE PLANS ARE APPROVED, WORK CANNOT BE STARTED UNTIL A PERMIT IS ISSUED. ALSO, FOR ANY WORK THAT CAN BE PERFORMED WITHOUT PLANS, AN EPP PERMIT MUST BE OBTAINED. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
CARB MONOX DETECT IN HOTEL | THIS INSPECTION NOTED NO CARBON MONOXIDE DETECTORS IN THIS HOTEL. 14X-1-103.2. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | THE BASEMENT ENTRY DOORS ARE RUSTED. THESE DOORS DO NOT CLOSH AND LATCH SHUT. 14X-3-304.6. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
POST FLOOR PLAN DIAGRAM | THERE ARE NO POSTED FLOOR PLANS ANYWHERE IN THIS 36 UNIT HOTEL. 14A-8-804.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
FOUNDATION FOR FURNACE/BOILER | HEATING UNIT WITHIN GARAGE / LAUNDRY SPACE NOT PROPERLY SUSPENDED WITH PROPER MATERIAL AND UNABLE TO VERIFY CONNECTIONS. DANGEROUS AND HAZARDOUS. 18-28-1004. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
SECURE RACEWAY | THERE ARE LOOSE RACEWAYS IN BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | ALL PLUMBING WORK MUST BE PERFORMED BY A LICENSED / BONDED PLUMBING CONTRACTOR. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PRV FLUE FOR HOT WATER HEATER | THE WATER HEATER HAS A BACK PITCHED EXHAUST FLUE PIPE IN THE NORTH BASEMENT. DANGEROUS AND HAZARDOUS POTENTIAL FOR CARBON MONOXIDE EMMISIONS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
INSTALL COVERS | THERE ARE OPEN BOXES AT BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
INSTALL GFCI'S | INSTALL GFCI OUTLETS IN ALL BATHROOMS AND KITCHEN AREAS AS WELL AS ANY AREAS WHERE THERE IS POTENTIAL MOISTURE. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
HOLDOPEN DEVICE ON APT DOOR | ALL OF THE STAIRWELL FIRE DOORS WERE PROPPED OPEN IN VARIOUS WAYS. 14X-5-505.8.4.2. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | THERE IS A MOLD LIKE SUBSTANCE THROUGHOUT THE BASEMENT WALLS. 7-28-060. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
DEFECTIVE DISTRIBUTION | VARIOUS PANELS APPEAR DETERIORATED AND DAMAGED. ENSURE DISTRIBUTION THROUGHOUT IN GOOD CONDITION. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
DEFECTIVE FIXTURES | THERE ARE DAMAGED LIGHT FIXTURES IN BOTH BASEMENTS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | THE ARE MULTIPLE AREAS OF THE BASEMENT CEILING WITH MISSING FIRE SEPARATION MATERIAL. DANGEROUS AND HAZARDOUS. 14X-5-502.3. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
CORRODED CONDUIT & EQUIP | AT BOTH BASEMNTS AND THROUGHOUT THE PROPERTY THERE ARE CORRODED RACEWAYS, BOXES AND ELECTRICAL EQUIPMENT. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
HEATING PLANT/BOILER ROOM DOOR | THE EXISTING BOILER ROOM DOORS ARE DAMAGED / INOPERABLE / UNLABELED. 14B-7-716. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
RESTORE EXIT AND EM | THE BATTERY BACK UP LIGHTS AND EXIT SIGNS ARE UNAPPROVED, NUMEROUS BACK UP LIGHTS AND EXIT SIGNS ARE INOPERABLE. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | A FULL INTERIOR INSPECTION IS REQUIRED TO INSPECT AREAS NOT YET INSPECTED. 14A-1-104.7. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PROVIDE ADEQUATE SUPPORT | IN BOTH BASEMENTS, THE SUSPENDED CAST IRON PIING IS POORLY SUPPORTED WITH UNAPPROVED FASTENERS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
TIGHT GARBAGE COVERS | THIS HOTEL IS SEVERELLY RAT INFESTED. 14X-3-302.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 14A-4-401.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | THERE IS UNAPPROVED PVC INSTALLED TO THE LAUNDRY ROOM (DRAINAGE) WASTE, THE LAVATORIES AND COMPRESSION CLEAN OUT PLUGS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PRV DISCHARGE PIPE FROM PRV | ALL LAVATORIES HAVE UNAPPROVED FLEXIBLE WATER PIPING. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PROPER SIZE GRD ELECTRODE COND | NO VISABLE WATER GROUNDS. ENSURE BOTH SERVICES GROUNDED IN APPROVED MANNER. DANGEROUS AND HAZARDOUS.ALSO, THERE ARE NUMEROUS PANELS AND DISCONNECTS COMPLETELY BLOCKED BY CLUTTER AND DEBRIS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
THERE IS A DAMAGED SIGN WITH OPEN WIRING AT THE FRONT OF THE HOTEL. DANGEROUS AND HAZARDOUS. 14E-1-1103. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View | |
CLASS B DOOR IN STAIRWELL | THERE ARE NUMEROUS STAIRWELL DOORS WITH INOPERABLE SELF CLOSING DEVICES. 14X-5-502.8. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
INTERIOR FINISH FIRERESISTANCE | THE ARE MISSING SECTIONS OF CEILING FIRE SEPARATION MATERIAL IN THE UPPER FLOORS BEHIND THE "DROPPED CEILINGS". DANGEROUS AND HAZARDOUS. 14B-8-803.1.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
DETERIORATED CONDUCTORS | THERE IS DETERIORATED WIRING VISABLE AT OPEN BOXES IN BOTH BASEMENTS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
SEE INSPECTOR COMMENTS | REQUIRED FIRE ALARM INSTALLED OPEN AIR CABLE. DAMAGED, HANGING, MISSING DEVICES. MAIN FA PANEL OPEN. DANGEROUS AND HAZARDOUS. 14E-7-760-180. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
OCCUPIED WITHOUT REQ'D C OF O | THERE IS NO CERTIFICATE OF OCCUPANCY ON FILE FOR THE CONTRUCTION PROJECT THAT ALTERED 3 SEPARATE BUILDINGS INTO A 36 UNIT HOTEL THAT NOW EXISTS. THIS CONCERNS AN ENTITY / BUILDING(S) KNOWN AS THE TOLEDO HOTEL. THIS HOTEL WAS ORIGINALLY 3 SEPARATE BUILDINGS ACCORDING TO THE CITY'S ZONING MAP (6219 S. ASHLAND, 6221-25 S. ASHLAND AND 6227 S. ASHLAND). WHAT EXISTS NOW ARE 3 BUILDINGS JOINED TOGETHER TO FORM A 36 UNIT HOTEL VIA A CONSTRUCTION PROCESS THAT JOINED THE 3 SEPARATE BUILDINGS INTO ONE. THE 6219 AND THE 6227 BUILDINGS ARE ORIGINALLY 2 STORY BRICK BUILDINGS WITH A 1ST FLOOR COMMERCIAL UNIT AND 2CD FLOOR DWELLING UNIT. THESE 2 BUILDINGS ARE JOINED TOGETHER BY A 1 STORY BUILDING SET AT THE BACK OF THE LOT. THERE WAS A COMPLETE GUT REHAB / ALTERATION TO INSTALL 36 HOTEL ROOMING UNITS THAT INCLUDED NEW ELECTRICAL PIPING / WIRING AND FIXTURES; NEW PLUMBING PIPING / FIXTURES; REMOVAL AND RECONFIGURATION OF PARTION AND LOAD BARING WALLS AND MUCH MORE RELATED WORK. THERE IS NO RECORD OF ARCHETECTURAL DRAWINGS HAVING BEEN SUBMITTED FOR REVIEW FOR THIS PROJECT AND NO RENOVATION PERMIT FOR THIS PROJECT IS ON FILE. 14A-4-401.1 | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REMOVE STAGNANT WATER BSMT | THERE IS STANDING WATER IN THE SOUTH BASEMENT BOILER ROOM. THERE IS STANDING RAW SEWAGE IN BOTH THE NORTH AND SOUTH BASEMENTS. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
GRADE AND DRAIN LOT | THE PARKING LOT HAS AREAS OF AN UNEVEN GRADIENT. 14X-3-302.2. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
STRUCTURAL MEMBER, PIER BLOCK | THERE ARE NUMEROUS TEMPORARY SHORING [POSTS IN THE BASEMENT BEING USED AS PERMANENT STRUCTURAL MEMBERS SUPPORTING THE 1ST FLOOR. DANGEROUS AND NHAZARDOUS. 14B-8-803.1.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
PLANS & PERMITS REQUIRED | A MASONRY GARAGE HAS BEEN CONSTRUCTED THAT IS CONNECTED TO THE EXISTING 36 UNIT HOTEL. NO PLANS OR PERMIT ON FILE FOR THIS GARAGE. 14A-4-401.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
1HR ENCL FLR TO FLR SHAFT/DUCT | ALL PIPE PENETRATIONS IN THE BASEMENT ARE WITHOUT REQUIRED FIRE CAULKING. 14X-5-502.3. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
DEFECTIVE SERVICE | NORTH SERVICE. THE OVERHEAD UTILITY SPLICE IS COMPLETELY UNINSULATED. THE MAIN DISCONNECT IS DAMAGED. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS.SOUTH SERVICE. THE MAIN DISCONNECT APPEARS WATER DAMAGED AND DETERIORATED. UNABLE TO DO A CLOSE UP INSPECTION DUE TO LARGE AMOUNTS OF RAW SEWAGE. ENSURE SERVICE IN GOOD CONDITION. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
H.P 2 HR ENCLOSURE | THERE IS A BOILER IN BOTH THE 6219 AND THE 6227 BUILDING'S BASEMENTS. THE FIRE SEPARATIONS IS DAMAGED AND AT BEST, A MAKE-SHIFT ATTEMPT AT FIRE SEPARATION. EACH BOILER ROOM MUST HAVE WALLS AND CEILINGS OF AT LEAST 2 HOUR FIRE RESISTIVE MATERIAL. 14B-406.2.9.1. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REPLACE DEFECTIVE WATER PIPING | THE NORTH AND SOUTH BASEMENTS HAVE DETERIORATING OR UNUSED PIPING. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | REMOVE ALL PLUMBING FIXTURES, WATER SUPPLY, VENT, SOIL AND WASTE PIPING INSTALLED WITHOUT PERMIT. SPECIFICALLY THE GARAGE LAUNDRY ROOM. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | THE CORRIDORS AND ROOMINF UNITS HAVE NUMEROUS DEFECTIVE SMOKE DETECTORS.14X-5-504.8. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | THE FIRE EXTINGUISHER CERTIFICATION TAGS ARE EXPIRED. 14X-5-504.5. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
SUPPORT OUTLET AND BOX | THERE ARE LOOSE / FALLEN BOXES AT BOTH BASEMENTS AND THROUGHOUT THIS PROPERTY. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
SUBMIT PLANS FOR PLUMBING PRMT | SUBMIT PLANS TO THE WATER, SEWER AND BUILDING DEPARTMENTS FOR REVIEW AND OBTAIN PERMIT IF APPROVED BEFORE DOING ANY FURTHER (CORRECTIVE) WORK. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
EXPOSED WIRING | THERE IS OPEN WIRING AT BOTH BASEMENTS AND THE MECHANICAL ROOM. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |
UNAPPROVED CORDS | IN BOTH BASEMENTS THERE ARE NUMEROUS DAMAGED EXTENSION CORDS IN USE. DANGEROUS AND HAZARDOUS. | 6219 S ASHLAND AVE | PERIODIC | FAILED | View |