Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CARB MONOX DETECT IN RESID | CO DETECTOR MISSING IN BOILER RM 2A BUILING 2ND FLOOR | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | CO DETECTOR MISSING IN BOILER RM 2A BUILING 2ND FLOOR | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TESTING OF ALL ELEVATORS & PROVIDE TAGS ON EQIPMENT & DOCUMENTATION IN MACHINE ROOMS AS REQUIRED BY CODE. | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | GUARD REQUIRED FOR CAR TOP LIGHTING ON ALL ELEVATORS. | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERLY SECURE 1ST FLOOR DOOR UNLOCKING DEVICE. 7-BLD 6117 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PULL STRAPS REQUIRED ON VERTICAL CAR GATES.7-BLDG 6117 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CURRENT MONTHLY FIRE SERVICE TEST LOG ON SITE. REAR-15A 5641 & 12-A 7129 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR ALARMBELL. 15-A 5641 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR OR REPLACE CAR DOOR RESTRICTING DEVICE. 12-A 7129 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
PRV HIGH SIDE | FOR ONE POMONA AIR / CARLYLE UNIT LOCATED IN BLDG 6 SOUTH MEZZ. TWO COMPRESSORS,R-22,AIR COOLED,SELF CONTAINED | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR ONE POMONA AIR / CARLYLE UNIT LOCATED IN BLDG. 6 SOUTH MEZZ. TWO COMPRESSORS. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
PROVIDE MINIMUM VENT QUANTITY | MECHANICAL VENTILATION INSURE MINIMUM AIR QUANTITIES 18-28-403 | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
GIVE VENT OPENINGS % FL. AREA | BLDG 3 1ST FLR MENS/WOMEN'S TOILETS EXHAUST FANS NOT WORKING WOMAN'S BATHROOM/LOUNGE/LOCKER ROOM-BLDG3/1ST FLR NO WALL SEPARATING AREAS FROM TOILET SPACE | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
ARRANGE ANNUAL INSP. | ARRANGE FOR ANNUAL INSPECTION 13-20-290, 13-20-020 | 6601 N RIDGE BLVD | COMPLAINT | PASSED | View |
PROVIDE MINIMUM VENT QUANTITY | MECHANICAL VENTILATION INSURE MINIMUM AIR QUANTITIES 18-28-403 | 6601 N RIDGE BLVD | COMPLAINT | PASSED | View |
GIVE VENT OPENINGS % FL. AREA | BLDG 3,1ST FLOOR MENS.WOMEN'S EXHAUST FANS TOILET NOT WORKING WOMEN'S BATHROOM & LOUNGE ROOM NO WALL SEPARATING AREAS FROM TOILET SPACE LOCKER ROOMS NO RETICULATION OF AIR PERMITTED IN SPACES 0.3 SUPPLY, 1.2 EXHAUST PER SQ FT OF AREA 18-28-403.3 NOT 5 | 6601 N RIDGE BLVD | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 5 TEST. TAG AND DOCUMENT AS REQUIRED. - ALL ELEVATORS. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSCRIBED CODE DATA TAGS REQUIRED ON ELEVATOR CONTROLLERS. - ALL ELEVATORS. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAINTENANCE CONTROL PROGRAMS REQUIRED TO BE ON SITE FOR ALL ELEVATORS. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH SECTION 8.6.5.8 OF A17.1-2007 (BULKHEAD REQUIREMENTS. ASSETS 6084,6363, AND 6117. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN AREA AROUN CONTROLLER AND PUMPING UNIT FOR ASSET 6117. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN AREA AROUND CONTROLLER AND PUMPING UNIT FOR ASSET 6117. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 5 TEST. TAG AND DOCUMENT AS REQUIRED. - ALL ELEVATORS.(PREVIOUSLY CITED) | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
ARRANGE ANNUAL INSP. | ARRANGE FOR ANNUAL INSPECTION | 6601 N RIDGE BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SHOW PROOF OF COMPLIANCE WITH SECTION 8.6.5.8 OF A17.1-2007 (BULKHEAD REQUIREMENTS. ASSETS 6084,6363, AND 6117.(PREVIOUSLY CITED) | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN AREA AROUND CONTROLLER AND PUMPING UNIT FOR ASSET 6117.(PREVIOUSLY CITED) | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: ASSET 6084 (BLDG 12) 1.IN CAR STOP SWITCH MUST ACTIVATE ALARM BELL 2.ADJUST AND LUBE CAR GATES AND LANDING DOORS AS REQUIRED TO OPEN AND CLOSE PROPERLY 3.INSTALL PULL STRAPS WHERE MISSING ON CAR GATES AND LANDING DOORS. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSCRIBED CODE DATA TAGS REQUIRED ON ELEVATOR CONTROLLERS. - ALL ELEVATORS.(PREVIOUSLY CITED) | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAINTENANCE CONTROL PROGRAMS REQUIRED TO BE ON SITE FOR ALL ELEVATORS.(PREVIOUSLY CITED) | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: ASSET 6362 (BLDG 6) 1. INSTALL PULL STRAPS ON CAR GATES AND LANDING DOORS WHERE MISSING. 2. IN CAR STOP SWITCH MUST ACTIVATE ALARM BELL 3. CLEAN ELEVATOR PIT. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: ASSET 8457 (BLDG 14A)A CURRENT FIRE SERVICE MONTHLY TEST LOG IS REQUIRED ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE: ASSET 8361 (ATC BLDG) 1. REPAIR MALFUNCTIONING ALARM BELL 2. LOCATE AND CORRECT SOURCE OF EXCESSIVE VIBRATION IN DOWN DIRECTION. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: ASSET 6363 (LAB BLDG) IN CAR STOP SWITCH MUST ACTIVATE ALARM BELL. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE: ASSET 5641 ( BLDG 15A) REPAIR FIRE SERVICE TO OPERATE PROPERLY - SEE FIRE SERVICE MANDATE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 5641: (BLDG 15A PASSENGER ELEVATOR):1) CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. 2) A CURRENT MONTHLY FIRE SERVICE MONTHLY TEST LOG IS REQUIRED TO BE ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 6363: (LAB BLDG FREIGHT): 1)CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. 2)MAINTENANCE CONTROL PROGRAM IS REQUIRED TO BE ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 7129 (BLDG 12A PASSENGER): REPAIR 1ST FLOOR LANDING DOOR AS NECESSARY TO PLACE ELEVATOR BACK IN SERVICE. 2)CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 6084: (BLDG 12 FREIGHT): 1) CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED.2)CLEAN ELEVATOR MACHINE ROOM-NOT TO BE USED FOR STORAGE.3)MAINTENANCE CONTROL PROGRAM IS REQUIRED TO BE ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR DUMBWTR | ASSET 6283: (BLDG 17 DUMBWAITER) REPAIR AND MAINTAIN DUMBWAITER. OUT OF SERVICE AT TIME OF THIS INSPECTION. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ASSET 8457: (BLDG 14A)PASSENGER ELEVATOR: 1)CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. 2) MAINTENANCE CONTROL PROGRAM REQUIRED TO BE ON SITE.3)CURRENT MONTHLY FIRE TEST LOG IS REQUIRED TO BE ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 8361: (ATC PASSENGER ELEVATOR):1)CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. 2)MAINTENANCE CONTROL PREORAM REQUIRED TO BE ON SITE.3) A CURRENT MONTHLY FIRE SERVICE TEST LOG IS REQUIRED TO BE ON SITE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ASSET 6362 (BLDG 6 FREIGHT):1) CATEGORY 1 TEST OVERDUE. TAG AND DOCUMENT AS REQUIRED. 2)MAINTENANCE CONTROL PROGRAM IS REQUIRED TO BE ON SITE. 3) BALANCE CAR GATE TO KEEP GATE FROM CLOSING BY ITSELF. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |
MAINT PLATFORM LIFT | ASSET 6118 (BLDG 7 PLATFORM LIFT) REPAIR OR REPLACE DEFECTIVE PROXIMITY SWITCH ON TOP LANDING GATE. | 6601 N RIDGE BLVD | PERIODIC | FAILED | View |