Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
POST APPROVED OCCUPANCY CARD | NO VISIBLE OCCUPANCY CARD POSTED. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OBSTRUCTIONS IN EXIT WAY | REAR SECONDARY EGRESS IS LOCATED BEHIND EMPLOYEE AREA (BAR). OPENING BETWEEN PERIMETER WALL AND BAR TOP LESS THAN 36 INCHES, BETWEEN BACK BAR AND COOLERS LESS THAN 36 INCHES. REAR YARD GATE CHAINED AND PADLOCKED. LARGE AMOUNTS OF GARBAGE AND DEBRIS BLOCKING REAR GATE - DANGEROUS AND HAZARDOUS. (13-160-010, 13-196-050, 13-200-330) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REMOVE | BASEMENT STAIRWAY LOADED WITH STOCK BLOCKING PATH OF TRAVEL. (15-4-880) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE OPEN FRONT TOILET SEAT | FIRST FLOOR, MENS BATHROOM - TOILET REMOVE ROUND FRONT TOILET, INSTALL AN ELONGATED TOILET WITH AN OPEN FRONT TOILET SEAT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
EXPOSED WIRING | REMOVE ALL EXPOSED WIRING AT PANELS, 1ST FLOOR AND BASEMENT - DANGEROUS AND HAZARDOUS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PRV FLUE FOR HOT WATER HEATER | BASEMENT - WATER HEATERS (2) FLUE PIPE IS BACK PITCHED - REALIGN AND INSTALL WITH PROPER PITCH. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPAIR DEFECTIVE FITTINGS | BASEMENT - WATER HEATERS, REMOVE FLEX GAS CONNECTORS AND REPIPE WITH BLACK STEEL PIPE AND FITTINGS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OBSTRUCTIONS IN EXIT WAY | SECONDARY MEANS OF EGRESS FOR SECOND FLOOR TENANT, THROUGH REAR YARD, IS BLOCKED WITH GARBAGE AND DEBRIS. REAR GATE CHAINED AND PADLOCKED - DANGEROUS AND HAZARDOUS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
1-HR STAIR ENCLOSURE, <3 STORY | BASEMENT STAIRWAY, SEE EXPOSED LATH AND WALL FRAMING, LACK OF FIRE SEPARATION. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIRWAY LEADING TO BASEMENT, RISER HEIGHTS ARE INCONSISTENT - RANGE BETWEEN 9 INCHES AND 12 INCHES - AND TREADS UNDER 9 INCHES IN WIDTH - DANGEROUS AND HAZARDOUS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PLANS & PERMITS REQUIRED | BASEMENT STAIRWAY WAS RECENTLY RECONSTRUCTED, POOR WORKMANSHIP, NO PLANS OR PERMITS ON FILE. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
CLASS B DOOR IN STAIRWELL | BASEMENT AND REAR DOORS MISSING CLASS B LABELS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PERFRM STRUCT ENGINEER REPAIRS | PROVIDE STRUCTURAL ENGINEER'S REPORT FOR FIRST FLOOR, FLOOR STRUCTURE, INCLUDING MAIN SUPPORT BEAMS AND COLUMNS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPAIR FLOOR | FRONT QUARTER OF FLOOR SYSTEM MISSING CENTER SUPPORT BEAM, 6 FT. SECTION. FRONT HALF OF FLOOR SYSTEM, JOISTS SISTERED ONTO ROTTED AND TERMITE DAMAGED MATERIAL, REAR PORTION OF FLOOR SYSTEM WITH DETERIORATED AND PARTLY MISSING JOISTS. MAIN BEAM IN REAR OF BASEMENT MISSING SUPPORT COLUMNS. BEAM SEVERELY SAGGING. MOST JOISTS FLOATING. CENTER SECTION OF FLOOR SYSTEM, SOUTH ELEVATION UNDER (MENS BATHROOM) BEING SUPPORTED WITH TWO, 2X8 LUMBER NAILED TOGETHER (AS HEADER) AND TWO 6X6 COLUMNS RESTING ON SLAB. THIS IS SUPPORTING THE JOISTS THAT HAVE ROTTED AWAY FROM EXTERIOR WALL POCKETS - DANGEROUS AND HAZARDOUS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
FIRE EXTNGSHR REQ, RESDNTL | NO VISIBLE FIRE EXTINGUISHERS PRESENT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION EXTERIOR WALL, SEVERE STEP FRACTURE FROM TOP OF SECOND FLOOR WINDOW THROUGH PARAPET WALL. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
SUBMIT 2 COPY STRUCTURAL RPT | PARAPET WALL WITH STEP FRACTURE, WALL BOWING ABOVE SECOND FLOOR WINDOWS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
CHIMNEY | SECOND FLOOR WINDOW LINTELS SEVERELY FLAKING AND SAGGING, CAUSING STEP FRACTURES. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE GUARD RAIL 42 IN HIGH | SECOND FLOOR APARTMENT REAR EGRESS LEADS ONTO ROOF TOP, PERIMETER GUARD RAILS UNDERSIZED - 34 INCHES IN HEIGHT ONLY, MISSING TOP RAIL. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INSTALL FIXTURES PROPER MATERL | FIRST FLOOR, MENS BATHROOM - LAVATORY MISSING GRID STRAINER. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OPEN | FIRST FLOOR, MENS BATHROOM - LAVATORY MISSING TEMPERING VALVE FOR HOT WATER. INSTALL AN APPROVED 101 ANTI-SCALD DEVICE. (18-29-607.1.1) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPLACE DEFECTIVE WATER PIPING | FIRST FLOOR, MENS BATHROOM - INSTALL AIR CHAMBERS ON ALL PLUMBING FIXTURES. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROPER SIXE SOIL/WASTE PIPE | FIRST FLOOR, MENS BATHROOM - URINAL, REMOVE THE 2" P.V.C. PIPE USED FOR THE FIXTURE WASTE AND REPIPE WITH AN APPROVED MATERIAL. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROPER MATRL WATER SUPPLY PIPE | FIRST FLOOR, MENS BATHROOM - REMOVE ALL FLEX WATER SUPPLIES TO ALL FIXTURES AND REPIPE WITH COPPER SUPPLIES. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPLACE DEFECTIVE WASTE PIPING | FIRST FLOOR, WOMEN'S BATHROOM - LAVATORY, REMOVE RUBBER HOSE USED ON THE WASTE LINE AND REPIPE WITH APPROVED MATERIAL. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE OPEN FRONT TOILET SEAT | FIRST FLOOR, WOMEN'S BATHROOM - TOILET, INSTALL AN OPEN FRONT SEAT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OPEN | FIRST FLOOR, WOMEN'S BATHROOM - INSTALL A FLOOR DRAIN IN BATHROOM. (18-29-412.4.3) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INSTALL INDIRECT SANT. WASTE | FIRST FLOOR BAR - BAR SINK, INSTALL A OPEN SITE WASTE AS CLOSE AS POSSIBLE TO THE FIXTURE FOR THE SINK WASTE. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INDIRECT CONN.FOR WATER SUPPLY | BASEMENT - HOSE BIBB REQUIRES A BACKFLOW PREVENTER. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REPAIR DEFECTIVE FITTINGS | BASEMENT - REMOVE ALL P.V.C. PIPE AND FITTINGS USED FOR SOIL, WASTE, AND VENT PIPING AND INSTALL APPROVED MATERIALS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | BASEMENT - REMOVE ALL FIXTURES, SOIL, WASTE, VENT AND WATER PIPE INSTALLED WITHOUT A PERMIT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PRV CLEANOUT AT BASE OF STACK | BASEMENT - INSTALL FULL SIZE CLEAN OUTS AT THE BASE OF ALL SOIL STACKS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE ADEQUATE SUPPORT | INSTALL HANGERS ON THE WATER, WASTE, VENT, SOIL AND GAS PIPE INSTALLED AT THE CEILING ELEVATION IN BASEMENT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE ADEQUATE SUPPORT | NO SUPPORT FOR THE 4" SOIL STACK ABOVE THE BASEMENT CEILING AT THE 90 DEGREE OFFSET TO THE BASE. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PRV DISCHARGE PIPE FROM PRV | BASEMENT - WATER HEATERS, RELIEF VALVE DISCHARGE PIPE IS TOO SHORT, REPIPE WITHIN SIX INCHES OF THE FLOOR. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OPEN | BASEMENT - RELIEF VALVE DISCHARGE PIPE IS THE WRONG MATERIAL, USE APPROVED MATERIAL. (18-29-504.7.1) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
SEAL DRAIN OPENING UNUSD FIXTR | BACK OF BASEMENT UNDER WOMEN'S BATHROOM, PROPERLY PLUG UNUSED OPENING ON THE BASE STACK FITTING, REMOVE CEMENT AND INSTALL A PLUG. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REMOVE STAGNANT WATER BSMT | RAW SEWAGE ON THE BASEMENT FLOOR. SOIL LINE RUNNING ALONG THE NORTH WALL HAS A RUBBER COUPLING THAT IS LEAKING, REMOVE COUPLING AND PROPERLY REPIPE 4" SOIL LINE. CLEAN FLOOR FROM SEWAGE. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
ENGAG LIC & BOND PLMBNG CNTRC | HIRE A LICENSED PLUMBING CONTRACTOR. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
OBTN PERMIT FOR PLUMBING WORK | PULL A PLUMBING PERMIT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
DEFECTIVE METER EQUIPMENT | REPLACE DEFECTIVE AND VANDALIZED POWER SERVICE WITH EXPOSED WIRING AT PANELS AND IMPROPER TERMINATIONS AT PANELS IN BASEMENT - DANGEROUS AND HAZARDOUS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INSTALL COVERS | INSTALL COVERS TO ALL OPEN JUNCTION BOXES IN BASEMENT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
EXPOSED WIRING | REMOVE EXPOSED WIRING AT LIGHT FIXTURE OUTSIDE OF REAR EXIT ON EXTERIOR AND ABOVE POOL TABLE IN CEILING. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
UNAPPROVED CORDS | REMOVE ALL EXTENSION CORDS IN BASEMENT AND 1ST FLOOR. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
(18-27-210.8) INSTALL GFCI'S TO WET LOCATIONS AT REAR EXTERIOR OF BUILDING. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View | |
SEE INSPECTOR COMMENTS | (18-27-210.5) INSTALL PROPER COLOR CODE TO UNGROUNDED CONDUCTORS IN PANEL. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
DEFECTIVE FIXTURES | REPLACE ALL DEFECTIVE LIGHT FIXTURES ON INTERIOR OF BASEMENT AND 1ST FLOOR AND ON EXTERIOR . | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INSTALL ILLUMINATION | INSTALL ILLUMINATION TO ALL EXTERIOR ENTRY DOORS. INSTALL ADDITIONAL ILLUMINATION TO BASEMENT AT ALL AREAS INCLUDING EXIT DOOR ON EXTERIOR. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
SOIL/WASTE,VENT PIPE MATRL | FIRST FLOOR BAR - INSTALL PROPER FITTINGS FOR THE WASTE PIPING FOR THE THREE COMPARTMENT BAR SINK. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE ADEQUATE SUPPORT | PROPERLY SUPPORT THE WATER SERVICE AND METER AT THE WEST SIDE OF BASEMENT. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
INSTALL FIXTURES PROPER MATERL | FIRST FLOOR, WOMEN'S BATHROOM - LAVATORY, INSTALL A GRID STRAINER ON DRAIN. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
REMOVE | PROVIDE EXITING DIAGRAM. (4-156-380, 13-84-400) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
PROVIDE | BASEMENT CEILING MISSING REQUIRED FIRE SEPARATION - DANGEROUS AND HAZARDOUS. (13-60-330B) | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
SUBMIT PLANS FOR PLUMBING PRMT | PROVIDE PLANS TO THE DEPARTMENT OF BUILDINGS AND SEWER DEPARTMENT FOR REVIEW AND PERMIT APPLICATION. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |
(13-12-360) PROVIDE PERMIT TO CORRECT VIOLATIONS. | 4957 S ASHLAND AVE | COMPLAINT | CLOSED | View |