Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | PROVIDE ELECTRICAL PERMIT IN ORDER TO CORRECT ALL ELECTRICAL VIOLATIONS (14A-4-404.6) | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
REPAIR GUTTER & DOWNSPOUT | GUTTERS AT NORTH ELEVATION RUSTED AND DETERIORATED 14X-3-303.7 | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PLANS & PERMITS REQ - CONTRCTR | THIS COMMERCIAL STOREFRONT IS OPERATING 2 BUSINESS THAT REQUIRE A LICENSE 1. ROADSIDE ASSISTANCE TOWING 2. MASSAGE SPA PLANS AND PERMITS ARE REQUIRED AS PART OF APPLICATION PROCESS TO ACQUIRE THESE LICENSES 14A-4-401.1 | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN PLUMBING PERMIT FOR PLUMBING WORK TO BE PERFORMED | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
LICENSED BONDED PLMBG CONTRCTR | EMPLOYED LICENSED AND BONDED PLUMBING CONTRACTOR FOR PLUMBING WORK TO BE PERFORMED TO ADDRESS PLUMBING VIOLATIONS | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PRV BALLCOCK,VB,OR AIR GAP | NO VACUUM BREAKER AT ELEVATED HOT WATER HEATER D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PRV BALLCOCK,VB,OR AIR GAP | NO VACUUM BREAKER AT HOSE BIBB AT EXTERIOR NORTH ELEVATION D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PRV FLOOR DRAIN WITH METAL STR | NO FLOOR DRAIN IN COMMERCIAL BATHROOM | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PROVIDE | NO MIXING VALVE AT BATHROOM LAVATORY 18.29.607.1.1 D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
DEFECTIVE SERVICE | REPLACE DEFECTIVE 60 AMP SERVICE SERVICE WHICH IS DETERIORATED AND NOT CURRENTLY UP TO CODE AND IN VIOLATION DUE TO ALTERATIONS WHICH WERE MADE WITHOUT PERMITS OR INSPECTIONS D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PROPER SIZE GRD ELECTRODE COND | PROVIDE PROPER GROUNDING ELECTRODE CONDUCTOR TO MAIN COLD WATER SERVICE D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
SYSTEM III | INSTALL EM LIGHTING AND EXIT SIGNS THROUGHOUT COMMERCIAL SPACE D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
CORRODED CONDUIT & EQUIP | REPLACE ALL RUSTED AND CORRODED CONDUITS AT THE REAR EXTERIOR OF THE BUILDING D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
UNAPPROVED CORDS | REMOVE ALL EXTENSION CORDS THROUGHOUT THE PROPERTY FEEDING FIXED ELECTRICAL EQUIPMENT D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
INSTALL GFCI'S | PROVIDE GFCI PROTECTION TO ALL REQUIRED RECEPTACLES AND AREAS SPECIFICALLY OUTLET IN THE BATHROOM D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
ADD BRANCH CIRCUITS | ADD ADDITIONAL RECEPTACLES IN ORDER TO ELIMINATE CORDS TO FIXED ELECTRICAL EQUIPMENT THROUGHOUT SPACE D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
WORKING SPACE | PROVIDE PROPER WORKING SPACE IN FRONT OF ALL ELECTRICAL EQUIPMENT SPECIFICALLY FOR ALL SERVICE EQUIPMENT D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
MULTIPLE CONDUCTOR TERM | REWORK SERVICE DISCONNECT WHICH HAS MULTIPLE TERMINATIONS ON LUGS WHICH ARE NOT DESIGNED AS WIRED D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
SOIL/WASTE,VENT PIPE MATRL | PVC IS LOCATED ON T&P VALVE | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
GROUNDING RECEPTACLES | REMOVE RECEPTACLE FROM BATHROOM MIRROR WHICH DOES NOT HAVE A GROUND CONNECTION AND NOT GFCI PROTECTED D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PRV BALLCOCK,VB,OR AIR GAP | NO VACUUM BREAKER AT LAUNDRY TUB IN MECHANICAL ROOM D&H | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PROVIDE OPEN FRONT TOILET SEAT | NO OPEN FRONT TOILET SEAT IN COMMERCIAL BATHROOM | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PROPER MATRL WATER SUPPLY PIPE | UNAPPROVED FLEXIBLE WATER SUPPLY AT ELEVATED HOT WATER TANK | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |
PROVIDE | NO SAFE PAN AT ELEVATED HOT WATER TANK 18.29.504.8 | 5741 N ELSTON AVE | COMPLAINT | PASSED | View |