Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PROVIDE | A REFRIGERANT DETECTOR, FOR COMPRESSOR ROOM ON ROOF. AUDIBLE ALARM(S) SHALL BE PLACED DIRECTLY OUTSIDE OF THE MACHINERY ROOM. VISUAL ALARM(S) SHALL CONSIST OF A FLASHING YELLOW LIGHT PLACED DIRECTLY OVER THE MACHINERY ROOM DOOR(S) WITH A SIGN THAT STATES: "DANGER DO NOT ENTER WHEN LIGHT IS FLASHING". (18-28-1105.5) | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
PROVIDE | A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS- TYPE SHALL PROVIDE ON-ONLY CONTTROL OF THE MACHINERY ROOM VENTILATION FANS. (18-28-1106.10.2) | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
PROVIDE | PROPER IDENTIFICATION OF THE HAND-OPERATED EMERGENCY VALVE(S). | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | CONTACT INSPECTOR STEPHEN MCGANN #971 @ 312-446-5390. | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
PROVIDE | A REFRIGERANT DETECTOR, FOR COMPRESSOR ROOM ON ROOF. AUDIBLE ALARM(S) SHALL BE PLACED DIRECTLY OUTSIDE OF THE MACHINERY ROOM. VISUAL ALARM(S) SHALL CONSIST OF A FLASHING YELLOW LIGHT PLACED DIRECTLY OVER THE MACHINERY ROOM DOOR(S) WITH A SIGN THAT STATES: "DANGER DO NOT ENTER WHEN LIGHT IS FLASHING". (18-28-1105.5) | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
PROVIDE | A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS- TYPE SHALL PROVIDE ON-ONLY CONTTROL OF THE MACHINERY ROOM VENTILATION FANS. (18-28-1106.10.2) | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | CONTACT INSPECTOR STEPHEN MCGANN # 971 @ (312)743-3562 ON TUESDAYS BETWEEN 7-8AM. | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | CONTACT INSPECTOR STEPHEN MCGANN #971 @ 312-446-5390. | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |
PRV HIGH SIDE | RE: FOR TWO COPELAND COMPRESSORS LOCATED ON ROOF, IN SHACK. | 3552 W ARMITAGE AVE | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CONTACT INSPECTOR STEPHEN MCGANN # 971 @ (312)743-3562 ON TUESDAYS BETWEEN 7-8AM. | 3552 W ARMITAGE AVE | PERIODIC | PASSED | View |
PROVIDE | PROPER IDENTIFICATION OF THE HAND-OPERATED EMERGENCY VALVE(S). | 3552 W ARMITAGE AVE | PERIODIC | FAILED | View |