Chicago Building Violations Data: 11 Violations
Violation Inspector Comments Address Category Status View
PROVIDE A REFRIGERANT DETECTOR, FOR COMPRESSOR ROOM ON ROOF. AUDIBLE ALARM(S) SHALL BE PLACED DIRECTLY OUTSIDE OF THE MACHINERY ROOM. VISUAL ALARM(S) SHALL CONSIST OF A FLASHING YELLOW LIGHT PLACED DIRECTLY OVER THE MACHINERY ROOM DOOR(S) WITH A SIGN THAT STATES: "DANGER DO NOT ENTER WHEN LIGHT IS FLASHING". (18-28-1105.5) 3552 W ARMITAGE AVE PERIODIC FAILED View
PROVIDE A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS- TYPE SHALL PROVIDE ON-ONLY CONTTROL OF THE MACHINERY ROOM VENTILATION FANS. (18-28-1106.10.2) 3552 W ARMITAGE AVE PERIODIC FAILED View
PROVIDE PROPER IDENTIFICATION OF THE HAND-OPERATED EMERGENCY VALVE(S). 3552 W ARMITAGE AVE PERIODIC FAILED View
ARRANGE FOR RE-INSPECTION CONTACT INSPECTOR STEPHEN MCGANN #971 @ 312-446-5390. 3552 W ARMITAGE AVE PERIODIC FAILED View
PROVIDE A REFRIGERANT DETECTOR, FOR COMPRESSOR ROOM ON ROOF. AUDIBLE ALARM(S) SHALL BE PLACED DIRECTLY OUTSIDE OF THE MACHINERY ROOM. VISUAL ALARM(S) SHALL CONSIST OF A FLASHING YELLOW LIGHT PLACED DIRECTLY OVER THE MACHINERY ROOM DOOR(S) WITH A SIGN THAT STATES: "DANGER DO NOT ENTER WHEN LIGHT IS FLASHING". (18-28-1105.5) 3552 W ARMITAGE AVE PERIODIC FAILED View
PROVIDE A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS- TYPE SHALL PROVIDE ON-ONLY CONTTROL OF THE MACHINERY ROOM VENTILATION FANS. (18-28-1106.10.2) 3552 W ARMITAGE AVE PERIODIC FAILED View
ARRANGE FOR RE-INSPECTION CONTACT INSPECTOR STEPHEN MCGANN # 971 @ (312)743-3562 ON TUESDAYS BETWEEN 7-8AM. 3552 W ARMITAGE AVE PERIODIC FAILED View
ARRANGE FOR RE-INSPECTION CONTACT INSPECTOR STEPHEN MCGANN #971 @ 312-446-5390. 3552 W ARMITAGE AVE PERIODIC FAILED View
PRV HIGH SIDE RE: FOR TWO COPELAND COMPRESSORS LOCATED ON ROOF, IN SHACK. 3552 W ARMITAGE AVE PERIODIC PASSED View
ARRANGE FOR RE-INSPECTION CONTACT INSPECTOR STEPHEN MCGANN # 971 @ (312)743-3562 ON TUESDAYS BETWEEN 7-8AM. 3552 W ARMITAGE AVE PERIODIC PASSED View
PROVIDE PROPER IDENTIFICATION OF THE HAND-OPERATED EMERGENCY VALVE(S). 3552 W ARMITAGE AVE PERIODIC FAILED View