Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ILLUMINATE PUBLIC STAIR/HALL | EMERGENCY LIGHT DEFECTIVE. | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | NOT ILLUMINATED. | 514 E 50TH PL | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPOPNSE, UNVERIIFED DETECTORS AND CONDITIONS. | 514 E 50TH PL | COMPLAINT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 514 E 50TH PL | PERIODIC | PASSED | View | |
STOP/REMOVE NUISANCE | EAST ELEVATION AT EXIT DOORS - MULTIPLE STOLEN SHOPPING CARTS. | 514 E 50TH PL | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY ONE TEST ON NO. 1 PASSENGER | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR DOOR RESTRICTOR ON NO. 1 PASSENGER | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR AND PROGRAM EMERGENCY PHONES TO A 24 HR SERVICE | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PEFORM CATEGORY ONE TEST ON NO.2 FREIGHT ELEVATOR | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR THE KEY SWITCH IN CAB (BASEMENT ACCESS), TO PROPERLY RESPOND, WHEN FIRE SERVICE PHASE 2 IS ACTIVATED. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR | SOUTH ELEVATION / FRONT ENTRY DOOR AND VESTIBULE DOOR - BOARDED WITH GLASS. FRONT ENTRY DOOR DOES NOT LATCH. | 514 E 50TH PL | COMPLAINT | FAILED | View |
REPAIR EXTERIOR STAIR | SOUTH ELEVATION / FRONT ENTRY STAIRS - SPALLING MASONRY. STEEL HANDRAIL - LOOSE AND LEANING. | 514 E 50TH PL | COMPLAINT | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | EMERGENCY LIGHT DEFECTIVE. | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN EXIT SIGN ILLUMINATED | NOT ILLUMINATED. | 514 E 50TH PL | PERIODIC | PASSED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY. UNVERIFIED DETECTORS AND CONDITIONS. | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REMOVE THE STANDING WATER IN PIT & MACHINE ROOM | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CAT1 TEST PROVIDE DOCUMENTATION | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | NORTHEAST INTERIOR STAIRWAY,BRICKS WITH SPALLING MORTAR JOINTS. | 514 E 50TH PL | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | SOUTHWEST INTERIOR STAIRWAY AT 2ND FLOOR,EMERGENCY LIGHTING LOW BATTERY. | 514 E 50TH PL | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CALL FOR RE INSPECTION AFTER STANDING WATER IS REMOVED | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR DOOR HARDWARE | 1ST, 2ND AND 4TH FLOOR STAIRWELL DOORS - DEFECTIVE LOCKS AND SELF-CLOSERS.APT. # 208 - HALLWAY AND BEDROOM CLOSET DOORS - OFF HINGES. | 514 E 50TH PL | COMPLAINT | CLOSED | View |
STAIR: SELF-CLOSE 1-3/4" DOOR | 1ST AND 3RD FLOOR STAIRWELL DOORS - MISSING.4TH AND 2ND FLOOR GARBAGE CHUTE DOORS - MISSING | 514 E 50TH PL | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | APARTMENT # 401 - BATHROOM WALL BEHIND TOILET - PLASTER HAS A HOLE.APT. # 105, SHOWER WALL - HAS LARGE HOLES. | 514 E 50TH PL | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | 3RD FLOOR CORRIDOR, EMERGENCCY LIGHT FIXTURE - FAILED TEST. | 514 E 50TH PL | COMPLAINT | FAILED | View |
INT WALL/CEILING PEELING PAINT | 3RD FLOOR HALLWAY CEILING AND 2ND FLOOR STAIRWELL WALL - PEELING PAINT. | 514 E 50TH PL | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | APARTMENT # 401 - BATHROOM WALL BEHIND TOILET - PLASTER HAS A HOLE.APT. # 105, SHOWER WALL - HAS LARGE HOLES. | 514 E 50TH PL | COMPLAINT | CLOSED | View |
INT WALL/CEILING PEELING PAINT | 3RD FLOOR HALLWAY CEILING AND 2ND FLOOR STAIRWELL WALL - PEELING PAINT. | 514 E 50TH PL | COMPLAINT | CLOSED | View |
DEFECTIVE FIXTURES | 3RD FLOOR CORRIDOR, EMERGENCCY LIGHT FIXTURE - FAILED TEST. | 514 E 50TH PL | COMPLAINT | CLOSED | View |
REPAIR/REPLACE SMOKE DETECTORS | APT. 105, SMOKE DETECTOR - HANGING LOOSE. | 514 E 50TH PL | COMPLAINT | CLOSED | View |
STAIR: SELF-CLOSE 1-3/4" DOOR | 1ST AND 3RD FLOOR STAIRWELL DOORS - MISSING.4TH AND 2ND FLOOR GARBAGE CHUTE DOORS - MISSING | 514 E 50TH PL | COMPLAINT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ENABLE DISABLE CAR DOOR RESTRICTOR | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATAGORY 1 SAFETY TEST | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | UPDATE FIRE EXTINGUISHER | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERTY PROGRAM EMERGENCY PHONE TO A 24HR ANSWERING SOURCE. | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CAR POSITION INDICATOR NOT WORKING PROPERLY. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | APT. 105, SMOKE DETECTOR - HANGING LOOSE. | 514 E 50TH PL | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | 1ST, 2ND AND 4TH FLOOR STAIRWELL DOORS - DEFECTIVE LOCKS AND SELF-CLOSERS.APT. # 208 - HALLWAY AND BEDROOM CLOSET DOORS - OFF HINGES. | 514 E 50TH PL | COMPLAINT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 514 E 50TH PL | PERIODIC | PASSED | View | |
NO ENTRY | 514 E 50TH PL | PERIODIC | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | PEFORM CATEGORY ONE TEST ON PASSENGER ELEVATOR | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN AND DRY ELEVATOR PIT | 514 E 50TH PL | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BUILDING - NOT REGISTERED YEARS 1990 THRU 2017. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR COPING | SOUTH, WEST AND EAST COPING STONES - WASHED OUT MORTAR. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION 2ND FLOOR - STEP CRACK. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR LINTELS | EAST, NORTH AND WEST WINDOW LINTELS - RUSTED AND DEFLECTING. MASONRY PERMIT REQUIRED TO REPLACE LINTELS. | 514 E 50TH PL | PERIODIC | FAILED | View |
WINDOW OPEN EASILY, STAY OPEN | APT. 406, LIVINGROOM WINDOW KEPT CLOSED WITH SCREWS. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | APARMENT 304, SMOKE DETECTOR HANGING LOOSE. | 514 E 50TH PL | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | SOUTHEAST STAIRWELL - MISSING SMOKE DETECTOR. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR, RESET | SOUTHEAST STAIRWELL DOOR - DO NOT CLOSE PROPERLY. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 2ND FLOOR HALLWAY CEILING - DRYWALL HAS A LARGE HOLE. | 514 E 50TH PL | PERIODIC | FAILED | View |
DEFECTIVE FIXTURES | 2ND FLOOR HALLWAY LIGHT FIXTURES - OUT OF SERVICE.SEVERAL EMERGENCY LIGHT ARE OUT OF SERVICE THRU OUT THE BUILSING. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR FLOOR | APARTMENT 406 - LOOSE ALUMINUM FLOOR TILE HOLDER. | 514 E 50TH PL | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF THE BUILDING - NO RESPONSE, UNVERIFIED DETECTORS AND CONDITIONS. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR COPING | SOUTH, WEST AND EAST COPING STONES - WASHED OUT MORTAR. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION 2ND FLOOR - STEP CRACK. | 514 E 50TH PL | PERIODIC | PASSED | View |
WINDOW OPEN EASILY, STAY OPEN | APT. 406, LIVINGROOM WINDOW KEPT CLOSED WITH SCREWS. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR/REPLACE SMOKE DETECTORS | APARMENT 304, SMOKE DETECTOR HANGING LOOSE. | 514 E 50TH PL | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | SOUTHEAST STAIRWELL - MISSING SMOKE DETECTOR. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR, RESET | SOUTHEAST STAIRWELL DOOR - DO NOT CLOSE PROPERLY. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR INTERIOR WALLS/CEILING | 2ND FLOOR HALLWAY CEILING - DRYWALL HAS A LARGE HOLE. | 514 E 50TH PL | PERIODIC | PASSED | View |
DEFECTIVE FIXTURES | 2ND FLOOR HALLWAY LIGHT FIXTURES - OUT OF SERVICE.SEVERAL EMERGENCY LIGHT ARE OUT OF SERVICE THRU OUT THE BUILSING. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR FLOOR | APARTMENT 406 - LOOSE ALUMINUM FLOOR TILE HOLDER. | 514 E 50TH PL | PERIODIC | PASSED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF THE BUILDING - NO RESPONSE, UNVERIFIED DETECTORS AND CONDITIONS. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR | EAST ELEVAION / EXIT DOOR AT GRADE - BROKEN CLOSER. | 514 E 50TH PL | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | ALL STAIRWAYS - BROKEN CLOSERS, MISSING HANDLES AND MISSING DOORS THROUGHOUT. | 514 E 50TH PL | PERIODIC | FAILED | View |
ILLUMINATE EXIT AREAS | NORTHEAST STAIRWAY / EMERGENY LIGHT - OUT OF SERVICE WITH LOOSE COVER. | 514 E 50TH PL | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | TRASH CHUTE DOORS THROUGHOUT - DO NOT LATCH. TRASH CLOSET DOORS - MISSING OR HELD OPEN AT TIME OF INSPECTION. | 514 E 50TH PL | PERIODIC | FAILED | View |
STOP SMOKE, NOXIOUS ODORS | 3RD FLOOR HALLWAY - FOUL ODORS EMINATING FROM 1 OR MORE APARTMENTS AT TIME OF INSPECTION. | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | EXIT SIGNS AT 1ST FLOOR - NOT ILLUMINATED AT TIME OF INSPECTION. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR, RESET | APT 103 / UNIT DOOR - DAMAGED AND LAYING IN OPENING WITH PLYWOOD AND TAPE COVERING DOORWAY. | 514 E 50TH PL | PERIODIC | FAILED | View |
SCREEN OUTER DOORS, WINDOWS | BUILDING / SCREENS - MISSING AT VARIOUS LOCATIONS. | 514 E 50TH PL | PERIODIC | FAILED | View |
HOLDOPEN DEVICE, STAIR 3+ FLRS | STAIWAY DOORS - HELD OPEN WITH WEDGES. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | EAST ELEVATION / WINDOWS - BROKEN. | 514 E 50TH PL | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | NORTHEAST STAIRWAY - DEAD BIRD ON 4TH FLOOR STAIRS. 1ST FLOOR HALLWAY - STORING SHOPPING CARTS. CONFERENCE ROOM - STORING GAS POWERED SNOW BLOWERS. | 514 E 50TH PL | PERIODIC | FAILED | View |
INSECTS | BED BUGS IN UNIT 204 | 514 E 50TH PL | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY. UNVERIFIED DETECTORS AND CONDITIONS. | 514 E 50TH PL | PERIODIC | FAILED | View |
INSECTS | BED BUGS IN UNIT 204 | 514 E 50TH PL | COMPLAINT | FAILED | View |
NO ENTRY | 514 E 50TH PL | PERIODIC | PASSED | View | |
REPAIR DOOR HARDWARE | NORTH STAIRWELL 3RD FLOOR - DEFECTIVE SELF-CLOSER. | 514 E 50TH PL | PERIODIC | FAILED | View |
REPAIR DOOR HARDWARE | NORTH STAIRWELL 3RD FLOOR - DEFECTIVE SELF-CLOSER. | 514 E 50TH PL | PERIODIC | PASSED | View |
REPAIR LINTELS | EAST, NORTH AND WEST WINDOW LINTELS - RUSTED AND DEFLECTING. MASONRY PERMIT REQUIRED TO REPLACE LINTELS. | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR THE EMERGENCY PHONE IN ELEVATOR | 514 E 50TH PL | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM THE FIRE SERVICE UPGRADE FOR PHASE 2 OPERATION-PER CITY OF CHICAGO FIRE SERVICE MANDATE | 514 E 50TH PL | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERLY SERVICE AND MAINTAIN THIS ELEVATOR. TENANTS ARE DISABLED | 514 E 50TH PL | PERIODIC | FAILED | View |