Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR LINTELS | EAST ELEVATION,GRADE THRU 3RD FLOOR,RUSTY LINTELS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | SOUTH ELEVATION,2-REAR PORCHES,6 BY 6 COLUMN HALF-LAP JOINTS WITH 2-3/8INCH BOLTS ONLY,RAILS ARE TOE NAILED TO SUPPORTS,PULLING APART,END SUPPORTS AT 3RD FLOOR ARE MASONRY NAILED TO WALL,DECKING BOARDS WITH NAILS POPPING,PERMIT REQUIRED FOR REPAIRS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BUILDING NOT REGISTERED FOR 2010-2011. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 5536 N. / FRONT INTEROR STAIRWELL A, 3RD FLOOR - JUNK AND STORAGE ITEMS AT TOP OF STAIRWELL - OBSTRUCTION AND FIRE HAZARD. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
CHIMNEY | WEST ELEVATION, CHIMNEY - WASHED OUT MORTAR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR LINTELS | NORTH AND EAST ELEVATIONS, LINTELS - RUSTED. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
CHIMNEY | WEST ELEVATION, CHIMNEY - WASHED OUT MORTAR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 5536 N. / FRONT ENTRY VESTIBULE - WATER DAMAGE TO CEILING. 3RD FLOOR APT. A3 - WATER DAMAGE AND MILDEW ON BATHROOM CEILING. 5536 N. / FRONT INTEROR STAIRWELL B/C, 3RD FLOOR - WATER DAMAGE TO CEILING. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 5536 N. / FRONT INTEROR STAIRWELLS A AND B/C - FIRE EXTINGUISHER RECHARGE TAG EXPIRED 2016. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | 3RD FLOOR APT. A3 - MISSING SMOKE DETECTOR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
1HR SEP-D.U. AND REST OF BLDG | BASEMENT LAUNDRY ROOM - HOLES IN CEILING - MISSING PROPER FIRE SEPARATION TO DWELLING UNIT ABOVE. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR LINTELS | NORTH AND EAST ELEVATIONS, LINTELS - RUSTED. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 5536 N. / FRONT INTEROR STAIRWELLS A AND B/C - FIRE EXTINGUISHER RECHARGE TAG EXPIRED 2016. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
PARAPET | SOUTH ELEVATION, PARAPET - WASHED OUT MORTAR. EAST ELEVATION, PARAPET - CRACKED STONEWORK AND WASHED OUT MORTAR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | SOUTH AND NORTH ELEVATIONS ,FRONT AND REAR EGRESS WOOD STAIRS - LOOSE , BUCKLED ,SPALLED TREADS AND DECK /LANDING BOARDS AT VARIOUS LOCATIONS THRU-OUT. PROTUDING NAILS. FASTENED BY ONLY NAILS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | SOUTH ELEVATION, WEST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. - COLUMN ON 4 INCH CONCRETE BASES, FOUNDATIONS UNKNOWN. METAL BASE CONNECTION FROM CONCRETE TO WOOD COLUMN SEVERELY RUSTED. EAST COLUMN SEVERELY CRACKED IN CORNER OF COLUMN FROM 1ST FLOOR TO 2ND FLOOR. 3RD FLOOR DECK BOARDS ROTTEN AND LOOSE. DECK JOIST HANGERS RUSTED. RAILINGS CRACKED AND SPLIT WITH LOOSE PICKETS. SOUTH ELEVATION, EAST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. METAL BASE CONNECTION FROM CONCRETE STOOP TO WOOD COLUMN SEVERELY RUSTED. 3RD FLOOR TREADS ROTTING AND SPLITTING. TOP OF RAILINGS ROTTING. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR STOOP | SOUTH ELEVATION, CONCRETE STOOP AT EAST PORCH SYSTEM, SOUTH SIDE OF STOOP AT PROPERTY LINE - LARGE HOLES IN CONCRETE - RAT HARBORAGE. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 5536 N. / FRONT INTEROR STAIRWELL A, 3RD FLOOR - JUNK AND STORAGE ITEMS AT TOP OF STAIRWELL - OBSTRUCTION AND FIRE HAZARD. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
WINDOW REPAIR FOR AIR SEEPAGE | 2ND FLOOR FLOOR APT. B2 - WINDOWS ARE DRAFTY AND DO NOT PROPERLY CLOSE SHUT. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
PARAPET | SOUTH ELEVATION, PARAPET - WASHED OUT MORTAR. EAST ELEVATION, PARAPET - CRACKED STONEWORK AND WASHED OUT MORTAR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | SOUTH ELEVATION, WEST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. - COLUMN ON 4 INCH CONCRETE BASES, FOUNDATIONS UNKNOWN. METAL BASE CONNECTION FROM CONCRETE TO WOOD COLUMN SEVERELY RUSTED. EAST COLUMN SEVERELY CRACKED IN CORNER OF COLUMN FROM 1ST FLOOR TO 2ND FLOOR. 3RD FLOOR DECK BOARDS ROTTEN AND LOOSE. DECK JOIST HANGERS RUSTED. RAILINGS CRACKED AND SPLIT WITH LOOSE PICKETS. SOUTH ELEVATION, EAST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. METAL BASE CONNECTION FROM CONCRETE STOOP TO WOOD COLUMN SEVERELY RUSTED. 3RD FLOOR TREADS ROTTING AND SPLITTING. TOP OF RAILINGS ROTTING. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | SOUTH ELEVATION - CONCRETE LANDING STEPS AT GRADE - SPALLED ,LOOSE AND BROKEN TREADS | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR STOOP | SOUTH ELEVATION, CONCRETE STOOP AT EAST PORCH SYSTEM, SOUTH SIDE OF STOOP AT PROPERTY LINE - LARGE HOLES IN CONCRETE - RAT HARBORAGE. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR STOOP | SOUTH ELEVATION, CONCRETE STOOP AT EAST PORCH SYSTEM, SOUTH SIDE OF STOOP AT PROPERTY LINE - LARGE HOLES IN CONCRETE - RAT HARBORAGE. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
PARAPET | SOUTH ELEVATION, PARAPET - WASHED OUT MORTAR. EAST ELEVATION, PARAPET - CRACKED STONEWORK AND WASHED OUT MORTAR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | NORTH ELEVATION, WINDOW SILLS - OPEN MORTAR JOINTS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 5536 N. / FRONT ENTRY VESTIBULE - WATER DAMAGE TO CEILING. 3RD FLOOR APT. A3 - WATER DAMAGE AND MILDEW ON BATHROOM CEILING. 5536 N. / FRONT INTEROR STAIRWELL B/C, 3RD FLOOR - WATER DAMAGE TO CEILING. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
WINDOW REPAIR FOR AIR SEEPAGE | 2ND FLOOR FLOOR APT. B2 - WINDOWS ARE DRAFTY AND DO NOT PROPERLY CLOSE SHUT. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
ARRANGE FOR REINSPECTION REGAR | INTERIOR OF BUILDING , NO RESPONSE . UNABLE TO VERIFY SMOKE OR CARBON MONOXIDE ALARMS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | NORTH ELEVATION, WINDOW SILLS - OPEN MORTAR JOINTS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | 3RD FLOOR APT. A3 - MISSING SMOKE DETECTOR. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
1HR SEP-D.U. AND REST OF BLDG | BASEMENT LAUNDRY ROOM - HOLES IN CEILING - MISSING PROPER FIRE SEPARATION TO DWELLING UNIT ABOVE. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 5536 N. / FRONT INTEROR STAIRWELL A, 3RD FLOOR - JUNK AND STORAGE ITEMS AT TOP OF STAIRWELL - OBSTRUCTION AND FIRE HAZARD. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | SOUTH ELEVATION, WEST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. - COLUMN ON 4 INCH CONCRETE BASES, FOUNDATIONS UNKNOWN. METAL BASE CONNECTION FROM CONCRETE TO WOOD COLUMN SEVERELY RUSTED. EAST COLUMN SEVERELY CRACKED IN CORNER OF COLUMN FROM 1ST FLOOR TO 2ND FLOOR. 3RD FLOOR DECK BOARDS ROTTEN AND LOOSE. DECK JOIST HANGERS RUSTED. RAILINGS CRACKED AND SPLIT WITH LOOSE PICKETS. SOUTH ELEVATION, EAST REAR EXTERIOR 3 STORY OPEN WOOD PORCH SYSTEM. METAL BASE CONNECTION FROM CONCRETE STOOP TO WOOD COLUMN SEVERELY RUSTED. 3RD FLOOR TREADS ROTTING AND SPLITTING. TOP OF RAILINGS ROTTING. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | BUILDING NO ENTRY TO UNITS TO CHECK OCCUPANCY,DETECTORS AND 5536 UNIT-3RD FLOOR TO CHECK COMPLAINT OF RODENTS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | NORTH ELEVATION, WINDOW SILLS - OPEN MORTAR JOINTS. | 5536 N CAMPBELL AVE | PERIODIC | FAILED | View |