Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR WINDOW SILLS | WEST ELEVATION - WINDOW SILLS OPEN MORTAR JOINTS | 2401 S TROY ST | PERIODIC | PASSED | View |
INSTALL DOOR VIEWING DEVICE | FRONT 2ND FLOOR MISSING VIEWING DEVICECOACH HOUSE 2ND FLOOR NO VIEWING DEVICE. | 2401 S TROY ST | PERIODIC | PASSED | View |
RELOCATE SMOKE DETECTOR | 3RD FLOOR APT 2 SMOKE DETECTOR 2' TO CEILING.REAR COACH HOUSE 2ND FLOOR SMOKE DETECTOR 2' TO CEILING. | 2401 S TROY ST | PERIODIC | PASSED | View |
INSTALL DEAD BOLT LOCK | FRONT EXTERIOR DOOR MISSING DEAD BOLT. | 2401 S TROY ST | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | 3RD FLOOR HALLWAY AND REAR PORCH BOXES BLOCKING EGRESS. | 2401 S TROY ST | PERIODIC | PASSED | View |
REPAIR EXTERIOR STAIR | COACH HOUSE FRONT STAIRS GRADE TO 2ND FLOOR .4X4 COLUMN ERECTED ON BLOCKS AND SERVICE WALK.JOIST NAILED TO HEADERS.FRONT STAIRS SOUTH CEMENT AND IRON TREADS CRACKED AND SHIFTING OUT.FRONT NORTH STAIRS GRADE TO 1ST FLOORCEMENT STAIRS CRACKED PERMIT REQUIRED FOR REPAIRS FRONT COACH HOUSE STAIRS AND FRONT STAIRSFRONT STAIRS SOUTH CEMENT AND IRON TREADS CRACKED AND SHIFTING OUT | 2401 S TROY ST | PERIODIC | PASSED | View |
REPAIR EXTERIOR WALL | REAR 3RD FLOOR SIDING MISSING AND LOOSE | 2401 S TROY ST | PERIODIC | PASSED | View |
STOP/REMOVE NUISANCE | NORTH AND WEST ELEVATION -GRAFFITI | 2401 S TROY ST | PERIODIC | PASSED | View |
PROTECT SIDEWALK DURING CONST | NORTH ELEVATION - CANOPY REQUIRED FOR REPAIRS TO CHIMNEY | 2401 S TROY ST | PERIODIC | PASSED | View |
CARB MONOX DETECT IN RESID | 1ST FLOOR ... NO CARBON MONOXIDE DETECTOR. | 2401 S TROY ST | PERIODIC | PASSED | View |
CHIMNEY CAPPING | COACH HOUSE CHIMNEY CAP OPEN MORTAR JOINT. | 2401 S TROY ST | PERIODIC | PASSED | View |
REPAIR PORCH SYSTEM | REAR PORCH GRADE TO 3RD FLOOR FIRE CUTS NO ANGLE. COLUMNS 1/2 LAPS 12' WITH 4 BOLTS.JOIST HANGERS NAILED TO HEADERS.1ST FLOOR DECK BOARD LOOSEGUARD RAILS AND STRINGERS NAILED TO COLUMNS,HEADERS AND WALL.GUARD RAILS 36" HIGH.1ST FL PICKETS BROKENPERMIT REQUIRED FOR REPAIR TO PORCH. | 2401 S TROY ST | PERIODIC | PASSED | View |
CHIMNEY | SOUTH CHIMNEY WASHED OUT MORTAR.NORTH ELEVATION - CHIMNEY LEANING OUT 6" OUT OF PLUMB MASON PERMINT REQUIRED FOR ALL MASONARY WORK TO BE DONE | 2401 S TROY ST | PERIODIC | PASSED | View |
FIRE EXTNGSHR RECHARGE & TAG | FRONT 1ST FLOOR STORE FIRE EXTINGUISHER TAGED 2014 | 2401 S TROY ST | PERIODIC | PASSED | View |
REPAIR FLOOR | FRONT INTERIOR STAIRS 2ND FLOOR TILES LOOSE AND MISSING. | 2401 S TROY ST | PERIODIC | PASSED | View |
PROVIDE GUARD RAIL 42 IN HIGH | REAR STORY PORCH AT GRADE MISSING GUARD RAILS. | 2401 S TROY ST | PERIODIC | PASSED | View |
REPAIR/REPLACE SMOKE DETECTORS | REAR COACH HOUSE 2ND FLOOR SOMOKE DETECTOR NOT WORKING.REAR COACH HOUSE BASEMENT SMOKE DETECTOR NOT WORKING.FRONT 1ST FLOOR REAR APT SMOKE DETECOR NOT WORKING AT TIME OF INSPECTION.3RD FLOOR SMOKE DETECTOR NOT WORKING. | 2401 S TROY ST | PERIODIC | PASSED | View |
ARRANGE PREMISE INSPECTION | UNABLE TO GAIN ENTRY TO VERIFY OCCUPANCY,DETECTORS AND OVERALL CONDITION FOR 2012 ANNUAL INSPECTION. | 2401 S TROY ST | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | FRONT BUILDING WEST ELEVATION 1ST FLOOR GANG GRAFFITI AND REAR BUILDING AND REAR BUILDING NORTH ELEVATION AT GRADE GANG GRAFFITI. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | EAST ELEVATION 3 STORY PARTIAL ENCLOSED PORCH 6X6 COLUMNS HAVE SCABBING,1FT SPLICES,OVERNOTCHED AND FIRECUTS PULLING AWAY AT BEAM TO COLUMN CONNECTIONS,GUARDRAILS ARE UNDER 42" HIGH,TOENAILED TO COLUMNS AND MISSING INTERMEDIATE POSTS,STAIR TREADS ARE ONLY 91/4" IN DEPTH AND FASTENED WITH NAILS SUBMIT PLANS AND OBTAIN PERMIT BEFORE REPAIRING OR REPLACING PORCH. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EAST ELEVATION FRONT BUILDING LOOSE AND MISSING ASPHALT SIDING ALSO REAR BUILDING SOUTH ELEVATION SPALLING BRICKS AND WASHED OUT MORTER JOINTS. | 2401 S TROY ST | PERIODIC | FAILED | View |
NO KEY TO USE EXIT DOOR | EAST ELEVATION GATE HAS DOUBLE CYLINDER LOCK. | 2401 S TROY ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | FRONT BUILDING NOT REGISTERED FROM 1990 THRU 2012. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | REAR BUILDING EAST ELEVATION AT GRADE BROKEN WINDOW PANE. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR | REAR BUILDING WEST ELEVATION 1ST FLOOR COMMON DOOR ROTTED AT BOTTOM WITH LARGE GAP. | 2401 S TROY ST | PERIODIC | FAILED | View |
INSTALL DEAD BOLT LOCK | REAR BUILDING WEST ELEVATION 1ST FLOOR MISSING ENTRY LOCK. | 2401 S TROY ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | REAR BUILDING WEST ELEVATION BASEMENT STAIRWELL MISSING GUARDRAIL. | 2401 S TROY ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | FRONT BUILDING NOT REGISTERED FROM 1990 THRU 2012. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | REAR BUILDING EAST ELEVATION AT GRADE BROKEN WINDOW PANE. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR | REAR BUILDING WEST ELEVATION 1ST FLOOR COMMON DOOR ROTTED AT BOTTOM WITH LARGE GAP. | 2401 S TROY ST | PERIODIC | FAILED | View |
INSTALL DEAD BOLT LOCK | REAR BUILDING WEST ELEVATION 1ST FLOOR MISSING ENTRY LOCK. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | REAR BUILDING WEST ELEVATION BASEMENT STAIRWELL MISSING HANDRAIL. | 2401 S TROY ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | 1ST FLOOR ... NO CARBON MONOXIDE DETECTOR. | 2401 S TROY ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | 1ST FLOOR ... NO CARBON MONOXIDE DETECTOR. | 2401 S TROY ST | COMPLAINT | FAILED | View |
PROVIDE | 1ST FLOOR IS MISSING AN EXIT SIGN ... SECTION 10(13-160-750). | 2401 S TROY ST | COMPLAINT | FAILED | View |
REPAIR FLOOR | FRONT INTERIOR STAIRS 2ND FLOOR TILES LOOSE AND MISSING. | 2401 S TROY ST | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | FRONT 2ND FLOOR MISSING VIEWING DEVICECOACH HOUSE 2ND FLOOR NO VIEWING DEVICE. | 2401 S TROY ST | PERIODIC | FAILED | View |
INSTALL DEAD BOLT LOCK | FRONT EXTERIOR DOOR MISSING DEAD BOLT. | 2401 S TROY ST | PERIODIC | FAILED | View |
CHIMNEY | SOUTH CHIMNEY WASHED OUT MORTAR.NORTH ELEVATION - CHIMNEY LEANING OUT 6" OUT OF PLUMB MASON PERMINT REQUIRED FOR ALL MASONARY WORK TO BE DONE | 2401 S TROY ST | PERIODIC | FAILED | View |
PROTECT SIDEWALK DURING CONST | NORTH ELEVATION - CANOPY REQUIRED FOR REPAIRS TO CHIMNEY | 2401 S TROY ST | PERIODIC | FAILED | View |
RELOCATE SMOKE DETECTOR | 3RD FLOOR APT 2 SMOKE DETECTOR 2' TO CEILING.REAR COACH HOUSE 2ND FLOOR SMOKE DETECTOR 2' TO CEILING. | 2401 S TROY ST | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 3RD FLOOR HALLWAY AND REAR PORCH BOXES BLOCKING EGRESS. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | REAR COACH HOUSE 2ND FLOOR SOMOKE DETECTOR NOT WORKING.REAR COACH HOUSE BASEMENT SMOKE DETECTOR NOT WORKING.FRONT 1ST FLOOR REAR APT SMOKE DETECOR NOT WORKING AT TIME OF INSPECTION.3RD FLOOR SMOKE DETECTOR NOT WORKING. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCH GRADE TO 3RD FLOOR FIRE CUTS NO ANGLE. COLUMNS 1/2 LAPS 12' WITH 4 BOLTS.JOIST HANGERS NAILED TO HEADERS.1ST FLOOR DECK BOARD LOOSEGUARD RAILS AND STRINGERS NAILED TO COLUMNS,HEADERS AND WALL.GUARD RAILS 36" HIGH.1ST FL PICKETS BROKENPERMIT REQUIRED FOR REPAIR TO PORCH. | 2401 S TROY ST | PERIODIC | FAILED | View |
CHIMNEY CAPPING | COACH HOUSE CHIMNEY CAP OPEN MORTAR JOINT. | 2401 S TROY ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | REAR STORY PORCH AT GRADE MISSING GUARD RAILS. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | COACH HOUSE FRONT STAIRS GRADE TO 2ND FLOOR .4X4 COLUMN ERECTED ON BLOCKS AND SERVICE WALK.JOIST NAILED TO HEADERS.FRONT STAIRS SOUTH CEMENT AND IRON TREADS CRACKED AND SHIFTING OUT.FRONT NORTH STAIRS GRADE TO 1ST FLOORCEMENT STAIRS CRACKED PERMIT REQUIRED FOR REPAIRS FRONT COACH HOUSE STAIRS AND FRONT STAIRSFRONT STAIRS SOUTH CEMENT AND IRON TREADS CRACKED AND SHIFTING OUT | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | WEST ELEVATION - WINDOW SILLS OPEN MORTAR JOINTS | 2401 S TROY ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FRONT 1ST FLOOR STORE FIRE EXTINGUISHER TAGED 2014 | 2401 S TROY ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | REAR BUILDING WEST ELEVATION BASEMENT STAIRWELL MISSING GUARDRAIL. | 2401 S TROY ST | PERIODIC | FAILED | View |
NO KEY TO USE EXIT DOOR | EAST ELEVATION GATE HAS DOUBLE CYLINDER LOCK. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR 3RD FLOOR SIDING MISSING AND LOOSE | 2401 S TROY ST | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | NORTH AND WEST ELEVATION -GRAFFITI | 2401 S TROY ST | PERIODIC | FAILED | View |
PROVIDE | 1ST FLOOR ... THERE IS ONLY ONE EXIT SIGN POSTED. SECTION 10 (13-160-750). | 2401 S TROY ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE, UNABLE TO VERFY DETECTORS. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR/REBUILD GARAGE OR SHED | GARAGE - STEP CRACK. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | SOUTHEAST CORNER - SPALLING BRICKS.REAR PORCH - TORN SIDING.EAST ELEVATION STEP CRACK. | 2401 S TROY ST | PERIODIC | FAILED | View |
PARAPET | EAST PARAPET - LOOSE PARGE COAT. | 2401 S TROY ST | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | EAST SILLS - ERODED MORTAR JOINTS. | 2401 S TROY ST | PERIODIC | FAILED | View |