Chicago Building Violations Data: 95 Violations
Violation Inspector Comments Address Category Status View
ARRANGE FOR INSPECTION CONTACT INSPECTOR ROBINSON #983 @ 312 743 3562 ON THURSDAYS FROM 700-800AM 7555 S RACINE AVE PERIODIC FAILED View
PRV RECEIVER 450# PSIG FOR THE FOLLOWING ONE 1.5 TON REMOTE REFRIGERATION UNIT THAT SERVES THE W.I.C. THE UNIT IS LOCATED ON THE ROOF 7555 S RACINE AVE PERIODIC FAILED View
PRV RECEIVER 450# PSIG FOR THE FOLLOWING ONE 1.5 TON REMOTE REFRIGERATION UNIT THAT SERVES THE W.I.C. THE UNIT IS LOCATED ON THE ROOF 7555 S RACINE AVE PERIODIC PASSED View
ARRANGE FOR INSPECTION CONTACT INSPECTOR ROBINSON #983 @ 312 743 3562 ON THURSDAYS FROM 700-800AM 7555 S RACINE AVE PERIODIC PASSED View
ACCESS TO ROOF ACCESS 7555 S RACINE AVE PERIODIC PASSED View
INTERIOR FINISH FIRERESISTANCE PLYWOOD PARTITIONS AT INTERIOR 7555 S RACINE AVE COMPLAINT PASSED View
BLOCKED FIRE DOOR EAST EXIT BLOCKED BY STOCK 7555 S RACINE AVE COMPLAINT PASSED View
SEAL DRAIN OPENING UNUSD FIXTR SEAL OPEN FLOOR DRAIN IN STORE AREA. 7555 S RACINE AVE COMPLAINT PASSED View
REPAIR EAVES ROTTED EAVES HOLES IN FACIA 7555 S RACINE AVE COMPLAINT PASSED View
REPAIR FENCE BROKEN SECTIONS OF TOP RAIL NORTH FENCE 7555 S RACINE AVE COMPLAINT PASSED View
FLUE PIPE CLEARANCE 6"X FLUE PASSES THROUGH DROPPED CEILING AT REAR 7555 S RACINE AVE COMPLAINT PASSED View
INTERIOR FINISH FIRERESISTANCE MISSING LARGE SECTIONS OF DRYWALL AT CEILING 7555 S RACINE AVE COMPLAINT PASSED View
LICENSED BONDED PLMBG CONTRCTR (4-332-010-100) EMPLOY A LICENSED AND BONDED PLUMBING CONTRACTOR. 7555 S RACINE AVE COMPLAINT PASSED View
OBTN PERMIT FOR PLUMBING WORK OBTAIN A PERMIT FOR PLUMBING BEFORE UNDERTAKING WORK 7555 S RACINE AVE COMPLAINT PASSED View
REPAIR DEFECTIVE DOWNSPOUT REPAIR OR REPLACE DEFECTIVE RAIN GUTTERS AND DOWNSPOUTS CREATING UNSANITARY CONDITIONS. 7555 S RACINE AVE COMPLAINT PASSED View
EXPOSE FOR INSPECT APPROVAL EXPOSE PLUMBING SYSTEM FOR INSPECTION AND APPROVAL WHERE COOLERS HAVE BEEN INSTALLED AND PLUMBING SYSTEM HAS BEEN ALTERED WITHOUT PERMIT. 7555 S RACINE AVE COMPLAINT PASSED View
OPEN (13-180-220) REMOVE WATER HEATER FROM BATHROOM AND REINSTALL IN PROPER AREA. 7555 S RACINE AVE COMPLAINT PASSED View
PRV CNTRL VALVE WATER SUPPLY PROVIDE CONTROL VALVE FOR WATER SUPPLY TO WATER HEATER AND WATER SERVICE TO BUILDING. 7555 S RACINE AVE COMPLAINT PASSED View
SOIL/WASTE,VENT PIPE MATRL PROVIDE PROPER MATERIALS FOR WASTE AND TRAPS FOR PLUMBING FIXTURES (REMOVE P.V.C. WASTE PIPING AND TRAPS) 7555 S RACINE AVE COMPLAINT PASSED View
OPEN (18-29-802.1.3 - 802.1.5) PROVIDE A FLOOR FOR DISCHARGE FROM WATER HEATER RELIEF VALVE. 7555 S RACINE AVE COMPLAINT PASSED View
REPLACE DEFECTIVE WATER PIPING (18-29-705.14.2) REPLACE ALL FLEXIBLE WATER SUPPLIES TO PLUMBING FIXTURES WITH SOLID ONES. 7555 S RACINE AVE COMPLAINT PASSED View
OPEN (18-29-102.3), (18-29-705.14.2) REPLACE DUAL OUTLET ANGLE STOP WITH SINGLE OUTLET ANGLE STOP ON HOT WATER SIDE OF LAVATORY. (BEING USED WITH A SPRAY HOLE ON IT). 7555 S RACINE AVE COMPLAINT PASSED View
ADD RECEPTACLES ADD RECEPTACLE TO EASE EXTENSION CORD USE FOR COOLER'S AND NEON SIGNS THROUGH OUT STORE -- 7555 S RACINE AVE COMPLAINT PASSED View
CONTINUITY OF RACEWAY PROVIDE GROUND CONTINUITY FOR CEILING LIGHT FIXTURES, EXTERIOR 1" CONDUIT RUN BY SERVICE RISER, EXTERIOR 1/2" CONDUIT RUN ON FRONT OF BUILDING, INTERIOR SEALTITE ABOVE COOLER'S INSIDE STORE DANGEROUS AND HAZARDOUS CONDITION -- 7555 S RACINE AVE COMPLAINT PASSED View
INSTALL COVERS PROVIDE PROPER COVERS FOR EXPOSED WIRES AT JUNCTION BOXES BY PANELS AND IN CEILING AREA'S -- 7555 S RACINE AVE COMPLAINT PASSED View
(18-27-110.11) PROVIDE WEATHER PROOF LIGHTS AND BOXES FOR ALL EXTERIOR LIGHTS THROUGH OUT STORE AREA -- 7555 S RACINE AVE COMPLAINT PASSED View
SECURE RACEWAY PROPERLY SUPPORT CONDUIT RUNS THROUGH OUT CEILING AREA'S, COOLER AREA'S -- 7555 S RACINE AVE COMPLAINT PASSED View
(18-27-110.12) ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMAN LIKE MANNER - ALL CONDUIT RUNS THROUGH OUT STORE AREA'S -- INTERIOR AND EXTERIOR -- 7555 S RACINE AVE COMPLAINT PASSED View
REMOVE************** (18-27-351) EXCESSIVE USE OF SEALTITE USED ABOVE COOLER AREA'S TO ROOF - 7555 S RACINE AVE COMPLAINT PASSED View
SEE INSPECTOR COMMENTS (13-12-360) OBTAIN ELECTRICAL PERMIT BEFORE STARTING TO CORRECT ELECTRICAL VIOLATIONS 7555 S RACINE AVE COMPLAINT PASSED View
SECURE RACEWAY PROPERLY SUPPORT JUNCTION BOX AND CONDUIT RUN THROUGH OUT THE REAR DROP CEILING AREA DANGEROUS AND HAZARDOUS CONDITION 7555 S RACINE AVE COMPLAINT FAILED View
ARRANGE FOR REINSPECTION REGAR REMOVE TILES FOR FULL CEILING INSPECTION STRUCTURAL AND MECHANICAL 14A-1-104.7 7555 S RACINE AVE COMPLAINT FAILED View
RESTORE EXIT AND EM RESTORE ALL EXIT SIGNS AND EM LIGHTS TO WORKING CONDITION DANGEROUS AND HAZARDOUS CONDITION 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE AISLE OBSTRUCTIONS THROUGH-OUT STORE CASHIER 22", AISLE 22" TO 27" DANGEROUS AND HAZARDOUS14B-10-1018.1 7555 S RACINE AVE COMPLAINT FAILED View
GAP AT BOX WALL FINISH IN REAR OF STORE THERE IS A DISCONNECT AND BOX WITH RECEPTACLE WHICH IS RECESS ABOUT 4" BACK OF FINISH WALL BOXES ARE NOT ACCESSIBLE DANGEROUS AND HAZARDOUS CONDITION 7555 S RACINE AVE COMPLAINT FAILED View
OBTAIN PERMIT TO CORRECT ELECTRICAL VIOLATIONS. (13-12-360) 7555 S RACINE AVE COMPLAINT FAILED View
CARB MONOX DETECT IN RESID MISSING CARBON MONOXIDE DETECTOR. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
REPAIR FENCE NORTH AND EAST CHAIN LINK FENCE DAMAGED, LEANING AND OUT OF PLUMB, TOP AND BOTTOM RAIL DISCONNECTED AT VARIOUS LOCATIONS. 7555 S RACINE AVE COMPLAINT FAILED View
SECURE RACEWAY SUPPORT THE PIPE ABOVE THE DROP CEILING AREA. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
ACCESS TO JBS BOXES IN THE DROP CEILING ABOVE THE DRYWALL NEED TO BE ACCESSIBLE. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE NO MIXING VALVE AT LAVATORY. (18-29-607.1.1) 7555 S RACINE AVE COMPLAINT FAILED View
NEED TO SUPPORT THE COMMUNICATION WIRING ABOVE THE DROP CEILING PROPERLY. (14E-8-800.24) 7555 S RACINE AVE COMPLAINT FAILED View
REPAIR OR REPLACE PARKING LOT GUARDRAILS/BUMPER GUARD DISCONNECTED FROM "I-BEAM" POSTS NEAR FRONT ENTRY DOOR. (13-196-010) 7555 S RACINE AVE COMPLAINT FAILED View
OBSTRUCTIONS IN EXIT WAY EAST MARKED EXIT WELDED SHUT AND BLOCKED BY STOCK. INTERIOR DOOR BEHIND EMPLOYEE COUNTER AREA IS ONLY 26". (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
SUPPORT OUTLET AND BOX SUPPORT THE BOX AND RECEPTACLE HANGING FROM THE DROP CEILING BEHIND THE CHIP RACK ON THE SOUTH ELEVATION OF THE STORE AND THE BOXES ABOVE THE DROP CEILING AREA. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
STOP/REMOVE NUISANCE EXCESSIVE STORAGE/STOCK ON FLOOR AND TOP OF COOLER FIRE HAZARD DANGEROUS AND HAZARDOUS 7555 S RACINE AVE COMPLAINT FAILED View
FLAMMABLE LIQUIDS 10-GAL LIMIT GAS GENERATOR ON TOP OF COOLER FIRE HAZARD DANGEROUS AND HAZARDOUS 14B-33-3317.1 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE INTERIOR PLATFORM 13" HIGH TRIP HAZARD APPROXIMATELY 6'X20', IF OVER 100 SQ REQUIRES PLANS AND PERMIT FOR FIRE BLOCKING DANGEROUS AND HAZARDOUS 14X-5-502 7555 S RACINE AVE COMPLAINT FAILED View
WORK NOT ALLOWED REMOVE ALL PARTITIONS AND FIXTURES (INCLUDING PLUMBING AND ELECTRIC) INSTALLED IN THE BUILDING WITH-OUT PLANS AND PERMIT EVIDENCE OF MULTIPLE UN IT MERCANTILE (1 STORY)BUSINESS BREACH IN WALLS TO MAKE SINGLE OCCUPANCY BEAM TO COLUMN CONNECTION COMPROMISED BY WAY OF COLUMN SCABBED BETWEEN BEAM AND COLUMN SEVERAL BRICKED OPENINGS EVIDENCE AT EXTERIOR WALLS METAL COVERING ON BRICK WALLS AND BRICKED IN DOORS AND WINDOWS DANGEROUS AND HAZARDOUS 14A-4-401 7555 S RACINE AVE COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO BUILDING 14A-4-401.1 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE NO SAFE PAN FOR HOT WATER TANK IN REAR OF STORE 18-29-504.8 7555 S RACINE AVE COMPLAINT FAILED View
WORKING SPACE PROVIDE PROPER CLEARANCES FOR PANELS OBSTRUCTED BY METAL TABLE AND PANEL OBSTRUCTED BY COOLERS WITH ACCESS OF 12" FROM BACK OF COOLER TO FRONT OF PANEL DANGEROUS AND HAZARDOUS CONDITION 7555 S RACINE AVE COMPLAINT FAILED View
ADD RECEPTACLES ADD RECEPTACLES TO EASE EXTENSION CORD USE IN SMALL OFFICE AREA AND COUNTERTOP AREAS DANGEROUS AND HAZARDOUS CONDITION 7555 S RACINE AVE COMPLAINT FAILED View
ABANDONED EQUIPMENT REMOVE ALL ABANDONED RACEWAY, BOXES, LIGHT FIXTURE THROUGH OUT THE DROP CEILING AREAS 7555 S RACINE AVE COMPLAINT FAILED View
DEFECTIVE FIXTURES ALTERED LIGHTS AND COVERS MISSING OFF OF ALL 2X4 LIGHT FIXTURES DANGEROUS AND HAZARDOUS 7555 S RACINE AVE COMPLAINT FAILED View
OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS 14A-4-404.6 7555 S RACINE AVE COMPLAINT FAILED View
SERVICE WALK, PASSAGE, AREAWAY PARKING LOT LARGE POT HOLES AND UNEVEN SURFACES 14X-3-302.4 7555 S RACINE AVE COMPLAINT FAILED View
REPAIR EXTERIOR WALL EXTERIOR WALLS EAST AND WEST ELEVATIONS STRESS FRACTURES PERMIT REQUIRED FOR ALL WORK 14X-3-303.1.1 7555 S RACINE AVE COMPLAINT FAILED View
WORK NOT ALLOWED FENCE OVER 5' REDUCE HEIGHT OR OBTAIN PERMIT 14A-4-404.7 7555 S RACINE AVE COMPLAINT FAILED View
OBTN PERMIT FOR PLUMBING WORK OBTAIN PLUMBING PERMIT FOR PLUMBING WORK TO BE PERFORMED 7555 S RACINE AVE COMPLAINT FAILED View
LICENSED BONDED PLMBG CONTRCTR EMPLOY LICENSED AND BONDED PLUMBING CONTRACTOR FOR PLUMBING WORK TO BE PERFORMED TO ADDRESS PLUMBING VIOLATIONS 7555 S RACINE AVE COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE 3/4 FLEXIBLE COLD AND HOT WATER SUPPLY LINES TO HOT WATER TANK UNDER THREE COMPARTMENT SINK 7555 S RACINE AVE COMPLAINT FAILED View
PRV FLOOR DRAIN WITH METAL STR NO FLOOR DRAIN INSTALLED IN COMMERCIAL BATHROOM 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE INDIRECT WASTE CONNECT CONDENSATE LINE LOCATED AT REAR BUILDING IS NOT CONNECTED TO BUILDING SEWER SYSTEM 7555 S RACINE AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION PROVIDE APPROVE LIGHTS FOR WALK IN COOLER AREAS 7555 S RACINE AVE COMPLAINT FAILED View
INSTALL COVERS PROPERLY SECURE COVER FOR ELECTRICAL PANEL AT REAR STORE AREA 7555 S RACINE AVE COMPLAINT FAILED View
ACCESS TO ROOF 7555 S RACINE AVE PERIODIC FAILED View
SUPPORT FIXTURES PROPERLY SUPPORT ALL 2X4 FLUORESCENT LIGHT FIXTURES THROUGH OUT STORE - 7555 S RACINE AVE COMPLAINT PASSED View
REPAIR ROOF ROOF LEAKS NORTH EAST CORNER 7555 S RACINE AVE COMPLAINT PASSED View
OPEN (18-29-102.3) REPLACE FLEXIBLE SUPPLIES TO WATER HEATER WITH SOLID PIPING. 7555 S RACINE AVE COMPLAINT PASSED View
WORKING SPACE PROVIDE PROPER CLEARANCES FOR ALL ELECTRICAL PANELS AND DISCONNECTS THROUGH OUT STORE AREA'S -- 7555 S RACINE AVE COMPLAINT PASSED View
SYSTEM III PROVIDE BATTERY BACK UP EXIT SIGNS - REMOVE AND REPLACE WITH CURRENT TYPE 7555 S RACINE AVE COMPLAINT PASSED View
INSTALL SUFFICIENT FIXTURES INSTALL JANITORS SINK FOR CLEANING PURPOSES. 7555 S RACINE AVE COMPLAINT PASSED View
REPAIR EXTERIOR WALL EXTERIOR MASONRY WALL: STEP FRACTURE AT NORTHEAST CORNER. 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE VARIOUS AISLES REDUCED BELOW THE REQUIRED 36" MINIMUM (VARIES FROM 26", 27", AND 28"). (15-4-880) 7555 S RACINE AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG FIRE EXTINGUISHER TAG OUTDATED (FROM MAY 2019) 7555 S RACINE AVE COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE REMOVE ALL UNAPPROVED FLEXIBLE SUPPLY LINES AT TOILET AND LAVATORY IN BATHROOM. 7555 S RACINE AVE COMPLAINT FAILED View
PROVIDE OPEN FRONT TOILET SEAT NO OPEN FRONT COMMERCIAL TOILET SEAT. 7555 S RACINE AVE COMPLAINT FAILED View
REPLACE DEFECTIVE FAUCET HANDLE MISSING ON FAUCET IN BATHROOM. 7555 S RACINE AVE COMPLAINT FAILED View
OBTN PERMIT FOR PLUMBING WORK OBTAIN PERMIT. 7555 S RACINE AVE COMPLAINT FAILED View
LICENSED BONDED PLMBG CONTRCTR OBTAIN LICENSED PLUMBING CONTRACTOR. 7555 S RACINE AVE COMPLAINT FAILED View
EXPOSED WIRING EXPOSED WIRING ON THE SOUTHEAST EXTERIOR ELEVATION OF THE BUILDING. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
INSTALL COVERS MISSING COVERS ON BOX ON THE SOUTHEAST EXTERIOR OF THE BUILDING, ON THE LIGHTS ON THE WEST EXTERIOR OF THE BUILDING, ABOVE THE DROP CEILING IN THE STORE, AND ABOVE THE DRYWALL IN THE STORE AREA ABOVE THE DROP CEILING AND IN THE WALK-IN COOLER LIGHT FIXTURE IS MISSING COVER. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
UNAPPROVED CORDS REMOVE EXTENSION CORDS GOING THROUGH THE DROP CEILING OF THE STORE AND THE CORDS GOING TO THE FREEZER IN THE MIDDLE OF THE STORE. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
ADD RECEPTACLES INSTALL ADDITIONAL RECEPTACLES TO EASE THE USE OF CORDS IN THE STORE. 7555 S RACINE AVE COMPLAINT FAILED View
CLOSE BOX OPENINGS CLOSE ALL UNUSED OPENINGS IN THE PANELS AND BOXES THROUGHOUT THE STORE AREA. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAYS ARMORED CABLE GOING TO THE HOT WATER TANK IS NOT PROPERLY CONNECTED TO THE HOT WATER TANK (MISSING CONNECTOR TO THE HOT WATER TANK). (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
APPLIANCE INSIGHT DISCONNECT ELECTRICAL HOT WATER TANK UNDER THE SINK IS MISSING A DISCONNECT SWITCH. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
ABANDONED EQUIPMENT REMOVE ABANDONED PIPE AND WIRING ABOVE THE DROP CEILING OF THE STORE AREA. 7555 S RACINE AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION ARMORED CABLE AND CONNECTORS IN THE FREEZER AREA IS NOT RATED TO BE USED IN THE FREEZER AREA. 7555 S RACINE AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAYS THE SWITCH IN THE FREEZER AREA IS NOT PROPERLY ATTACHED TO THE JUNCTION BOX. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
WORKING SPACE MISSING CLEARANCE IN FRONT OF THE PANEL AREA. (DANGEROUS AND HAZARDOUS) 7555 S RACINE AVE COMPLAINT FAILED View
PANEL SCHEDULES NEED TO LABEL THE PANELS PROPERLY. 7555 S RACINE AVE COMPLAINT FAILED View
SUPPLEMENTAL GROUND MISSING SUPPLEMENTAL GROUND TO THE METER BANK. 7555 S RACINE AVE COMPLAINT FAILED View