Chicago Building Violations Data: 11 Violations
Violation Inspector Comments Address Category Status View
SEE INSPECTOR COMMENTS PROVIDE REQUIRED PERFORMANCE TESTING OF GROUND FAULT PROTECTION SYSTEM WHEN FIRST INSTALLED ON-SITE.18-27-230.95(C) 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS PROVIDE PROPER GROUNDING ELECTRODE SYSTEM, PROPERLY BOND ALL EQUIPMENT REQUIRED TO BE BONDED.18-27-250.3 & .50 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS PROVIDE MAIN BONDING JUMPER.18-27-250.28 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS INSTALL EQUIPMENT GROUNDING CONCUCTOR IN UNDERGROUND PVC RACEWAYS.18-27-250.100 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS NO REPONSE TO DEFECT LETTER SENT 03/25/19 FOR 11655 S TORRENCE AVE PERMIT #100736124 RESULTS IN IMMEDIATE SUSPENSION OF PERMITTING PRIVILEGES AND AN ADDITIONAL $250 FEE 13-12-430 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS FAILED TO SCHEDULE AN INSPECTION PRIOR TO ENERGIZING EQUIPMENT.13-12-420 11655 S TORRENCE AVE PERMIT FAILED View
SEE INSPECTOR COMMENTS ELECTRICAL EQUIPMENT MUST BE APPROVED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.18-27-110.3 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS PROVIDE REQUIRED WORKING SPACE ABOUT ALL ELECTRICAL EQUIPMENT.18-27-110.26 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS MUST INSTALL GROUNDED CONDUCTOR TO FIRST SYSTEM DISCONNECTING MEANS AND BE BONDED PROPERLY.18-27-250.36(D) 11655 S TORRENCE AVE PERMIT FAILED View
SEE INSPECTOR COMMENTS SIZE GROUNDING ELECTRODE CONDUCTOR PROPERLY.18-27-250.66 11655 S TORRENCE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS WORK IS CONTRARY TO PLANS.13-12-050(I)(I) & 13-12-080(I)(I) 11655 S TORRENCE AVE PERMIT FAILED View