The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | PROVIDE REQUIRED PERFORMANCE TESTING OF GROUND FAULT PROTECTION SYSTEM WHEN FIRST INSTALLED ON-SITE.18-27-230.95(C) | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE PROPER GROUNDING ELECTRODE SYSTEM, PROPERLY BOND ALL EQUIPMENT REQUIRED TO BE BONDED.18-27-250.3 & .50 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE MAIN BONDING JUMPER.18-27-250.28 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL EQUIPMENT GROUNDING CONCUCTOR IN UNDERGROUND PVC RACEWAYS.18-27-250.100 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | NO REPONSE TO DEFECT LETTER SENT 03/25/19 FOR 11655 S TORRENCE AVE PERMIT #100736124 RESULTS IN IMMEDIATE SUSPENSION OF PERMITTING PRIVILEGES AND AN ADDITIONAL $250 FEE 13-12-430 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | FAILED TO SCHEDULE AN INSPECTION PRIOR TO ENERGIZING EQUIPMENT.13-12-420 | 11655 S TORRENCE AVE | PERMIT | FAILED | View |
SEE INSPECTOR COMMENTS | ELECTRICAL EQUIPMENT MUST BE APPROVED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.18-27-110.3 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE REQUIRED WORKING SPACE ABOUT ALL ELECTRICAL EQUIPMENT.18-27-110.26 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | MUST INSTALL GROUNDED CONDUCTOR TO FIRST SYSTEM DISCONNECTING MEANS AND BE BONDED PROPERLY.18-27-250.36(D) | 11655 S TORRENCE AVE | PERMIT | FAILED | View |
SEE INSPECTOR COMMENTS | SIZE GROUNDING ELECTRODE CONDUCTOR PROPERLY.18-27-250.66 | 11655 S TORRENCE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | WORK IS CONTRARY TO PLANS.13-12-050(I)(I) & 13-12-080(I)(I) | 11655 S TORRENCE AVE | PERMIT | FAILED | View |