Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View | |
INSTALL | DIVERTORS ON EXHAUST AND INTAKE FOR #1 HYDROTHERM BD# 22753. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
INSTALL | DIVERTORS ON EXHAUST AND INTAKE FOR #2 HYDROTHERM BD# 22751. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
INSTALL | DIVERTORS ON EXHAUST AND INTAKE FOR #3 HYDROTHERM BD# 22752. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
INSTALL | PROTECTIVE CAGE OVER DIVERTORS TO PREVENT VANDALISM AND NESTING OF WILDLIFE. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View | |
GIVE VENT OPENINGS % FL. AREA | PROVIDE MECHANICAL EXHAUST VENTILATION AT CU FT PER MINUTE EQUAL TO S FT OF FLOOR AREA TIMES FACTOR BASED ON USE (18-28-403.3) (1) ALL EXHAUST RETURN FANS NOT GOING INTO PROPER EXHAUST MODE DUE TO FAULTY ACTUATORS NOT WORKING PROPERLY (2) NEED TO INSTALL EXHAUST FAN FOR MOP BASIN | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
PROVIDE OUTSIDE AIR SUPPLY | PROVIDE OUTSIDE AIR SUPPLY (18-28-403.1) ALL O.A.I. ACTUATORS NOT WORKING PROPERLY TO BRING IN CODE REQUIREMENT OF OUTSIDE AIR | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
POST CURRENT CERTIF PASS ELE | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View | |
TEST G & S PASS ELE | PRESSURE TEST AND TAG VALVE. | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |
SECURE TOP ACCESS COVER PASS | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View | |
OPEN TYPE VIOLATION | 1. PROPERLY MAINTAIN ELEVATOR IN A SAFE OPERATING CONDITION. ELEVATOR IS CURRENTLY NOT BEING PROPERLY MAINTAINED. 2. PROVIDE APPROVED SUMP PUMP COVER ELEVATOR PIT. (13-196-590,13-196-630) 18-30-010,13-20-120 (EV011935) | 1841 N SPRINGFIELD AVE | PERIODIC | PASSED | View |