Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
REPAIR | BURNER REFRACTORY #1 BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE TRI COCKS ON BOILERS #2. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #1 BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
PRV RECEIVER | 450 PSIG FOR THE FOLLOWING TWO ONE TON REMOTE REFRIGERATION UNITS THAT SERVES THE W.I.C/W.I.F. THE UNITS ARE LOCATED IN THE KITCHEN. | 7646 S GREEN ST | PERIODIC | FAILED | View |
CONNECT VENT LINE | FOR THE ABOVE EQUIPMENT | 7646 S GREEN ST | PERIODIC | FAILED | View |
PRV RECEIVER | 450 PSIG FOR THE FOLLOWING TWO ONE TON REMOTE REFRIGERATION UNITS THAT SERVES THE W.I.C/W.I.F. THE UNITS ARE LOCATED IN THE KITCHEN. | 7646 S GREEN ST | PERIODIC | PASSED | View |
CONNECT VENT LINE | FOR THE ABOVE EQUIPMENT | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE CONTROL ON INTAKE AIR DAMPER #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
ADJUST BOILER BURNER | #2 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REMOVE CHIMNEY DEBRIS | BOILER ROOM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE GAS VALVE ON #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
BAROMETRIC CONTROL | #1 KEWANEE SCOTCH MARINE BOILERS. | 7646 S GREEN ST | PERIODIC | PASSED | View |
BAROMETRIC CONTROL | #2 KEWANEE SCOTCH MARINE BOILERS. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
LEAKING BOILER TUBES | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
REPAIR | REPLACE DEFECTIVE FIRE EYE #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | MISSING TRI-COCK KNOBS ON BOILER #1. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | MISSING TRI-COCK KNOBS ON BOILER #2. | 7646 S GREEN ST | PERIODIC | PASSED | View |
WATER GAUGE GLASS | #2 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
WATER GAUGE GLASS | #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE WATER GAUGE GLASS BOILER FEED WATER TANK. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | DEFECTIVE BROKEN BURNER SIGHT GTLASS REAR MANHOLE DOOR. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
BLOW-DOWN VALVE - LOW WATER | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
BLOW-DOWN VALVE - LOW WATER | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | BOTTOM BLOW DOWN VALVES #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | BOTTOM BLOW DOWN VALVES #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
ADJUST BOILER BURNER | #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #2 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
DEFECTIVE SAFETY VALVE-BOILER | #2 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
MAINT INCLIN VERT WHLCHAR LIFT | REPAIR EMERGENCY PHONE | 7646 S GREEN ST | COMPLAINT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
MAINTAIN | CLEAR BOILERDRAIN LINES FOR PROPER BOILER OFFS ON BOILER #1. | 7646 S GREEN ST | PERIODIC | PASSED | View |
MAINTAIN | CLEAR BOILER DRAIN LINES FOR PROPER BOILER BLOW OFFS ON BOILER #2. | 7646 S GREEN ST | PERIODIC | PASSED | View |
INTERNAL | #2 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPAIR DOOR HARDWARE | REPLACE MISSING DOOR CLOSER AT AUDITORIUM BALCONY DOOR. | 7646 S GREEN ST | PERIODIC | FAILED | View |
DOOR SWING IN DIR. OF TRAVEL | CAFETERIA EXIT DOORS SWING AGAINST EXIT TRAVEL. | 7646 S GREEN ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 7646 S GREEN ST | PERIODIC | FAILED | View | |
FIRE EXTNGSHR REQ, RESDNTL | RECHARGE AND RETAG ALL FIRE EXTINGUISHERS | 7646 S GREEN ST | PERIODIC | FAILED | View |
PROVIDE | PROVIDE A REPORT FROM A ILLINOIS LIC.ASBESTOS TESTING COMPANY FOR THE COVERING ON WATER TANK @ BSMNT (EXPOSED) AND ABATE IF REQUIRED. | 7646 S GREEN ST | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | REPLACE WINDOW GLASS IN ALL FIRE DOORS AND TRANSOMS WITH RATED GLASS AT REQUIRED OPENINGS. | 7646 S GREEN ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OCCUPANCY CARDS REQUIRED AT AUDITORIUM BALCONY AND STUDENT LUNCHROOM. | 7646 S GREEN ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | REPLACE MISSING DOORS @ STAIRWELL #6 BSMNT | 7646 S GREEN ST | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
INTERNAL | #1 KEWANEE 74 SM. | 7646 S GREEN ST | PERIODIC | PASSED | View |
SEE INSPECTOR COMMENTS | #1 AIR TANK. | 7646 S GREEN ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | NO.1 AND NO.2 KEWANEE SCOTCH MARINE BOILERS | 7646 S GREEN ST | PERIODIC | CLOSED | View |
REPLACE BOILER PRESSURE GAUGE | NO.2 KEWANEE SCOTCH MARINE BOILER | 7646 S GREEN ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | CLOSED | View | |
REPLACE | DEFECTIVE TRI COCKS ON BOILERS #1. | 7646 S GREEN ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 7646 S GREEN ST | PERIODIC | PASSED | View | |
SEAL CRACKED BRICKWORK | #1 KEWANEE SCOTCH MARINE BOILER. | 7646 S GREEN ST | PERIODIC | PASSED | View |
REPLACE | OR REPAIR BROKEN, MISSING HEADER VALVE CONTROL WHEEL. | 7646 S GREEN ST | PERIODIC | PASSED | View |