Chicago Building Violations Data: 37 Violations
Violation Inspector Comments Address Category Status View
LICENSED BONDED PLMBG CONTRCTR OBTAIN A LICENSED PLUMBER TO DO PLUMBING WORK. 7141 S STATE ST COMPLAINT PASSED View
(18-27-110.4) REMOVE ALL IMPROPER CONNECTIONS IN PANELS AT LIGHT FIXTURES IN CEILING. REMOVE CARDBOARD IN CEILING TILES TO COMPLETE REINSPECTION OF LIGHTING CONDUIT SYSTEM. 7141 S STATE ST COMPLAINT PASSED View
REPAIR FLOOR CONCRETE FLOORS IN VARIOUS LOCATIONS CRACKING AND MISSING SECTIONS IN MULTIPLE LOCATIONS WITH STANDING WATER AT INTERIOR IS A SLIP AND FALL HAZARD. 7141 S STATE ST COMPLAINT PASSED View
REPAIR DOWNSPOUT DOWNSPOUT IN THE INTERIOR OF THE STORE LOCATED IN THE FREEZER AREA IMPROPER MATERIAL REMOVE AND REPLACE WITH THE PROPER MATERIAL. 7141 S STATE ST COMPLAINT PASSED View
INTERIOR FINISH FIRERESISTANCE REMOVE ALL UNRATED UNAPPROVED CARDBOARD BLANKETING INTERIOR CEILING - DANGEROUS CONDITION. 7141 S STATE ST COMPLAINT PASSED View
PLANS & PERMITS REQ - CONTRCTR RAISED PLATFORM IN THE STORE CASH REGISTER AREA BOTH NOT CONSTRUCTED WITH THE PROPER PLANS OR PERMITS. REAR DOOR IS BELOW THE REQUIRED MINIMUM OF 36". A LICENSED MASON CONTRACTOR IS REQUIRED. 7141 S STATE ST COMPLAINT PASSED View
OBSTRUCTIONS IN EXIT WAY REAR DOOR MARKED EXIT LOCKED WITH STEEL BARS AND PADLOCKS. REMOVE THESE OBSTRUCTIONS, FIRE HAZARDS. 7141 S STATE ST COMPLAINT PASSED View
UNSANITARY CONDITIONS-ANIMALS UNSANITARY CONDITIONS THROUGHOUT STORE FLY CATCHING LIGHTS IN MULTIPLE LOCATIONS OVER THE FOOD PREP AREAS AND VARIOUS OTHER WALLS THROUGHOUT. ROTTING FOOD, AN EXTERIOR METAL DOWNSPOUT RUNS THROUGH A FOOD COOLER. 7141 S STATE ST COMPLAINT PASSED View
MICE/RODENTS RODENT INFESTATION THROUGHOUT STORE. MICE TRAPS AND LIVE MICE NOTICED DURING INSPECTION. 7141 S STATE ST COMPLAINT PASSED View
RMV PLBFIX INSTALLD W/0 PERMIT NO PERMIT TO INSTALL THREE COMPARTMENT SINK AND HAND SINK NORTH ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
REPLACE DEFECTIVE FAUCET THREE COMPARTMENT SINK FAUCET NORTH ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
SUPPLY HOT WTR MIN TEMP 120DEG THREE COMPARTMENT SINK, HAND SINK AND LAVATORY NORTH ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
PRV BALLCOCK,VB,OR AIR GAP HOSE BIB BY MEAT COUNTER NORTHEAST ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
PRV BALLCOCK,VB,OR AIR GAP HOSE BIB BY VEGGIE COUNTER SOUTHWEST ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
PROVIDE PROVIDE FLOOR DRAIN FOR CONDENSATE WATER FROM COOLER SOUTHWEST ELEVATION. (18-29-402.5) 7141 S STATE ST COMPLAINT PASSED View
REMOVE STAGNANT WATER BSMT STANDING WATER IN FRONT OF COOLER CREATING A DANGEROUS CONDITION SOUTHWEST ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
SEE INSPECTOR COMMENTS REMOVE ALL UNAPPROVED CONNECTIONS TO FLUORESCENT LIGHT FIXTURES IN CEILING. INSTALL A JUNCTION BOX TO TO FEED A MINIMUM OF 2 LIGHT FIXTURES. REMOVE ALL DAISY CHAIN CONNECTIONS. (18-27-110.12L) 7141 S STATE ST COMPLAINT PASSED View
REMOVE ALL UNAPPROVED JUNCTION BOXES AND FITTINGS INSIDE WALK IN COOLER AND WALK IN FREEZER. INSTALL COMPRESSION FITTINGS AND WEATHERPROOF LIGHT FIXTURES AND BOXES, INCLUDING BOXES AT FRONT EXTERIOR OF BUILDING. DANGEROUS CONDITION. (18-27-300.4) 7141 S STATE ST COMPLAINT PASSED View
SYSTEM III INSTALL EMERGENCY LIGHTING SYSTEM III WITH CHICAGO APPROVED EXIT SIGNS AND BATTERY PACKS - DANGEROUS CONDITION. 7141 S STATE ST COMPLAINT PASSED View
UNAPPROVED CORDS REMOVE ALL UNAPPROVED EXTENSION CORDS AND POWER STRIPS BEHIND REGISTER AREA AND INSTALL ADDITIONAL OUTLETS TO AVOID USE OF CORDS - DANGEROUS CONDITION. 7141 S STATE ST COMPLAINT PASSED View
EXPOSED WIRING REMOVE EXPOSED WIRING AT LIGHT FIXTURES BEHIND REGISTER AREA IN CEILING. EXPOSED WIRES IN CONTACT WITH CARDBOARD - DANGEROUS CONDITION. 7141 S STATE ST COMPLAINT PASSED View
(13-12-360) PROVIDE PERMIT TO CORRECT VIOLATIONS. 7141 S STATE ST COMPLAINT PASSED View
INSUFFICIENT MEANS OF EGRESS REAR DOOR MARKED EXIT 32" UNDER THE REQUIRED 36". REMOVE AND REPLACE FIRE HAZARD. 7141 S STATE ST COMPLAINT PASSED View
PROVIDE DIELECTRIC UNIONS WATER HEATER SOUTHEAST ELEVATION. (18-29-605.2.1.1) 7141 S STATE ST COMPLAINT PASSED View
PROVIDE SAFE PAN FOR WATER HEATER SOUTH ELEVATION. (18-29-504.8) 7141 S STATE ST COMPLAINT PASSED View
REMOVE STOCK BY WATER HEATER SOUTH ELEVATION. (18-29-501.4) 7141 S STATE ST COMPLAINT PASSED View
REMOVE REMOVE ALL GAS POWERED APPLIANCES FROM THE INTERIOR OF THE STORE. (7-28-080) 7141 S STATE ST COMPLAINT PASSED View
PROPER MATRL WATER SUPPLY PIPE REMOVE FLEXIBLE SUPPLIES TO LAVATORY AND TOILET NORTH EAST ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
REPAIR OR REPLACE AISLE RESTRICTIONS WITHIN THE FRONT OF THE STORE 25", 30", AND 32" AISLES BEING OBSTRUCTED BY ATM MACHINE, STORE STOCK AND OTHER ITEMS. REMOVE TO ALLOW FOR CLEAR PATH OF FIRST RESPONDERS OR CUSTOMERS. DANGEROUS CONDITION. (13-160-050, 13-160-070) 7141 S STATE ST COMPLAINT PASSED View
DEFECTIVE FIXTURES REPLACE DEFECTIVE AND VANDALIZED LIGHT FIXTURES ON EXTERIOR UNDER CANOPY - DANGEROUS CONDITION. 7141 S STATE ST COMPLAINT PASSED View
PROVIDE FLOOR DRAIN FOR WATER HEATER SOUTH ELEVATION. (18-29-412.4) 7141 S STATE ST COMPLAINT PASSED View
PROVIDE RPZ ON WATER COOLED ICE MAKER EAST ELEVATION. (18-29-608.13.2) 7141 S STATE ST COMPLAINT PASSED View
ARRANGE PREMISE INSPECTION EXPOSE PLUMBING FOR THREE COMPARTMENT SINK AND HAND SINK NORTH ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
CLOSE BOX OPENINGS INSTALL FILLERS TO ALL ELECTRICAL PANELS. 7141 S STATE ST COMPLAINT PASSED View
OBTN PERMIT FOR PLUMBING WORK PERMIT FOR VIOLATIONS. 7141 S STATE ST COMPLAINT PASSED View
STOP LEAKING WATER THREE COMPARTMENT SINK DRAINS LEAK NORTH ELEVATION. 7141 S STATE ST COMPLAINT PASSED View
PROVIDE LAUNDRY TUB OR MOP SINK. (18-29-403.1) 7141 S STATE ST COMPLAINT PASSED View