Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-21 @ 1:08 PM
PIN: 20224060410000
Property Address: 6700 S COTTAGE GROVE AVE
City - Zip: CHICAGO - 60637
2023 Property Class: 523
2023 Township: 70 - Hyde Park
2023 Neighborhood: 70030
2023 Tax District: 70136
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 40 Violations
Violation Inspector Comments Address Category Status View
OBTAIN PERMIT FOR PLUMBING OBTAIN PERMIT BEFORE CONSTRUCTING, ALTERING OR USING PLUMBING SYSTEM. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS. (13-12-360) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE GAS STATION PLATFORM AT CASHIER, FIRE RATING UNKNOWN. (15-8-570) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
ENGAG LIC & BOND PLMBNG CNTRC ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
CARB MONOX DETECT IN RESID MISSING CARBON MONOXIDE DETECTOR. (DANGEROUS AND HAZARDOUS) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE AISLES RESTRICTION DUE TO EXCESSIVE STORAGE: 27", 24", 20". (DANGEROUS AND HAZARDOUS) (15-4-880) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
SUPPORT FIXTURES IN STORE AREA LIGHT FIXTURES ARE MISSING CORD GRIPS TO SUPPORT LIGHT FIXTURES AND IN GARAGE AREA THERE ARE LIGHT FIXTURES NOT SUPPORTED PROPERLY. (DANGEROUS AND HAZARDOUS CONDITION) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE GFCI PROTECTION FOR ALL GARAGE RECEPTACLES THROUGHOUT ALL GARAGE AREAS. (14E-5-511.12) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE A WATER MAIN GROUND CONDUIT AND CONDUCTOR TO WITHIN 5 FT. OF WATER METER OR VALVE. (14E-2-250.68(C1)) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
DEBRIS, EXCESSIVE REAR EXCESSIVE DEBRIS - FIRE HAZARD. (DANGEROUS AND HAZARDOUS) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE PROPER TYPE FIXTURES FOR FIX LIGHTING IN GARAGE AREAS WITH CAR LIFTS. (14E-5-511.7) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PROVIDE INDIRECT WASTE CONNECT NO BACKFLOW PREVENTER TO WATER SUPPLIES AT ICE MACHINE LOCATED IN GARAGE AREA AND COFFEE MACHINE IN GAS STATION. DANGEROUS AND HAZARDOUS WATER CROSS CONTAMINATION. (18-29-802) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG FIRE EXTINGHUISHERS OUTDATED TAGS. (DANGEROUS AND HAZARDOUS) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAYS PROVIDE GROUND CONTINUITY FOR CONDUIT APART AT FITTING AT GARAGE SOUTH BAY CEILING AREA AND AT LIFT STATIONS WITH BARE WIRES TO LIFT CONTROLS AND BARE WIRES IN CEILING AREA WHERE ARMORED CABLE IS LOCATED. (DANGEROUS AND HAZARDOUS CONDITION) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
DWELLING CLEAN AND SANITARY REMOVE EXCESSIVE STORAGE FROM MOTOR VEHICLE REPAIR SHOP. FOOD PRODUCTS ON FLOOR. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
GRADE AND DRAIN LOT PARKING LOT UNEVEN AND BROKEN PAVEMENT. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
FIRE EXTNGSHR REQ, RESDNTL FIRE EXTINGUISHERS NOT INSTALLED PROPERLY. FIRE EXTINGUISHERS SITTING ON FLOOR. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
ALL ELECTRICAL EQUIPMENT, CONDUIT, BOXES, WIRING SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER THROUGHOUT GARAGE AREA. (14E-1-110.12) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
INSTALL COVERS PROVIDE PROPER TYPE COVERS FOR OPEN JUNCTION BOXES WITH EXPOSED WIRING AT STORE PANEL AREA AND IN GARAGE AREA BY AIR COMPRESSOR, CEILING AREAS. (DANGEROUS AND HAZARDOUS CONDITION) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
ADD RECEPTACLES ADD RECEPTACLES TO EASE EXTENSION CORD USE THROUGHOUT THE STORE AND GARAGE AREA. (DANGEROUS AND HAZARDOUS CONDITION) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION IN WALK-IN COOLER AREA NEED WEATHERPROOF BOXES, LIGHTS, FITTINGS AND APPROVED RACEWAYS. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
INSPECT CONSTRUCTION WORK FAILED TO GET ROUGH AND FINAL INSPECTIONS. UNABLE TO VERIFY PERMITTED WORK. STORE AND MOTOR VEHICLE REPAIR SHOP HAS ALTERATIONS. (13-12-100) STRUCTURAL REPAIR AND ALTERATIONS MUST BE INCLUDED IN PLANS. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
VENT SYSTEM TO PRVNT BACK PRES UNAPPROVED S-TRAP AT HAND SINK IN REAR KITCHEN AREA OF GAS STATION. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
A BUILDING SHALL BE FED THROUGH ONLY ONE SET OF SERVICE CONDUCTORS. (14E-2-230.2) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
REPAIR/REPLACE SMOKE DETECTORS SMOKE DETECTOR LOW BATTERY INDICATOR CHIRPING. (DANGEROUS AND HAZARDOUS) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
WORKING SPACE PROVIDE PROPER CLEARANCES FOR ALL ELECTRICAL PANELS AND DISCONNECTS THROUGHOUT THE STORE AND GARAGE AREA. (DANGEROUS AND HAZARDOUS) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
MIXED OCCUPANCY SEPARATION PROVIDE EVIDENCE OF FIRE SEPARATION BETWEEN MOTOR VEHICLE REPAIR SHOP AND GAS STATION. REQUIRED SEPARATION BETWEEN MERCANTILE AND MVR 3 HOUR SEPARATION. SHOULD REFLECT ON PLANS. DOOR MISSING LABEL AND CLOSURE, AND UNKNOWN CINDER BLOCK WIDTH AND FILL. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
APPLIANCE INSIGHT DISCONNECT PROVIDE DISCONNECTS FOR ALL LIFT STATION AREAS. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
STRUCTURAL MEMBER, PIER BLOCK CANOPY OVER PUMPS SECTIONS OF EAVE/TRIM ON OUTER SECTIONS HAVE BEEN PULLED AWAY AND PARTIALLY DISCONNECTED AT THE NORTH AND WEST ELEVATIONS OF CANOPY. PERMIT REQUIRED. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
SECURE RACEWAY PROPERLY SUPPORT ALL CONDUIT RUNS THROUGHOUT THE GARAGE AREA AND STORE AREA. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
REPAIR OR REPLACE PROVIDE ORIGINAL PLANS AND PERMIT. EVIDENCE OF REMODEL AND OR ADDITION TO BUILDING. FIRE SEPARATION NOT VERIFIED BETWEEN GAS STATION AND REPAIR SHOP. INSTALLATION OF LOFT AREA IN GAS STATION. NO REAR EXIT IN GAS STATION. RAISED PLATFORM AT CASHIER. CINDER BLOCK ADDITION AT REAR ROOF WITH EXPOSED ROOF JOIST. (13-12-050) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
NO PLASTIC EM LIGHTS AND EXIT SIGNS APPROVED FOR USE - ONLY METAL TYPE. (14E-7-700.66(C3)) 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
DEBRIS, EXCESSIVE WEST SERVICE AREA - DISCARDED SHELF PARTS, PILE OF TREE LIMBS AND JUNK ACCUMULATION. 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
REPAIR/REPLACE SMOKE DETECTORS SMOKE DETECTORS INOPERABLE 6700 S COTTAGE GROVE AVE COMPLAINT CLOSED View
PERMIT REQUIRED - CONTRACTOR PERMIT REQUIRED FOR PROJECTION OVER PUBLIC WAY 6700 S COTTAGE GROVE AVE COMPLAINT CLOSED View
FIRE EXTNGSHR RECHARGE & TAG RETAG AND HANG FIRE EXTINGUISHERS 6700 S COTTAGE GROVE AVE COMPLAINT CLOSED View
MAINTAIN PROJECTIONS WOOD AWNING ATTACHED TO PARAPET WALLS PULLING AWAY FROM BUILDING 6700 S COTTAGE GROVE AVE COMPLAINT CLOSED View
REMOVE AND REPLACE***** REPAIR OR REPLACE BROKEN POLE SIGN.13-20-530.SIGN READS,"PAY AT THE PUMP". 6700 S COTTAGE GROVE AVE COMPLAINT FAILED View
PRV HIGH SIDE FOR ONE COPELAND 2 HP. COMPRESSOR LOCATED ON ROOF . 6" X 12" RECEIVER. SERVING WALK - IN COOLER. 6700 S COTTAGE GROVE AVE PERIODIC FAILED View
PRV HIGH SIDE FOR ONE COPELAND 2 HP. COMPRESSOR LOCATED ON ROOF . 6" X 12" RECEIVER. SERVING WALK - IN COOLER. 6700 S COTTAGE GROVE AVE PERIODIC PASSED View