Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR #1: REPLACE/REPAIR ALARM BELL | 6565 S YALE AVE | PERIODIC | FAILED | View |
IDENTIFY ELEV POWER LINE DISC | BOTH: PROVIDE DISCONNECT SOURCE FEED LABELS ON MAIN LINE AND 110V DISCONNECTS | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH: CAT1 TEST HAVE EXPIRED AS OF 08/27/2020 | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #2 ELEVATOR: MAKE NEEDED REPAIRS AND RETURN TO SERVICE | 6565 S YALE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | PROGRAM EMERGENCY TELEPHONE TO 24HR ANSWERING SOURCE ON ELEVATORS #1 & #2 | 6565 S YALE AVE | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RETURN EMERGENCY PHONES TO PROPER WORKING ORDER. | 6565 S YALE AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING ¿ NO RESPONSE TO CHECK DETECTOR AND CONDITIONS | 6565 S YALE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAKE ALARM BELL OPERATIONAL. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM ANNUAL PRESSURE TEST AS PER CITY CODE. #136271 | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: RESTRICTOR HAS BEEN DISABLED/REMOVED | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: FIRE SERVICE HOLD FEATURE NOT OPERABLE. ALSO, ONCE PHASE I HAS BEEN TURNED OFF WITH PHASE II ON IN SINGLE ELEVATOR, PHASE I IS NOT RESETTING SERVICE TO NORMAL OPERATION | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PREVIOUS VIOLATION: BOTH ELEVATORS: PROVIDE CODE COMPLIANT PIT LADDERS | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: PROVIDE IN-CAR ELEVATOR IDENTIFICATION ON C.O.P. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PREVIOUS VIOLATION: BOTH ELEVATORS: CORRECT EMERGENCY PHONE ISSUE - MUST WORK WITH THE LOSS OF 110V POWER. PROGRAM TO REPEAT LOCATION TWICE TO 24 HOUR SERVICE PROVIDER | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: PROVIDE CODE COMPLIANT PIT LADDERS | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH ELEVATORS: CORRECT EMERGENCY PHONE ISSUE - MUST WORK WITH THE LOSS OF 110V POWER. PROGRAM TO REPEAT LOCATION TWICE TO 24 HOUR SERVICE PROVIDER | 6565 S YALE AVE | PERIODIC | FAILED | View |
REPAIR CORNICE | NORTHWEST; SOUTHWEST AND SOUTHEAST STONE CORNICE - WASHED OUT MORTAR. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | BUILDING / FIRE EXTINGUISHERS - EXPIRED TAGS ( 2018 ). | 6565 S YALE AVE | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | 6 FLOOR EAST STAIRWAY DOOR DOES NOT LATCH. 3RD, 4TH, AND 7TH FLOORS / TRASH CHUTE DOORS - DO NOT LATCH. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
STOP STORING GARBAGE | WEST STAIRWAY AT GRADE - STORING OLD CARPETING. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
ROACHES | MOST APARTMENTS, INCLUDING 103, 306, 307 AND 308 - ROACHES INFESTATION. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | NO VISIBLE CAT 1 (ANNUAL) TESTING TAG | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | HOISTWAY FACIA NEEDS TO BE SECURED ON CAR #1. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | GUIDE ROLLER NEEDS ON CAR #1 NEEDS TO BE REPAIRED OR REPLACED. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SIGNALING ALARM BELL NOT FUNCTIONING PROPERLY. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | 110 V BATTERY BACK UP NOT FUNCTIONING PROPERLY | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | FIRE EXTINGUISHER IN MACHINE ROOM OUT OF DATE. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SIGNAGE NEEDED FOR THE MACHINE ROOM DOOR | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | TWO-WAY COMMUNICATION ANNOUNCEMENT ON CAR #2 NOT COMPLETE. IT MUST HAVE THE COMPLETE ADDRESS FOR DISPATCH. | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CAR DESIGNATION NEEDED FOR EACH CAR, ON EACH FLOOR. | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SIGNALING ALARM BELL NOT FUNCTIONING PROPERLY.CAR #1 | 6565 S YALE AVE | PERIODIC | FAILED | View |
PARAPET | SOUTHWEST CORNER - PARAPET WALL - LOOSE AND MISSING BRICKS AND STONES, WITH MASONRY SECTION WASHED OUT MORTAR; HOLE IN WALL SECTION AT CORNER. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | ALL FLOORS - ELECTICAL CLOSETS - WALLS, FLOORS AND CEILING - PIPE, CONDUIT AND CABLE PENETRATION HOLES SEALED WITH EXPANDABLE SPRAY FOAMS. SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE-RATED CAULK FILLED WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
INSECTS | MOST APARTMENTS, INCLUDING 302, 304 AND 409 - BEDBUGS INFESTATIONS THROUGHOUT. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION | 6565 S YALE AVE | COMPLAINT | FAILED | View |
ROACHES | MOST APARTMENTS, INCLUDING 103, 306, 307 AND 308 - ROACHES INFESTATION. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
REPAIR FLOOR | 406 - KITCHEN FLOOR TILES - CRACKED AND BROKEN. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
DWELLING CLEAN AND SANITARY | 409 - CARPETING FILTHY AND UNSANITARY. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | 406 - EXCESSIVE ACCUMULATION OF PAPERS, GARBAGE, JUNK AND DEBRIS. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
COVER OUTLETS AND JBS | 7TH FLOOR / ELECTRIC CLOSET AND 5TH FLOOR / WEST STAIRWELL CEILINGS - OPEN JUNCTION BOXES. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
PROVIDE | EAST AND WEST STAIRWELLS - MISSING IDENTIFICATION AND DIRECTIONAL SIGNS AT EACH FLOOR ON INTERIOR STAIRWELL AND CORRIDOR SIDE OF STAIRS. (SECTION 13-76-075). | 6565 S YALE AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | WEST STAIRWELL - HOLES ON BLOCK WALL, NEAR CEILING. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
REMOVE | ALL FLOORS / EAST STAIRWELL - WOOD BOARDS USED ON SECTIONS OF THE FLOOR. REMOVE AND REPLACE WITH FIRE RESISTANT NON COMBUSTIBLE MATERIALS. PERMIT REQUIRED FOR REPLACEMENT. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | 5TH FLOOR / ELECTRIC CLOSET - SMOKE DETECTOR - SENSOR COVERED WITH PLASTIC. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE TOILET SEAT | 304 - TOILET - SEAT COVER BROKEN. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | MOST APARTMENTS, INCLUDING 505, 211, 309, 411, 501, 606, 703, 308, 209, 201, 401, 506, 509 AND 602 - NO RESPONSE - UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO VERIFY COMPLIANCE TO PREVIOUS VIOLATIONS - SEE INSPECTION #11650991, WRITTEN ON 08/18/2015. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
PARAPET | SOUTHWEST CORNER - PARAPET WALL - LOOSE AND MISSING BRICKS AND STONES, WITH MASONRY SECTION WASHED OUT MORTAR; HOLE IN WALL SECTION AT CORNER. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
PIPE OPENING W/NONCOMBUST MATL | ALL FLOORS - ELECTICAL CLOSETS - WALLS, FLOORS AND CEILING - PIPE, CONDUIT AND CABLE PENETRATION HOLES SEALED WITH EXPANDABLE SPRAY FOAMS. SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE-RATED CAULK FILLED WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
INSECTS | MOST APARTMENTS, INCLUDING 302, 304 AND 409 - BEDBUGS INFESTATIONS THROUGHOUT. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REPAIR FLOOR | 406 - KITCHEN FLOOR TILES - CRACKED AND BROKEN. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
DWELLING CLEAN AND SANITARY | 409 - CARPETING FILTHY AND UNSANITARY. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
DEBRIS, EXCESSIVE | 406 - EXCESSIVE ACCUMULATION OF PAPERS, GARBAGE, JUNK AND DEBRIS. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
COVER OUTLETS AND JBS | 7TH FLOOR / ELECTRIC CLOSET AND 5TH FLOOR / WEST STAIRWELL CEILINGS - OPEN JUNCTION BOXES. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REPAIR DOOR HARDWARE | 7H FLOOR / ELECTRIC CLOSET DOOR - BROKEN KNOB AND MISSING SELF-CLOSER DEVICE. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
PROVIDE | EAST AND WEST STAIRWELLS - MISSING IDENTIFICATION AND DIRECTIONAL SIGNS AT EACH FLOOR ON INTERIOR STAIRWELL AND CORRIDOR SIDE OF STAIRS. (SECTION 13-76-075). | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REPAIR INTERIOR WALLS/CEILING | WEST STAIRWELL - HOLES ON BLOCK WALL, NEAR CEILING. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REMOVE | ALL FLOORS / EAST STAIRWELL - WOOD BOARDS USED ON SECTIONS OF THE FLOOR. REMOVE AND REPLACE WITH FIRE RESISTANT NON COMBUSTIBLE MATERIALS. PERMIT REQUIRED FOR REPLACEMENT. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REPAIR/REPLACE SMOKE DETECTORS | 5TH FLOOR / ELECTRIC CLOSET - SMOKE DETECTOR - SENSOR COVERED WITH PLASTIC. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | MOST APARTMENTS, INCLUDING 505, 211, 309, 411, 501, 606, 703, 308, 209, 201, 401, 506, 509 AND 602 - NO RESPONSE - UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO VERIFY COMPLIANCE TO PREVIOUS VIOLATIONS - SEE INSPECTION #11650991, WRITTEN ON 08/18/2015. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PREVIOUS VIOLATION: BOTH ELEVATORS - RESTRICTOR HAS BEEN DISABLED/REMOVED | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PREVIOUS VIOLATION: BOTH ELEVATORS: FIRE SERVICE HOLD FEATURE NOT OPERABLE. ALSO, ONCE PHASE I HAS BEEN TURNED OFF WITH PHASE II ON IN SINGLE ELEVATOR, PHASE I IS NOT RESETTING SERVICE TO NORMAL OPERATION | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BOTH: POST CURRENT CERTIFICATE | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #1 ELEVATOR: REPAIR HANDLE FOR EMERGENCY PHONE DOOR | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR/UPGRADE FIRE SERVICE PHASE II OPERATION TO MEET CITY OF CHICAGO 2017 PHASE II MANDATE. ELEVATOR 2 DOES NOT OPERATE ON PHASE II. PERMIT REQUIRED FOR CITY OF CHICAGO 2017 PHASE II MANDATE/ALTERATIONS TO CONTROLLER. | 6565 S YALE AVE | PERIODIC | FAILED | View |
REPLACE DEFECTIVE TOILET SEAT | 304 - TOILET - SEAT COVER BROKEN. | 6565 S YALE AVE | COMPLAINT | PASSED | View |
REPAIR DOOR HARDWARE | 7H FLOOR / ELECTRIC CLOSET DOOR - BROKEN KNOB AND MISSING SELF-CLOSER DEVICE. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 7TH FLOOR STAIRS SIGN BY UNIT 703 - NOT ILLUMINATED. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CATEGORY 1 TEST PAST DUE. PROVIDE DOCUMENTATION. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CURRENT FIRE SERVICE TEST LOGS. BOTH ELEVATORS. | 6565 S YALE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CURRENT FIRE SERVICE TEST LOGS. BOTH ELEVATORS. | 6565 S YALE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CATEGORY 1 TEST DUE. BOTH UNITS. | 6565 S YALE AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | SOUTHWEST CORNER 1ST FLOOR - VERTICAL CRACK. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE, UNABLE TO VEFY DETECTORS. | 6565 S YALE AVE | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 7TH FLOOR STAIRS SIGN BY UNIT 703 - NOT ILLUMINATED. | 6565 S YALE AVE | COMPLAINT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR/UPGRADE FIRE SERVICE PHASE II OPERATION TO MEET CITY OF CHICAGO 2017 PHASE II MANDATE. ELEVATOR 2 DOES NOT OPERATE ON PHASE II. PERMIT REQUIRED FOR CITY OF CHICAGO 2017 PHASE II MANDATE/ALTERATIONS TO CONTROLLER. | 6565 S YALE AVE | PERIODIC | PASSED | View |