Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | INSTALL LISTED HANDLE TIES WHERE REQUIRED.14E-2-210.4(B) | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION FOR DISHWASHER.14E-2-210.8(D) | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | USE TAMPER RESISTANT RECEPTACLES WHERE REQUIRED.14E-4-406.12 | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL PANEL SCHEDULES.14E-1-110.22(B) | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE REQUIRED GFCI PROTECTED OUTLET ON KITCHEN PENINSULA.14E-2-210.52 | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL SELF GROUNDING RECEPTACLES OR EGC FROM RECEPTACLE TO BOX.14E-2-250.146 | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE APPROVED WALL SWITCH CONTROLLED LIGHTING OUTLET WHERE REQUIRED.14E-2-210.70 IN FULL | 5152 S MAYFIELD AVE | PERMIT | PASSED | View |