Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS FOR STADIUM, POOL, LIBRARY, BALCONY, STAFF, MEETING ROOM FIRST FLOOR. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | FRACTURED AND SPALLING CONCRETE STAIRS (D&H) - UNEVEN RISERS. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | FRACTURED AND SPALLING CONCRETE AT VARIOUS LOCATIONS WITH EXPOSED REBAR. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | SOUTH ELEVATION WEST GRAND STAND - MISSING GUARD -RAILS AT BASEMENT STAIRWELL. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PROVIDE STRUCTURAL ENGINEERS STATEMENT FOR STAIRS, EXTERIOR WALLS, AND SHORING UNDER STAIRS AT EAST AND WEST GRANDSTAND. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
TEST G & S PASS ELE | FULL LOAD/CONTRACT SPEED 5 YEAR TEST. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | ANNUAL RELIEF PRESSURE TEST AND TAG VALUE. (CHAPTER 18-30 OF THE CITY OF CHICAGO BUILDING CODE AND ASME 17.1 1996) (18-30-010,13-20-120) EV000078 | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | #1 SELLARS 83 FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #2 SELLARS 83 FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #3 WILLIAMS & DAVIS 74 SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS FOR POOL, LIBRARY RM, 200, LIBRARY BALCONY, 1ST FLOOR STAFF MEETING ROOM AND TEACHER'S LOUNGE | 2501 W ADDISON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARD WITH DIAGRAM FOR STADIUM SEATING | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | FRACTURED AND SPALLING CONCRETE STAIRS WITH UNEVEN RISERS (D & H) | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | FRACTURED AND SPALLING CONCRETE AT VARIOUS LOCATIONS WITH EXPOSED REBAR-ALL WALLS | 2501 W ADDISON ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | SOUTH ELEVATION, WEST GRAND STANDS: MISSING GUARD RAILS AT BASEMENT STAIRWELL | 2501 W ADDISON ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PROVIDE STRUCTURAL ENGINEER'S STATEMENT FOR STAIRS, EXTERIOR WALLS, AND SHORING UNDER STAIRS AND EAST AND WEST GRAND STANDS; PLANS AND PERMITS | 2501 W ADDISON ST | PERIODIC | FAILED | View |
UNINTERRUPTED EXIT AT GRADE | WEST ELEVATION EXIT AISLE-ONLY 32" CLEARANCE AT FIELD LIGHT POLE FOUNDATION | 2501 W ADDISON ST | PERIODIC | FAILED | View |
INTERNAL | #4 WILLIAM DAVIS 74 SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | #2 SELLERS 83 FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | #1 SELLERS 83 FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #2 SELLERS 83 FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #3 WILLIAM & DAVIS 74 SM #4416. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | #3 WILLIAM DAVIS 74 SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #5 WILLIAM DAVIS 74 SM #4384. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS W/DIAGRAMS FOR POOL, LIBRARY, RM 200, LIBRARY BALCONY, 1ST FLR STAFF MEETING RM, GYM 1 BALCONY, SOUTH AND TEACHERS LOUNGE. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 04/13/10. STICKER LEFT ON DOOR. NO ONE CONTACTED DEPARTMENT OF BUILDINGS TO ALLOW ACCESS. TO ARRANGE INSPECTION OF PREMISES PLEASE CALL (312) 743 - 3538. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | APPLY FOR NEW OCCUPANCY CARD FOR POL DECK/BLEACHERS & LIBRARY (MAIN FLOOR). DISPLAY BOTH OCCUPANCY DRAWING AND OCCUPANCY CARD. APPLY FOR DUPLICATE OR NEW OCCUPANCY CARD FOR GYMNASIUM 1 BALCONY SOUTH. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
INT WALL/CEILING PEELING PAINT | INTERIOR 3RD FLOOR ROOM 355 COMPUTER ROOM SEVERE WATER DAMAGE WALLS AND CEILING. | 2501 W ADDISON ST | COMPLAINT | FAILED | View |
MAINTAIN WINDOW | INTERIOR 3RD FLOOR ROOM 355 COMPUTER ROOM INTERIOR WOOD WINDOW FRAME/ AND SILLS ROTTED. | 2501 W ADDISON ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SIDEWALK LIFT REMOVE WATER FROM PIT. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SIDEWALK LIFT REPAIR ALARM BELL. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
MAINT STAGE/ORCH LIFT | AUDITORIUM WHEELCHAIR LIFT, PROGRAM EMERGENCY PHONE. EV000078 | 2501 W ADDISON ST | PERIODIC | FAILED | View |
DEFECTIVE SAFETY VALVE-BOILER | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | WMS SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
REPAIR | WMS SM #4415-DETERIORATING REFRACTORY ON BACK DOOR. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | SELLERS NB# 5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY PLACARDS FOR GYM #2 , LIBRARY, AND POOL | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | CLOSED | View | |
INTERNAL | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | WMS SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | CLOSED | View | |
REPAIR | WMS SM #4415- REFRACTORY AND STAY BARS IN BACK OF FIRE CHAMBER. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
REPAIR | WMS SM #4415 FRONT DOOR INSULATION. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS WITH DIAGRAMS FOR POOL,ROOM 200 LIBRARY, LIBRARY BALCONY, 1ST FLOOR STAFF MEETING ROOM, GYM #1 BALCONY SOUTH. OBTAIN NEW OCCUPANCY CARD FOR AUDITORIUM- DO NOT INCLUDE STAGE IN OCCUPANCY NUMBER | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 04/13/2010,12/01/2011 AND 12/21/2012. STICKER LEFT ON DOOR. NO ONE CONTACTED DEPT. OF BUILDINGS TO ALLOW ACCESS. TO ARRANGE INSPECTION PLEASE CALL 312-743-3610. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | CLOSED | View | |
LEAKING BOILER TUBES | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
MAINTAIN EXIT SIGN ILLUMINATED | REPAIR EXIT SIGNS NOT ILLUMINATED THROUGHOUT BUILDING. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | REPAIR MALFUNCTIONING GENERAL ILLUMINATION AT ALL STAIRWELLS. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | EXIT DOORS AT GYM AND AUDITORIUM OBSTRUCTED. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR DOOR HARDWARE | REPAIR OR REPLACE BROKEN AND MISSING DOOR HARDWARE AT: SECOND FLOOR AUDITORIUM REAR DOOR CLOSER; BOY'S LOCKER ROOM WEST DOOR MISSING PANIC HARDWARE; SECOND FLOOR GYM DOOR CLOSER NOT WORKING; FIRST FLOOR DOOR CLOSER MISSING. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | REPLACE BROKEN AND MISSING PANES AT THIRD FLOOR GYM AND FIRST FLOOR EXIT DOORS B AND C. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR WATER DAMAGED WALLS AND CEILINGS THROUGHOUT BASEMENT. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR | WMS SM #4416- REFRACTORY AND STAY BARS IN BACK OF FIRE CHAMBER. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
REPAIR | WMS SM #4415-REFRACTORY ON BACK FIRE DOOR. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS SM# 4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | ON SELLERS NB# 5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | ON WMS NB# 4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
REPAIR | WMS SM #4416-REAR FIRE DOOR AND ACCESS FIRE MANHOLE. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
LEAKING BOILER TUBES | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE SIGNAGE ON MACHINE ROOM DOOR | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERMENANTLY MOUNT FIRE EXTINGUSHER IN MACHINE ROOM | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE P.I. SCREEN BY HALL STATION | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE BRAILLE PLATES ON ALL HOISTWAY ENTRANCES | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | IDENTIFY/ STENCIL ALL ELEVATOR EQUIPMENT IN MACHINE ROOMS | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CAR NUMBERS ON ALL HOISTWAY ENTRANCES | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE TRI-PICTOGRAPHS AT ALL HALL STATIONS | 2501 W ADDISON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | DO NOT USE LULA WASNT ABLE TO PERFORM ACCEPTANCCE TESTING | 2501 W ADDISON ST | PERMIT | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | ENDS OF ALL WALL MOUNTED HANDRAILS MUST RETURN TO WALL. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHER RECHARGE TAGS EXPIRED. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR WATER DAMAGED DRYWALL AT ROOMS UNDER THE BLEACHERS. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REPAIR LOOSE SECTION OF CONCRETE AT SIDE WALL IN NORTHWEST STAIRWELL. DANGEROUS AND HAZARDOUS CONDITION. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | REPAIR ALL EXIT SIGNS NOT ILLUMINATED. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
INT WALL/CEILING CHIP PLASTER | REMOVE PEELING PAINT AT WALLS AND CEILINGS THROUGHOUT BASEMENT. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | REPLACE MISSING HANDRAILS ON SECOND FLOOR AT GYM #2 AND THIRD FLOOR GYM IN NORTH STAIRWELL. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
INTERNAL | WMS SM #4415. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
ADJUST BOILER BURNER | #3 WILLIAMS & DAVIS 74 SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
SEAL CRACKED BRICKWORK | #3 WILLIAMS & DAVIS 74 SM #4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
SEAL CRACKED BRICKWORK | #4 WILLIAMS & DAVIS 74 SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | CLOSED | View | |
INTERNAL | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | SEL FT #5751. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | WMS SM #4416. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | #1 SELLERS 83 FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
DEFECTIVE SAFETY VALVE-BOILER | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
POST APPROVED OCCUPANCY CARD | OCCUPANCY CARDS NOT POSTED. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR WATER DAMAGED WALLS AND CEILINGS AT WEST TOILET ROOMS. DRYWALL DAMAGED AND MOLD COVERED. WOOD PALLETS PLACED ON FLOOR DUE TO STANDING WATER. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OCCUPANCY CARDS NOT POSTED. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | SELLERS NB# 5750. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS NB# 4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
REPAIR DEFECTIVE FOUNDATION | AUDITORIUM BASEMENT SOUTHEAST WALL--WATER SEEPAGE AFTER RAIN ENTERS BASEMENT CORRIDOR. DAMAGE TO INTERIOR WALLS 30 INCHES ABOVE FLOOR. MOLD PRESENT ON FOUNDATION WALL. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR DOOR HARDWARE | GYM #1 2ND FLOOR WEST DOOR WON'T LATCH | 2501 W ADDISON ST | PERIODIC | FAILED | View |
INT WALL/CEILING CHIP PLASTER | AUDITORIUM - NORTHEAST ABOVE WINDOW AT BALCONY - LOOSE WATER DAMAGED PLASTER | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | GYM #3 WEST WALLAT SOUTH BASKETBALL NET, WALL MOUNT - LOOSE SHIFTED BRICKS. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | DOOR HARDWARE WON'T LATCH AT GYM 1 AND SECOND FLOOR WEST DOOR. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
LEAKING BOILER TUBES | SEL FT #5750. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | ANNUAL GOVERNOR AND SAFETY TEST REQUIRED TAG GOVERNOR. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
REMOVE | BOILER JACKET IN REAR INSPECT PLATE FOR EXCESSIVE HEAT #4 WMS 74 SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | #4 WILLIAM & DAVIS 74 SM #4415. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OPEN | 2501 W ADDISON ST | PERMIT | PASSED | View | |
OPEN TYPE VIOLATION | FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 12-1-11, 4-13-10 2011.STICKER LEFT ON DOOR. NO ONE CONTACTED DEPT. OF BUILDINGS TO ALLOW ACCESS. PLEASE CALL 312.743.3610 TO ARRANGE FOR INSPECTION | 2501 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SIDEWALF LIFT PERFORM CATEGORY I TEST AND TAG UNIT. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR | WMS SM #4415 -LEAKING SAFETY VALVE FLANGE CONNECTIONS. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
REPAIR | WMS SM #4416-REFRACTORY ON BACK FIRE DOOR. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | SEL FT #5750 | 2501 W ADDISON ST | PERIODIC | PASSED | View |
INTERNAL | WMS SM# 4416. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
DEBRIS, EXCESSIVE | REMOVE JUNK AND DEBRIS THROUGHOUT BASEMENT. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ACCESS TO STADIUM FOR 2017 ANNUAL INSPECTION. ENGINEER SAID DOEXHO OR ARAMARK NOW OPERATES THE FACILITY. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR OR REPLACE | REPLACE BROKEN FURNACES AT STADIUM ROOMS. | 2501 W ADDISON ST | PERIODIC | FAILED | View |
REPAIR | WMS SM #4415-BURNER ASSEMBLY. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | PASSED | View | |
INTERNAL | ON SELLERS NB# 5751. | 2501 W ADDISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 2501 W ADDISON ST | PERIODIC | CLOSED | View | |
INTERNAL | #2 SEL 83 FT NB#5751 | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
REPAIR | #1 WHS 74 SM NB#4384:REPLACE CRACKED AND BROKEN REFRACTORY INSIDE THE BOILER. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
REPAIR | #1 WHS 74 SM NB#4384:REPAIR OR REPLACE LEAKING FEEDWATER LINE. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | #4 WMS 74 SM NB#4416 | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
DEFECTIVE SAFETY VALVE-BOILER | #1 WHS 74 SM NB#4384 | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
MAINTAIN | #WWHS 74 SM NB#4384: MAINTAIN PROPER CHEMICAL TREATMENT DUE TO EXCESSIVE SCALE. | 2501 W ADDISON ST | PERIODIC | CLOSED | View |
INTERNAL | #3 SEL 83 FT NB#5750 | 2501 W ADDISON ST | PERIODIC | CLOSED | View |