Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
NO PLASTIC TYPE ENCLOSURE APPROVED FOR BATTERY EMERGENCY LIGHTS OR EXIT SIGNS. 18-27-700.66-3 | 1501 W 47TH ST | COMPLAINT | FAILED | View | |
MINI BREAKERS NOT APPROVED FOR USE IN PANELS. 18-27-240.85 | 1501 W 47TH ST | COMPLAINT | FAILED | View | |
ARRANGE PREMISE INSPECTION | NO ENTRY TO INTERIOR OF BUILDING. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | MISSING OWNER POSTING. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | SOUTH WALL LOOSE/MISSING MORTAR. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REPAIR LINTELS | NORTH/EAST STEEL LINTELS IN NEED OF REPAIR. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | SUPPORT LIGHT FIXTURE AT THE EAST ELEVATION SOUTH DIRECTION OF BUILDING. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | PULL A PLUMBING PERMIT. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | BASEMENT MISSING SECTIONS OF PLASTER AND LATH. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
STRUCTURAL MEMBER, PIER BLOCK | EAST ELEVATION LINTEL OVER GLASS BLOCK SAGGING. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WATER PIPING | INSTALL AIR CHAMBERS ON HOT AND COLD WATER LINES TO (2) WASHERS AND (1) LAUNDRY SINK. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WASTE PIPING | RE-CONNECT WASTE PIPE FROM LAUNDRY TUB TO WASTE LINE. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
VENT 5' WITHIN TRAP | INSTALL A VENT LINE FOR LAUNDRY TUB WITHIN FIVE FEET OF TRAP. (18-29-102.3) CURRENTLY 7' FROM TRAP. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
INDIRECT CONN.FOR WATER SUPPLY | INSTALL APPROVED BACK FLOW PREVENTER ON THE COLD WATER SUPPLY LINE TO BOILER. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REMV SADDLE HUB CONNECTIONS | REMOVE SADDLE TYPE CONNECTION FOR WASTE PIPE FROM FIRST FLOOR WITH APPROVED CONNECTION TO SOIL PIPE. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | REMOVE BLACK PIPE AND FITTINGS USED FOR WASTE LINE FROM FIRST FLOOR SINK AND INSTALL APPROVED MATERIALS. FIRST FLOOR. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REMV RARELY USED FIXTURE | REMOVE ABANDONED FAUCET AND PIPING FROM BEHIND BAR. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | REMOVE (2)-2" RUBBER COUPLINGS USED FOR A WASTE TIE IN BEHIND BAR AND INSTALL APPROVED ADAPTERS AND MATERIALS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | REPLACE ALL FLEXIBLE SUPPLIES TO PLUMBING FIXTURES THROUGHOUT BUILDING. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
PROVIDE ADEQUATE SUPPORT | REHANG URINAL WATER PIPE WITH APPROVED MATERIALS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | PROVIDE OPEN FRONT TOILET SEATS FOR PUBLIC TOILETS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | HIRE A LICENSED PLUMBING CONTRACTOR. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
WORKING SPACE | REMOVE ALL DEBRIS FROM IN FRONT OF SERVICE DISCONNECT LOCATED IN BASEMENT AREA. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLES TO EASE EXTENSION CORD USE THROUGH OUT THE BAR COUNTER TOP AREAS, TV AND FOR LIGHTS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
PROVIDE A WATER MAIN GROUND CONDUCTOR, CONDUIT TO WITHIN 5' OF WATER METER OR VALVE. 18-27-250.50 | 1501 W 47TH ST | COMPLAINT | FAILED | View | |
SECURE RACEWAY | PROPERLY SUPPORT ALL LOW VOLTAGE WIRING THROUGHOUT ALL BASEMENT AREAS AND 1ST FLOOR BAR AREAS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
FROM DISCONNECT TO TAP BOX EXCEEDS 25' RULE. 18-27-240.21 B-2 | 1501 W 47TH ST | COMPLAINT | FAILED | View | |
NO PERMIT WIRING | OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS AND FOR PANELS INSTALLED WITH OUT PERMITS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WASTE PIPING | REMOVE PVC PIPE AND FITTINGS USED FOR (2) SUMP PUMPS DISCHARGE PIPING WITH APPROVED MATERIALS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |
INSTALL COVERS | PROVIDE PROPER TYPE BOXES, COVERS FOR EXPOSED WIRING AT COMPRESSORS LOCATED IN BASEMENT AREAS. DANGEROUS AND HAZARDOUS. | 1501 W 47TH ST | COMPLAINT | FAILED | View |