Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-22 @ 10:35 PM
PIN: 20081010110000
Property Address: 1501 W 47TH ST
City - Zip: CHICAGO - 60609
2023 Property Class: 212
2023 Township: 72 - Lake
2023 Neighborhood: 72051
2023 Tax District: 72094
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 30 Violations
Violation Inspector Comments Address Category Status View
NO PLASTIC TYPE ENCLOSURE APPROVED FOR BATTERY EMERGENCY LIGHTS OR EXIT SIGNS. 18-27-700.66-3 1501 W 47TH ST COMPLAINT FAILED View
MINI BREAKERS NOT APPROVED FOR USE IN PANELS. 18-27-240.85 1501 W 47TH ST COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION NO ENTRY TO INTERIOR OF BUILDING. 1501 W 47TH ST COMPLAINT FAILED View
POST OWNER/MANAGERS NAME/# MISSING OWNER POSTING. 1501 W 47TH ST COMPLAINT FAILED View
REPAIR EXTERIOR WALL SOUTH WALL LOOSE/MISSING MORTAR. 1501 W 47TH ST COMPLAINT FAILED View
REPAIR LINTELS NORTH/EAST STEEL LINTELS IN NEED OF REPAIR. 1501 W 47TH ST COMPLAINT FAILED View
SUPPORT FIXTURES SUPPORT LIGHT FIXTURE AT THE EAST ELEVATION SOUTH DIRECTION OF BUILDING. 1501 W 47TH ST COMPLAINT FAILED View
OBTN PERMIT FOR PLUMBING WORK PULL A PLUMBING PERMIT. 1501 W 47TH ST COMPLAINT FAILED View
1HR FLR OVER BSMT, 1 OR 2 DU BASEMENT MISSING SECTIONS OF PLASTER AND LATH. 1501 W 47TH ST COMPLAINT FAILED View
STRUCTURAL MEMBER, PIER BLOCK EAST ELEVATION LINTEL OVER GLASS BLOCK SAGGING. 1501 W 47TH ST COMPLAINT FAILED View
REPLACE DEFECTIVE WATER PIPING INSTALL AIR CHAMBERS ON HOT AND COLD WATER LINES TO (2) WASHERS AND (1) LAUNDRY SINK. 1501 W 47TH ST COMPLAINT FAILED View
REPLACE DEFECTIVE WASTE PIPING RE-CONNECT WASTE PIPE FROM LAUNDRY TUB TO WASTE LINE. 1501 W 47TH ST COMPLAINT FAILED View
VENT 5' WITHIN TRAP INSTALL A VENT LINE FOR LAUNDRY TUB WITHIN FIVE FEET OF TRAP. (18-29-102.3) CURRENTLY 7' FROM TRAP. 1501 W 47TH ST COMPLAINT FAILED View
INDIRECT CONN.FOR WATER SUPPLY INSTALL APPROVED BACK FLOW PREVENTER ON THE COLD WATER SUPPLY LINE TO BOILER. 1501 W 47TH ST COMPLAINT FAILED View
REMV SADDLE HUB CONNECTIONS REMOVE SADDLE TYPE CONNECTION FOR WASTE PIPE FROM FIRST FLOOR WITH APPROVED CONNECTION TO SOIL PIPE. 1501 W 47TH ST COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL REMOVE BLACK PIPE AND FITTINGS USED FOR WASTE LINE FROM FIRST FLOOR SINK AND INSTALL APPROVED MATERIALS. FIRST FLOOR. 1501 W 47TH ST COMPLAINT FAILED View
REMV RARELY USED FIXTURE REMOVE ABANDONED FAUCET AND PIPING FROM BEHIND BAR. 1501 W 47TH ST COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL REMOVE (2)-2" RUBBER COUPLINGS USED FOR A WASTE TIE IN BEHIND BAR AND INSTALL APPROVED ADAPTERS AND MATERIALS. 1501 W 47TH ST COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE REPLACE ALL FLEXIBLE SUPPLIES TO PLUMBING FIXTURES THROUGHOUT BUILDING. 1501 W 47TH ST COMPLAINT FAILED View
PROVIDE ADEQUATE SUPPORT REHANG URINAL WATER PIPE WITH APPROVED MATERIALS. 1501 W 47TH ST COMPLAINT FAILED View
PROVIDE OPEN FRONT TOILET SEAT PROVIDE OPEN FRONT TOILET SEATS FOR PUBLIC TOILETS. 1501 W 47TH ST COMPLAINT FAILED View
ENGAG LIC & BOND PLMBNG CNTRC HIRE A LICENSED PLUMBING CONTRACTOR. 1501 W 47TH ST COMPLAINT FAILED View
WORKING SPACE REMOVE ALL DEBRIS FROM IN FRONT OF SERVICE DISCONNECT LOCATED IN BASEMENT AREA. 1501 W 47TH ST COMPLAINT FAILED View
ADD RECEPTACLES ADD RECEPTACLES TO EASE EXTENSION CORD USE THROUGH OUT THE BAR COUNTER TOP AREAS, TV AND FOR LIGHTS. 1501 W 47TH ST COMPLAINT FAILED View
PROVIDE A WATER MAIN GROUND CONDUCTOR, CONDUIT TO WITHIN 5' OF WATER METER OR VALVE. 18-27-250.50 1501 W 47TH ST COMPLAINT FAILED View
SECURE RACEWAY PROPERLY SUPPORT ALL LOW VOLTAGE WIRING THROUGHOUT ALL BASEMENT AREAS AND 1ST FLOOR BAR AREAS. 1501 W 47TH ST COMPLAINT FAILED View
FROM DISCONNECT TO TAP BOX EXCEEDS 25' RULE. 18-27-240.21 B-2 1501 W 47TH ST COMPLAINT FAILED View
NO PERMIT WIRING OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS AND FOR PANELS INSTALLED WITH OUT PERMITS. 1501 W 47TH ST COMPLAINT FAILED View
REPLACE DEFECTIVE WASTE PIPING REMOVE PVC PIPE AND FITTINGS USED FOR (2) SUMP PUMPS DISCHARGE PIPING WITH APPROVED MATERIALS. 1501 W 47TH ST COMPLAINT FAILED View
INSTALL COVERS PROVIDE PROPER TYPE BOXES, COVERS FOR EXPOSED WIRING AT COMPRESSORS LOCATED IN BASEMENT AREAS. DANGEROUS AND HAZARDOUS. 1501 W 47TH ST COMPLAINT FAILED View