The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OCCUPIED WITHOUT REQ'D C OF O | FOR WORK COMPLETED AND OCCUPIED UNDER PERMIT #100085967 ISSUED 06/06/2006. MAKE ORIGINAL APPROVED ARCHITECTURAL PLANS AND ORIGINAL PERMIT AVAILABLE FOR FINAL CERTIFICATE OF OCCUPANCY INSPECTION. FAILURE TO OBTAIN CERTIFICATE OF OCCUPANCY BEFORE OCCUPYING BUILDING UNDER BUILDING PERMIT #100085967 ISSUED ON 06/06/2006 SEC (13-36-010 THRU 13-36-070) TO APPLY FOR CERTIFICATE OF OCCUPANCY CONTACT (312) 744-6695 MONDAY - FRIDAY 8:00AM - 4:30PM. NUMBER OF UNITS OCCUPIED _____. | 7047 S STATE ST | COMPLAINT | FAILED | View |
NO PLANS/PERMIT AT JOBSITE | FOR ALL INSPECTIONS. | 7047 S STATE ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | MISSING EQUIPMENT COVERS AT REAR TRASH COMPACTOR INSTALL EQUIPMENT COVERS WHERE REQUIRED THROUGHOUT PREMISES (14E-1-110.3) DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
ENGAG LIC & BOND PLMBNG CNTRC | ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING (18-29-106.1) | 7047 S STATE ST | COMPLAINT | PASSED | View |
PROVIDE PERMIT TO CORRECT VIOLATIONS (14A-4-404.6) | 7047 S STATE ST | COMPLAINT | PASSED | View | |
UNAPPROVED FLEXIBLE METAL CONDUIT BETWEEN LIGHT FIXTURES AT NORTH SERVICE AREA CEILING (14E-3-348.12) | 7047 S STATE ST | COMPLAINT | PASSED | View | |
INTERIOR FINISH FIRERESISTANCE | FAILED TO USE MATERIALS WITH APPROPRIATE FIRE RESISTANCE MATERIAL TO FINISH INTERIOR WALLS CURRENTLY WALLS LOCATED AT BEHIND COUNTER, STORAGE AREAS AT REAR OF PROPERTY,WORK SHOP AREA LOCATED AT THE FAR SOUHTEAST SECTION, AND ALL WALLS WHERE PLYWOOD MATERIALS TAKES THE PLACE WHERE 1HR FIRE RESISTANT MATERIALS ARE REQUIRED (DANGEROUS AND HAZARDOUS) | 7047 S STATE ST | COMPLAINT | PASSED | View |
PROVIDE PERMIT FOR THE INSTALLATION OF GENERATOR AT SOUTH ELECTRICAL SERVICE EQUIPMENT ROOM NO PERMIT ON RECORD FOR GENERATOR INSTALLATION (14A-4-404.6) | 7047 S STATE ST | COMPLAINT | PASSED | View | |
FLAMMABLE LIQUIDS 10-GAL LIMIT | REMOVE ALL FLAME SPREADING LIQUIDS UNDER OFFICE AREA STORAGE AREA, CURRENTLY MULTIPLE GALLONS OF PAINT STORED UNDER OFFICE BEHIND COUNTER UNDER OFFICE (FIRE HAZARD) | 7047 S STATE ST | COMPLAINT | PASSED | View |
PROPER MATRL WATER SUPPLY PIPE | UNAPPROVED FLEXIBLE WATER SUPPLIES TO PLUMBING FIXTURES THROUGHOUT PREMISES (18-29-605) | 7047 S STATE ST | COMPLAINT | PASSED | View |
VENT SYSTEM TO PRVNT BACK PRES | LAUNDRY TUB AND HAND SINK ADJACENT TO NORTHWEST EMPLOYEE BATHROOM MISSING VENTS TO SERVE FIXTURE TRAPS (18-29-901) | 7047 S STATE ST | COMPLAINT | PASSED | View |
SOIL/WASTE,VENT STK THRU ROOF | NORTHWEST INTERIOR EMPLOYEE BATHROOM DRAINAGE VENTILATION PIPING TERMINATES WITHIN BUILDING SPACE NOT THROUGH ROOF TO OUTER AIR EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS SEWER GASES (18-29-904) | 7047 S STATE ST | COMPLAINT | PASSED | View |
OBTAIN PERMIT FOR PLUMBING | OBTAIN PERMIT BEFORE CONSTRUCTING, ALTERING OR USING PLUMBING SYSTEM (13-12-080, 13-32-010) | 7047 S STATE ST | COMPLAINT | PASSED | View |
INSTALL COVERS | OPEN ELECTRICAL BOX WITH WIRES HANGING OUT BELOW FRONT CHECK OUT DESK AREA OPEN BOXES WITH HANGING WIRES AT REAR MAINTENANCE ROOM OPEN ELECTRICAL BOXES AT NORTHWEST STORAGE CLOSE OPEN BOXES WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
EXPOSED WIRING | OPEN WIRING AT REAR TRASH COMPACTOR AREA OPEN WIRE AT UNATTACHED LIQUID TIGHT FLEXIBLE METAL CONDUIT AT REAR EXTERIOR REMOVE OPEN WIRING WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
DEFECTIVE DISTRIBUTION | BROKEN/MISSING PANEL COVER DOOR AT NORTH ELECTRICAL SERVICE AREA ENSURE DISTRIBUTION EQUIPMENT IN SAFE APPROVED CONDITION THROUGHOUT PREMISES | 7047 S STATE ST | COMPLAINT | PASSED | View |
SUPPORT OUTLET AND BOX | UNSUPPORTED BOX REAR NORTH ELECTRICAL SERVICE AREA ENSURE BOXES ARE SUPPORTED IN APPROVED MANNER THROUGHOUT PREMISES | 7047 S STATE ST | COMPLAINT | PASSED | View |
ADD RECEPTACLES | ADD RECEPTACLE OUTLET TO ABATE EXTENSION CORD THROUGH CEILING NEAR ENTRY DESK AREA AND EXCESSIVE CORDS AT FRONT DESK AREA DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
WORKING SPACE | INSUFFICIENT WORKING SPACE AT PANELS AT SOUTH ELECTRICAL SERVICE AREA MAINTAIN REQUIRED WORKING SPACE WHERE REQUIRED THROUGHOUT PREMISES | 7047 S STATE ST | COMPLAINT | PASSED | View |
RESTORE EXIT AND EM | UNAPPROVED EMERGENCY LIGHT/EXIT SIGN AT FRONT DOOR BROKEN EMERGENCY LIGHT/EXIT SIGN AT REAR STORAGE AREA EM SYSTEM DOSES NOT APPEAR TO E MAINTAINED AND FULLY OPERABLE DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
CONTINUITY OF RACEWAYS | LIQUID TIGHT FLEXIBLE METAL CONDUIT (SEALTIGHT) NOT CONNECTED TO WASHROOM HAND DRYERS IN APPROVED MANNER ENSURE GROUND CONTINUITY WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS | 7047 S STATE ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | EXCESSIVE UNSUPPORTED LIQUID TIGHT FLEXIBLE METAL CONDUIT (SEALTIGHT) AT NORTH EXTERIOR (14E-3-350) | 7047 S STATE ST | COMPLAINT | PASSED | View |