Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR INTERIOR STAIR SYSTEM | GRADE TO BASEMENT HAS DANGEROUS AND HAZARDOUS STAIRS, BROKEN TREADS/STRINGERS AT BOTTOM OF STAIRS, INCORRECT RISER HEIGHTS AND WORN TREADS, MISSING HANDRAILS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
SUBMIT STRUCT. ENG. RPT (INT.) | 2X8 CEILING JOISTS AT EAST ELEVATION 13 TOTAL, AT 16' SPAN SHOWS THEY ARE DEFLECTING DOWNWARD CAUSING THAT SECTION OF ROOF STRUCTURE TO BE COMPROMISED AND IS A DANGEROUS AND HAZARDOUS CONDITION. ROOF STRUCTURE PLANK SHEATHING ARE WATER DAMAGED. ELEVATED WOOD PLATFORM SPANNING 20' RESTING ON BOW TRUSS RAFTERS. ALL REQUIRE A STRUCTURAL ENGINEER'S REPORT. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | ELEVATED 2X8 WOOD PLATFORM SPANNING 20' OVER SHOP NORTH ELEVATION RESTING ON BOW TRUSS RAFTERS AND SOUTH ELEVATION NOT SITTING IN BRICK/MORTAR POCKET. CENTER OF WOOD PLATFORM SUPPORTED BY FLAT STOCK ATTACHED TO ROOF STRUCTURE. CONSTRUCTED WITHOUT PLANS/PERMITS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | STEEL PANEL FENCE OVER 5 FT. REDUCE HEIGHT, REMOVE OR OBTAIN A PERMIT. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
NO BARBED WIRE ON FENCE < 8FT | REAR STEEL PANEL FENCE HAS RAZOR WIRE. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS HAVE EXPIRED TAGS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EAST/SOUTH WALLS HAVE LOOSE/MISSING MORTAR. SOUTH WALL HAS A STRESS CRACK. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | NEW NON-LOAD BEARING WOOD PARTITION WALLS FORMING A 20X26 ROOM WITH ELEVATED MEZZANINE WITH WOOD STAIRS 1ST FLOOR HAS LARGE ROOM, BATH, CLOSET. MEZZANINE HAS LARGE ROOM WITH BATH ALL CONSTRUCTED WITHOUT PLANS/PERMITS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE TRIPLE BASIN (18-29-1003.7.2) 15 CARS IN GARAGE. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | REMOVE FLEXIBLE SUPPLY TO TOILET NORTHWEST ELEVATION 1ST FLOOR. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | PERMIT FOR VIOLATIONS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | OBTAIN A LICENSED PLUMBER TO DO PLUMBING WORK. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
SUBMIT PLANS FOR PLUMBING PRMT | NO PERMITS FOR ROUGH PLUMBING, WATER WASTE AND VENT PIPING: 1ST FLOOR LAVATORY, TOILET, LAUNDRY BOX, LAUNDRY TUB NORTHWEST ELEVATION. 2ND FLOOR LAVATORY, TOILET NORTHWEST ELEVATION. 1ST FLOOR LAVATORY, TOILET WEST ELEVATION. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | REMOVE ALL PVC WASTE AND VENT PIPING 1ST AND 2ND FLOORS NORTHWEST ELEVATION, 1ST FLOOR WEST ELEVATION, BASEMENT NORTHWEST ELEVATION, BASEMENT SUBSOIL PIPING. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
EXPOSE FOR INSPECT APPROVAL | ALL SUBSOIL DRAIN TILE BASEMENT. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
REMOVE | REMOVE PVC WATER PIPE FOR SILCOCKS 1ST FLOOR SOUTH, EAST, WEST ELEVATION. PROVIDE PROPER MATERIAL. (18-29-605.6) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE RPZ FOR SILCOCKS 1ST FLOOR SOUTH, EAST AND WEST ELEVATION. (18-29-608.13.2) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE LID FOR SUMP PUMP BASEMENT NORTH ELEVATION. (18-29-1003.12) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | REMOVE 1-1/2 PVC DISCHARGE PIPE AND PROVIDE PROPER MATERIAL BASEMENT NORTH ELEVATION. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE FLOOR DRAIN FOR WATER HEATER 1ST FLOOR NORTHWEST ELEVATION. (18-29-412.4) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | INSTALL ILLUMINATION TO ALL EXTERIOR ENTRY DOORS AT FRONT AND REAR OF BUILDING INCLUDING SIDE OF BUILDING. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
CORRODED CONDUIT & EQUIP | REPLACE DEFECTIVE AND BROKEN CONDUITS THROUGHOUT GARAGE - DANGEROUS AND HAZARDOUS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
EXPOSED WIRING | REMOVE EXPOSED WIRING THROUGHOUT GARAGE - DANGEROUS AND HAZARDOUS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
NO PERMIT WIRING | PROVIDE PERMIT FOR ELECTRICAL INSTALLATION TO OFFICE BUILDOUT INSTALLED WITHOUT PERMIT. BOXES, WIRES, AND CONDUITS INSTALLED WITHOUT PERMIT TO 2 STORY OFFICE BUILDOUT. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
DEFECTIVE METER EQUIPMENT | REPLACE DEFECTIVE AND UNDERSIZED POWER SERVICE IMPROPERLY INSTALLED. ILLEGAL USE OF EMT MUST BE RIGID. RELOCATE METER TO EXTERIOR REAR OF BUILDING AND INSTALL MINIMUM 400 AMP POWER SERVICE. SERVICE NOT PROPERLY GROUNDED TO WATER MAIN - DANGEROUS AND HAZARDOUS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | REPLACE DEFECTIVE LIGHT FIXTURES THROUGHOUT SPECIFICALLY IN SPRAY AREA. ALL ELECTRICAL EQUIPMENT MUST BE EXPLOSION PROOF. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
(18-27-110.5) REMOVE ALL UNWORKMANLIKE INSTALLATIONS OF CONDUITS AND WIRING AND INSTALL PROPERLY. | 4519 W LAKE ST | COMPLAINT | FAILED | View | |
UNAPPROVED CORDS | REMOVE ALL UNAPPROVED EXTENSION CORDS THROUGHOUT GARAGE. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
ADD RECEPTACLES | INSTALL ADDITIONAL OUTLETS TO AVOID USE OF CORDS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
(18-27-516.2.(1)(2)(3)(4)(5)(6) INSTALL SPRAY BOOTH CLASS I OR ISOLATE ROOMS DESIGNATED FOR SPRAYING AUTOMOBILES AND ROOM DESIGNATED FOR DRYING. ALL FIXTURES AND ELECTRICAL EQUIPMENT MUST BE EXPLOSION PROOF FOR CLASS I LOCATION. | 4519 W LAKE ST | COMPLAINT | FAILED | View | |
SEE INSPECTOR COMMENTS | (13-12-360) PROVIDE PERMIT TO CORRECT VIOLATIONS. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | TOILET NORTHWEST ELEVATION 1ST FLOOR. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
(18-27-516.3A) ALL WIRING AND EQUIPMENT WITHIN CLASS I LOCATION SHALL BE EXPLOSION PROOF TYPE. | 4519 W LAKE ST | COMPLAINT | FAILED | View | |
PROVIDE | PROVIDE DRINKING FOUNTAIN. (18-29-403.1) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
(18-27-210.8) INSTALL GFCI'S TO GARAGE AREAS AND WET LOCATIONS. | 4519 W LAKE ST | COMPLAINT | FAILED | View | |
PROVIDE | PROVIDE LAUNDRY TUB OR MOP SINK. (18-29-403.1) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
STOP ODORS RPR DFT SEWAGE SYS | CAP OFF ALL OPEN PLUMBING TO ABATE SEWER GAS THROUGHOUT BUILDING. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE WORKING LAVATORY IN RESTROOM 1ST FLOOR NORTHWEST ELEVATION. (13-196-360) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
REMOVE STAGNANT WATER BSMT | STANDING WATER IN BASEMENT. | 4519 W LAKE ST | COMPLAINT | FAILED | View |
REMOVE | GAS CANS THROUGHOUT BUILDING IMPROPERLY STORED. (15-4-880) | 4519 W LAKE ST | COMPLAINT | FAILED | View |
OPEN | 4519 W LAKE ST | PERMIT | FAILED | View |