Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
LOOSE PLATE GLASS | SOUTH ENTRY DOOR GLASS PLATE CRACKED | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
PROVIDE | NORTH WEST PARKING MISSING DRAINAGE / SEWER CAUSING FLOOD TO ADJACENT PROPERTY-7-28-060 | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | SOUTH WEST WINDOW STONE SILL SPALLING, BROKEN CONCRETE CHIPPING EXPOSE REBAR. FALLING CONCRETE BADLY DETERIORATED | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 2ND / 3RD / 4TH EXIT SIGN BULBS OUT | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
TEST G & S PASS ELE | BOTH TRACTION CARS. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | PERFORM PRESSURE TEST #3 CAR. SEAL AND TAG VALUES AND SUBMIT REPORT TO CITY.(18-30-010,13-20-120) EV003048 | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
PRV RECEIVER | 450# PSIG FOR THE FOLLOWING TWO (2) 1/2 TON REMOTE REFRIGERATION UNITS THAT SERVES THE WALK IN COOLER/FREEZER THE UNITS ARE LOCATED ON THE 1ST FLOOR MACHINE ROOM. | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | FOR THE FOLLOWING THE VENT LINE OFF THE SAFETY VALVES ON THE 275 TON CHILLER. COPPER TUBING USED IN REFRIGERATION SYSTEMS SHALL BE BRAZED, SOLDERED JOINTS AND MECHNICAL JOINTS SHALL NOT BE USED. ALL JOINTS MUST BE BRAZED. | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
NO PERMIT PROJECT SIGN | SIGN READS " ASSOCIATION HOUSE OF CHICAGO" SIZE OF SIGN APPROXIMATELY 3' X 7' ON POLE | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
POST APPROVED OCCUPANCY CARD | PROVIDE OCCUPANCY CARDS FOR 3RD FLOOR CHAPEL, 2ND FLOOR STAFF LUNCH ROOM, 2ND FLOOR MULTI-PURPOSE, 1ST FLOOR CONFERENCE ROOMS A, B, C | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
NO KEY TO USE EXIT DOOR | "B" DOOR TO EXIT STAIRS RUSTED & CORRODED AT BASE | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
INTERIOR FINISH FIRERESISTANCE | 1ST FLOOR CAFETERIA MISSING SECOND EXIT SIGN | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | FIX PHONE TO WORK EQ1. 18-30-010, 13-20-120. EV003048 | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
REPAIR OR REPLACE | FOR THE FOLLOWING THE VENT LINE OFF THE SAFETY VALVES ON THE 275 TON CHILLER. COPPER TUBING USED IN REFRIGERATION SYSTEMS SHALL BE BRAZED, SOLDERED JOINTS AND MECHNICAL JOINTS SHALL NOT BE USED. ALL JOINTS MUST BE BRAZED. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
PRV RECEIVER | 450# PSIG FOR THE FOLLOWING TWO (2) 1/2 TON REMOTE REFRIGERATION UNITS THAT SERVES THE WALK IN COOLER/FREEZER THE UNITS ARE LOCATED ON THE 1ST FLOOR MACHINE ROOM. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE TEMPURATURE CONTROL IN MACHINE ROOM. | 1116 N KEDZIE AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE VENT IN MACHINE ROOM. | 1116 N KEDZIE AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE BETTER LIGHTING IN MACHINE ROOM. | 1116 N KEDZIE AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE GFI OUTLETS IN MACHINE ROOM. | 1116 N KEDZIE AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE FROM SERVIVE PROPERLY #3 HYDRO ELEVATOR | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE HOIST ROPES #2 ALSO WORN SHEAVE DRIVE MACHINE | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CURRENT CERTS | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN HOISTWAY AND PITS ELEV # 1&2 | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE WORN DRIVE SHEAVE | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
REMOVE | HOSE CLAMPS AND RUBBER HOSE FROM REFRIGERANT VENT LINE ON THE TRANE R-11 CENTRIFUGAL CHILLER LOCATED IN 3RD FLOOR MECHANICAL ROOM. STEEL PIPE AND FITTINGS ARE CODE. | 1116 N KEDZIE AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ON PHASE 2 DETECTOR EDGES NOT JUMPED OUT. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CARS 1&2 NEED CITY OF CHICAGO FIRE SERVICE MANDATE. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE PIPE TOP OF HOISTWAY. | 1116 N KEDZIE AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE THREADED ROD TOP OF HOISTWAY. | 1116 N KEDZIE AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH ALL HOLES IN HOISTWAY. | 1116 N KEDZIE AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST PHASE 1 &2 WHEN KEY SWITCH CUT OUTS ARE WIRED. | 1116 N KEDZIE AVE | PERMIT | PASSED | View |
CUT OR REMOVE HIGH WEEDS | SOUTHWEST HIGH WEEDS & SHRUBS | 1116 N KEDZIE AVE | COMPLAINT | FAILED | View |
OPEN TYPE VIOLATION | #3 ELEVATOR OUT OF SERVICE FOR JACK REPLACEMENT. | 1116 N KEDZIE AVE | PERIODIC | PASSED | View |