Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
WORK NOT ALLOWED | STEEL PANEL FENCE OVER 5 FT. REDUCE HEIGHT, REMOVE OR OBTAIN A PERMIT. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
NO BARBED WIRE ON FENCE < 8FT | REMOVE RAZOR WIRE AROUND PERIMETER OF FENCE. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | SOUTH WALL DEFLECTING OUTWARD OVER PUBLIC WALKWAY. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
SUBMIT 2 COPY STRUCTURAL RPT | PROVIDE STRUCTURAL ENGINEER'S REPORT FOR SOUTH WALL. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
PROTECT SIDEWALK DURING CONST | PROVIDE A CANOPY FOR SOUTH WALL. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | EAST/SOUTH MARKED EXIT DOORS UNDER THE REQUIRED 7'. NORTHEAST MARKED EXIT UNDER THE REQUIRED 36", DOOR AT 32". | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REPAIR FENCE | SOUTH METAL PANEL FENCE IS OUT OF PLUMB AND IN NEED OF REPAIR. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REPAIR ROOF | ROOF IN NEED OF REPAIR. WATER PENETRATING INTERIOR OF PROPERTY. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REMOVE | EXCESSIVE AMOUNTS OF DANGEROUS AND HAZARDOUS CHEMICALS THAT ARE IMPROPERLY STORED. IMPROPERLY STORED PROPANE, WELDING AND GAS CONTAINERS CAUSING A DANGEROUS AND HAZARDOUS CONDITION. (15-4-090) | 320 N HARDING AVE | COMPLAINT | FAILED | View |
DWELLING CLEAN AND SANITARY | EXCESSIVE AMOUNTS OF GARBAGE AND DEBRIS THROUGHOUT FACILITY. THIS POSES A DANGEROUS AND HAZARDOUS CONDITION. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REPAIR FLOOR | 1ST/2ND FLOORS HAS BROKEN AND MISSING CONCRETE AND SECTIONS OF FLOORS ARE UNEVEN CAUSING A TRIP HAZARD. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REMOVE STAGNANT WATER BSMT | ENTIRE FACILITY VARIOUS AREAS, THERE IS STAGNANT WATER. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | SOUTH WALL HAS STRESS CRACKS WITH SECTIONS OF BLOCK MISSING. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | EAST DOCK MISSING PROPER GUARDRAILS. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | ALL VIOLATIONS REQUIRE PROPER PLANS AND OR PERMITS BEFORE WORK IS STARTED. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | REMOVE ALL EXPOSED WIRING THROUGHOUT PLANT. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | INSTALL COVERS TO ALL ELECTRICAL EQUIPMENT THROUGHOUT PLANT. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
(18-27-110.5) PROPERLY SECURE CONDUITS FROM DISTRIBUTION. | 320 N HARDING AVE | COMPLAINT | FAILED | View | |
UNAPPROVED EM | MAINTAIN SYSTEM III IN OPERABLE CONDITION. | 320 N HARDING AVE | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | INSTALL ILLUMINATION TO AREAS OF PLANT WITH NO ILLUMINATION. PROVIDE PERMIT TO CORRECT VIOLATIONS. | 320 N HARDING AVE | COMPLAINT | FAILED | View |