Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-24 @ 3:19 PM
PIN: 16111150010000
Property Address: 646 N LAWNDALE AVE
City - Zip: CHICAGO - 60624
2023 Property Class: EX
2023 Township: 77 - West Chicago
2023 Neighborhood: 77101
2023 Tax District: 77052
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 89 Violations
Violation Inspector Comments Address Category Status View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL #1 & #2 SCOTCH MARINE BOILERS. 646 N LAWNDALE AVE PERIODIC PASSED View
REPAIR INTERIOR WALLS/CEILING REMOVE PEELING PAINT AT AUDITORIUM AND BALCONY CEILING. 646 N LAWNDALE AVE PERIODIC FAILED View
POST APPROVED OCCUPANCY CARD OCCUPANCY PLACARDS REQUIRED AT CAFETERIA AND GYMNASIUM. 646 N LAWNDALE AVE PERIODIC FAILED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC CLOSED View
INTERNAL #1 SUPERIOR SCOTCH MARINE BOILER BD# 6265. 646 N LAWNDALE AVE PERIODIC CLOSED View
INTERNAL #2 SUPERIOR SCOTCH MARINE BOILER BD# 6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC CLOSED View
REPLACE BLISTERED TUBES #1 SUPERIOR SCOTCH MARINE BOILER BD# 6265. 646 N LAWNDALE AVE PERIODIC CLOSED View
REPLACE GAS VALVE #1 SUPERIOR BOILER BD#6265. 646 N LAWNDALE AVE PERIODIC CLOSED View
REPLACE BOTTOM DRAIN ASSEMBLEY #2 SUPERIOR BOILER BD# 6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
SEAL CRACKED BRICKWORK SUPERIOR BOILER BD# 6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
REPLACE BOTTOM DRAIN ASSEMBLY #1 SUPERIOR BOILER BD# 6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC CLOSED View
INTERNAL #2 SUPERIOR SCOTCH MARINE BOILER NATIONAL BD# 6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
POST FLOOR PLAN DIAGRAM POST OCCUPANCY PLACARD DIAGRAMS ALL ROOMS 646 N LAWNDALE AVE PERIODIC FAILED View
REPAIR EAVES FASCIA BOARD AND GUTTER PULLING AWAYS FROM BUILDING WEST ELELVATION AND NORTH END OF BUILDING. 646 N LAWNDALE AVE PERIODIC FAILED View
REPAIR INTERIOR WALLS/CEILING PEELING PAINT CEILING AND WALLS IN GYMNASIUM AND VARIOUS OF HALLWAYS. 646 N LAWNDALE AVE PERIODIC FAILED View
LEAKING BOILER TUBES ON SUPERIOR BOILER #1. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
REPAIR OR REPLACE LEAKS IN MORRISON TUBE ON BOILER #1. 646 N LAWNDALE AVE PERIODIC PASSED View
HYDROSTATIC TEST ON SUPERIOR BOILER #1. 646 N LAWNDALE AVE PERIODIC PASSED View
SEAL CRACKED BRICKWORK AROUND BURNER CONE AND ON REAR DOOR OF SUPERIOR BOILER #2. 646 N LAWNDALE AVE PERIODIC PASSED View
REMOVE CHIMNEY DEBRIS IN BOILER ROOM. 646 N LAWNDALE AVE PERIODIC PASSED View
SEND EX. METAL LETTER ENGINEER REPORT 646 N LAWNDALE AVE COMPLAINT FAILED View
REMOVE RUST REMOVE RUST 646 N LAWNDALE AVE COMPLAINT FAILED View
USE NEW BOLTS OR RODS REPLACE HEAD RODS WHERE NEEDED 646 N LAWNDALE AVE COMPLAINT FAILED View
BROKEN OR MISSING RUNGS FIX STAIR 646 N LAWNDALE AVE COMPLAINT FAILED View
PROTECT METAL MEMBERS SCRAPE AND PAINT 646 N LAWNDALE AVE COMPLAINT FAILED View
POST APPROVED OCCUPANCY CARD AQUIRE DUPLICATE OCCUPANCAY CARD AND POST FOR GYM 646 N LAWNDALE AVE PERIODIC FAILED View
INT WALL/CEILING PEELING PAINT PEELING PAINT AT ASSEMBLY HALL & BALCONY CEILING. 646 N LAWNDALE AVE PERIODIC FAILED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL SUPERIOR SM NAT'L BD# 6264. 646 N LAWNDALE AVE PERIODIC PASSED View
INSTALL VENT/AS SHOWN ON PLANS 646 N LAWNDALE AVE PERMIT PASSED View
POST APPROVED OCCUPANCY CARD ACQUIRE DUPLICATE OCCUPANCY CARD AND POST FOR GYM. 646 N LAWNDALE AVE PERIODIC PASSED View
INT WALL/CEILING PEELING PAINT PEELING PAINT AT ASSEMBLY HALL & BALCONY CEILING. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC CLOSED View
INTERNAL #1 SUPERIOR 72 SM #6265. 646 N LAWNDALE AVE PERIODIC CLOSED View
INTERNAL #2 SUPERIOR 72 SM #6264. 646 N LAWNDALE AVE PERIODIC CLOSED View
REMOVE CHIMNEY DEBRIS BOILER ROOM. 646 N LAWNDALE AVE PERIODIC CLOSED View
SEAL BREECHNG AT CHMNY-BOILER BOILER ROOM. 646 N LAWNDALE AVE PERIODIC CLOSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
REPAIR SUP SM #6264 - REAR DOOR REFRACTORY. 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING BOILER TUBES SUP SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
REPLACE SUP SM #6264-BOTTOM HANDHOLE PLATES. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUP 72 SM NB# 6265. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUP 72 SM NB# 6264. 646 N LAWNDALE AVE PERIODIC PASSED View
REPLACE SUP SM #6265-BOTTOM HANDHOLE PLATES. 646 N LAWNDALE AVE PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR EMERGENCY 2-WAY COMMUNICATION (PHONE) IN PASSENGER ELEVATOR. 646 N LAWNDALE AVE PERIODIC FAILED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL BOILER #1 SUP 72 SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL BOILER #2 SUP 72 SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
DEFECTIVE SAFETY VALVE-BOILER BOILER #2 SUP 72 SM #6264 646 N LAWNDALE AVE PERIODIC PASSED View
REMOVE CHIMNEY DEBRIS COMPLETELY BLOCKED. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUPERIOR NB# 6265. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUPERIOR NB# 6264. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL #1 SUPERIOR 72 SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING BOILER TUBES #2 SUPERIOR 72 SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
HAND HOLE GASKETS BOTTOM TOW HAND HOLES #1 SUPERIOR 72 SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
HAND HOLE GASKETS BOTTOM TOW HAND HOLES #2 SUPERIOR 72 SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
POST APPROVED OCCUPANCY CARD OBTAIN OCCUPANCY PLACARD FOR THE GYM. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL BOILER #1 SUP 72 SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUPERIOR #1. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL ON SUPERIOR #2. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING BOILER TUBES SUPERIOR BOILER #1 NB# 6265. 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING BOILER TUBES SUPERIOR BOILER #2 NB# 6264. 646 N LAWNDALE AVE PERIODIC PASSED View
REPLACE DEFECTIVE BOILER GAS VALVE. 646 N LAWNDALE AVE PERIODIC PASSED View
OWNER OR LICENSED CONTRACTOR 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL BOILER #2 SUP 72 SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL SUPERIOR SM NAT'L BD# 6265. 646 N LAWNDALE AVE PERIODIC PASSED View
REMOVE SUP SM #6265-EXCESSIVE SCALE FROM BOTTOM OF BOILER ON THE WATERSIDE. 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING BOILER TUBES SUP SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
LEAKING MANHOLE GASKET BOILER #2 SUP 72 SM #6264 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL #2 SUPERIOR 72 SM #6264. 646 N LAWNDALE AVE PERIODIC PASSED View
INTERNAL BOILER #6 SUP 72 SM #6265. 646 N LAWNDALE AVE PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE MONTHLY MAINTENANCE LOG IN ELEVATOR MACHINE ROOM AS REQUIRED. 646 N LAWNDALE AVE PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE CURRENT ELEVATOR MONTHLY FIRE SERVICE TEST LOG ON SITE AS REQUIRED. 646 N LAWNDALE AVE PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE ELEVATOR MAINTENANCE CONTROL PROGRAM IN MACHINE ROOM AS REQUIRED. 646 N LAWNDALE AVE PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR CAR DOOR RESTRICTING DEVICE FOR PASSENGER ELEVATOR. 646 N LAWNDALE AVE PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA REMOVE ACCUMULATED DEBRIS FROM ELEVATOR PIT. 646 N LAWNDALE AVE PERIODIC FAILED View
MAINT PLATFORM LIFT PROPERLY REPAIR & MAINTAIN VERTICAL WHEELCHAIR LIFT IN A SAFE OPERATING CONDITION. CURRENTLY OUT OF SERVICE. 646 N LAWNDALE AVE PERIODIC FAILED View