Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PRV 5 YEARS OLD | ON CENTRAL AMMONIA SYSTEM | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
PROVIDE | 1) AUDIBLE AND VISUAL ALARMS BOTH INSIDE AND OUTSIDE THE ENGINE ROOM (18-28-1105.5)2) SWEEPS ON THE BOTTOM OF THE DOORS THAT PROVIDE ENTRANCE TO THE ENGINE ROOM (18-28-1105.3)3) AN OPERATIONAL EYE WASH/BODY SHOWER WITHIN 50'OF THE MAIN ENTRANCE TO THE ENGINE ROOM.(18-28-1101.7)4) A WIND SOCK ON THE ROOF OF THE BUILDING VISIBLE TO THE FIRE DEPARTMENT AS THEY APPROACH THE FIREMANS DUMP IN THE EVENT OF A RELEASE. (18-28-1101.7) | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
REPAIR OR REPLACE | ALL OPENINGS IN THE WALL,FLOOR OR CEILING THAT WOULD ALLOW A RELEASE OF REFRIGERANT. ALL OPENINGS/PENETRATIONS MUST BE SEALED SMOKE TIGHT.(18-28-1106.5) | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 7:00-8:00 AM. | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
PROVIDE | NEW WINDSOCK @ ROOF. ADD SIGNAGE ON AMMONIA VENT LINE ON ROOF. "AMMONIA VENT" | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAINTAIN OR DECOMMISSION ELEVATOR FROM SERVICE WITH PERMIT | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINT PLATFORM LIFT | REPAIR/MAINTAIN PLATFORM LIFT OR REMOVE FROM SERVICE WITH PERMIT. | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CODE DATA PLATE REQUIRED ON CONTROLLER | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PREVIOUS VIOLATION: BRING ELEVATOR INTO FULL COMPLIANCE BY PROVIDING: CAT1 TEST & TAGS, MAINTENANCE CONTROL PROGRAM, OIL USAGE LOG, CODE DATA PLATE OR HAVE AN ELEVATOR COMPANY PULL A PERMIT TO DECOMMISSION ELEVATOR IN UNUSED PORTION OF LAGROU | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
REPAIR OR REPLACE | THE INSULATION ON THE PIPING FOR THIS PUMP PACKAGE.ICING IS VISIBLE THROUGH THE INSULATION ESPECIALLY ON THE PUMP DISCHARGE PIPING. | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 7:00-8:00 AM | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CAT 1 TEST | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | MAINTAIN OR REMOVE ELEVTOR FROM SERVICE | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINT PLATFORM LIFT | REPAIR/MAINTAIN PLATFORM LIFT OR REMOVE FROM SERVICE. | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |
MAINT PLATFORM LIFT | PREVIOUS VIOLATION: REPAIR/MAINTAIN PLATFORM LIFT AT REAR OF BUILDING OR HAVE AN ELEVATOR COMPANY PULL A PERMIT TO DECOMMISSION UNIT. | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | BRING BOTH UNITS, ELEVATOR AND PLATFORM LIFT, UP TO CODE OR DECOMMISSION AND RESCHEDULE INSPECTION WITH THE CITY OF CHICAGO. | 3534 S KOSTNER AVE | PERIODIC | PASSED | View |
PROVIDE | NEW WINDSOCK @ ROOF. | 3534 S KOSTNER AVE | PERIODIC | FAILED | View |