Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | (VT 7034) ALL DUCT IN ATTIC SPACE MUST BE WRAPPED WITH R-5 VALUE INSULATION WITH R-VALVE STAMPED ON MATERIAL 18-28-603 18-28-604.7 18-28-603.11 | 2548 W BRYN MAWR AVE | COMPLAINT | PASSED | View |
OPEN TYPE VIOLATION | (VT 7030) DO NOT RETURN AIR FROM INSIDE FURNACE CLOSET. ALL RETURN OPENINGS ON FURNACES MUST BE DUCTED TO THE OUTSIDE OF FURNACE RM 18-28-918.9.4.3 | 2548 W BRYN MAWR AVE | COMPLAINT | PASSED | View |
OPEN TYPE VIOLATION | (VT 7022) COMPLETELY SEAL ALL SIDES OF ALL DUCT CONNECTIONS WITH PROPER SEALANT 18-28-603.8 | 2548 W BRYN MAWR AVE | COMPLAINT | PASSED | View |
REMOVE | REMOVE ALL DRYWALL COVERING DUCTWORK TO INSPECT AND TO PROPERLY CORRECT INCORRECTLY INSTALLED DUCTS | 2548 W BRYN MAWR AVE | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE. UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, BASEMENT, REAR PREMISES, AND REAR PORCHES. UNVERIFIED DETECTORS AND OCCUPANCY. | 2548 W BRYN MAWR AVE | COMPLAINT | FAILED | View |
FILE BLDG REGISTRATION | NOT REGISTERED 2000-2015 | 2548 W BRYN MAWR AVE | COMPLAINT | FAILED | View |
OPEN TYPE VIOLATION | (VT 7021) REMOVE ALL FLEXIBLE DUCT AND REPLACE WITH RIGID METAL DUCTWORK 18-28-603.5.1 | 2548 W BRYN MAWR AVE | COMPLAINT | PASSED | View |
ARRANGE PERMIT INSP. | 2548 W BRYN MAWR AVE | PERMIT | PASSED | View |