Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR EXTERIOR WALL | ALL ELEVATIONS VARIOUS LOCATIONS LOOSE AND WASHED OUT MORTER JOINTS SPALLING BRICKS. | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
FLAKY INTERIOR PAINT | ALL ELEVATIONS EXTERIOR WOOD LOOSE AND FLAKY PAINT. | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | 2 STORY PORCH WEST ELEVATION 2X8 JOIST SPANNING OVER 12 FT, GUARD RAILS UNDER 42" HIGH,JOIST AND STRINGERS TOENAILED TO RIM JOIST AND FOUNDATIONS UNKNOWN SUBMIT PLANS AND OBTAIN PERMIT BEFORE REPAIRING OR REPLACING PORCH. | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | SOUTH ELEVATION SERVICE WALK SINKING IN TOWARD HOUSE. | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | 7718 S LOOMIS NO RESPONSE UNABLE TO GAIN ENTRY TO VERIFY COMPLAINT OF MOLD IN BEDROOMS AND LOCKS ON FRONT ENTRY DOORS. | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | NO OWNER I.D SIGN POSTED | 7718 S LOOMIS BLVD | COMPLAINT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 7718 S LOOMIS BLVD | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | MULTI-WIRE BRANCH CIRCUIT DISCONNECTING MEANS MUST SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT POINT WHERE BRANCH CIRCUIT ORIGINATES (HANDLE TIES OR MULTI-POLE BREAKERS) 14E -2-210.4(B) | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED BY TESTING LABORATORY - BREAKERS TO BE LISTED FOR PANELBOARD 14E-1-110.3 | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | ONLY ALLOWED RIGID, IMC, SE CABLE (NOT MORE THAN 3 DU'S), BUSWAYS, CABLEBUS, MINERAL INSULATED- METAL SHEATHED CABLE. NO EMT! 14E-2-230.43 | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL MAIN BONDING JUMPER AT ALL SERVICE DISCONNECTS 14E-2-250.28 | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE A GROUNDING ELECTRODE SYSTEM TO INCLUDE ALL GROUNDING ELECTRODES (METAL UNDERGROUND WATER PIPE, METAL IN GROUND SUPPORT STRUCTURE, CONCRETE ENCASED ELECTRODE, GROUND RING, ROD & PIPE ELECTRODES, AND PLATE ELECTRODES) PRESENT AT BUILDING OR STRUCTURE SERVED.A METAL UNDERGROUND WATER PIPE WILL REQUIRE A SUPPLEMENTAL GROUNDING ELECTRODE 14E-2-250.50(A)(1) THRU (A)(7) 14E-2-250(D)(2) | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | GROUNDING ELECTRODE CONDUCTORS AND BONDING CONDUCTORS ON THE SUPPLY SIDE OF THE SERVICE DISCONNECT SHALL BE SIZED TO TABLE 250.66 14E-2-250.28 14E-2-250.30 14E-2-250.102 | 7718 S LOOMIS BLVD | PERMIT | PASSED | View |