Chicago Building Violations Data: 13 Violations
Violation Inspector Comments Address Category Status View
REPAIR EXTERIOR WALL ALL ELEVATIONS VARIOUS LOCATIONS LOOSE AND WASHED OUT MORTER JOINTS SPALLING BRICKS. 7718 S LOOMIS BLVD COMPLAINT FAILED View
FLAKY INTERIOR PAINT ALL ELEVATIONS EXTERIOR WOOD LOOSE AND FLAKY PAINT. 7718 S LOOMIS BLVD COMPLAINT FAILED View
REPAIR PORCH SYSTEM 2 STORY PORCH WEST ELEVATION 2X8 JOIST SPANNING OVER 12 FT, GUARD RAILS UNDER 42" HIGH,JOIST AND STRINGERS TOENAILED TO RIM JOIST AND FOUNDATIONS UNKNOWN SUBMIT PLANS AND OBTAIN PERMIT BEFORE REPAIRING OR REPLACING PORCH. 7718 S LOOMIS BLVD COMPLAINT FAILED View
SERVICE WALK, PASSAGE, AREAWAY SOUTH ELEVATION SERVICE WALK SINKING IN TOWARD HOUSE. 7718 S LOOMIS BLVD COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION 7718 S LOOMIS NO RESPONSE UNABLE TO GAIN ENTRY TO VERIFY COMPLAINT OF MOLD IN BEDROOMS AND LOCKS ON FRONT ENTRY DOORS. 7718 S LOOMIS BLVD COMPLAINT FAILED View
POST OWNER/MANAGERS NAME/# NO OWNER I.D SIGN POSTED 7718 S LOOMIS BLVD COMPLAINT FAILED View
ARRANGE COMPLETED PERMIT INSP. 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS MULTI-WIRE BRANCH CIRCUIT DISCONNECTING MEANS MUST SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT POINT WHERE BRANCH CIRCUIT ORIGINATES (HANDLE TIES OR MULTI-POLE BREAKERS) 14E -2-210.4(B) 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED BY TESTING LABORATORY - BREAKERS TO BE LISTED FOR PANELBOARD 14E-1-110.3 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS ONLY ALLOWED RIGID, IMC, SE CABLE (NOT MORE THAN 3 DU'S), BUSWAYS, CABLEBUS, MINERAL INSULATED- METAL SHEATHED CABLE. NO EMT! 14E-2-230.43 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS INSTALL MAIN BONDING JUMPER AT ALL SERVICE DISCONNECTS 14E-2-250.28 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS PROVIDE A GROUNDING ELECTRODE SYSTEM TO INCLUDE ALL GROUNDING ELECTRODES (METAL UNDERGROUND WATER PIPE, METAL IN GROUND SUPPORT STRUCTURE, CONCRETE ENCASED ELECTRODE, GROUND RING, ROD & PIPE ELECTRODES, AND PLATE ELECTRODES) PRESENT AT BUILDING OR STRUCTURE SERVED.A METAL UNDERGROUND WATER PIPE WILL REQUIRE A SUPPLEMENTAL GROUNDING ELECTRODE 14E-2-250.50(A)(1) THRU (A)(7) 14E-2-250(D)(2) 7718 S LOOMIS BLVD PERMIT PASSED View
SEE INSPECTOR COMMENTS GROUNDING ELECTRODE CONDUCTORS AND BONDING CONDUCTORS ON THE SUPPLY SIDE OF THE SERVICE DISCONNECT SHALL BE SIZED TO TABLE 250.66 14E-2-250.28 14E-2-250.30 14E-2-250.102 7718 S LOOMIS BLVD PERMIT PASSED View