Chicago Building Violations Data: 43 Violations
Violation Inspector Comments Address Category Status View
VENT SYSTEM TO PRVNT BACK PRES FIXTURE TRAPS MISSING VENTS THROUGHOUT PREMISES. 6027 S KEDZIE AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG FIRE EXTINGUISHERS THROUGH-OUT ARE EXPIRED/ OUTDATED. D&H 6027 S KEDZIE AVE COMPLAINT FAILED View
UNINTERRUPTED EXIT AT GRADE NORTHWEST ELEVATION REAR EGRESS BLOCKED BY GOODS. D&H 6027 S KEDZIE AVE COMPLAINT FAILED View
1HR FLR OVER BSMT, 1 OR 2 DU BASEMENT CEILING 1/4" PLYWOOD USED (COMBUSTIBLE). 1 HOUR FIRE SEPARATION IS REQUIRED. 5/8" TYPE X FIRECODE 6027 S KEDZIE AVE COMPLAINT FAILED View
PERMIT REQUIRED - CONTRACTOR PROVIDE PERMIT FOR INSTALLATION OF DRYWALL. 6027 S KEDZIE AVE COMPLAINT FAILED View
WORK NOT ALLOWED REMOVE ALL PARTITIONS AND FIXTURES INSTALLED IN 6033 S KEDZIE (KEDZIE SPA) WITH OUT A PERMIT. 6027 S KEDZIE AVE COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO 6033 S KEDZIE (KEDZIE SPA) OR RESTORE THE BUILDING TO THE ORIGINAL STATE. 6027 S KEDZIE AVE COMPLAINT FAILED View
STRUCTURAL MEMBER, PIER BLOCK THERE ARE SEVERAL TEMP LALLY COLUMNS (SCREW TYPE) INSTALLED AT 1ST FLOOR REAR AND BASEMENT AREAS. TEMP LALLY COLUMNS ARE NOT PERMITTED FOR PERMANENT USE. REPLACE WITH CORRECT TYPE OF COLUMN. 6027 S KEDZIE AVE COMPLAINT FAILED View
HEATING PLANT ENCLOSURE OPEN STUDDING AT FURNACE ROOM 1ST FLOOR REAR AREA. D&H 6027 S KEDZIE AVE COMPLAINT FAILED View
WORKING SPACE MAIN SERVCIE DISCONNECT AND DISTRIBUTION EQUIPMENT BLOCKED BY DEBRIS, STORAGE AND CLUTTER. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
25-33 OBTAIN PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANEOUIS ELECTRICAL WORK VARIOUS AREAS. NO PERMITS. PART SOUTH WEST PART OF 25-33 BUILT OUT INTO MASSAGE PARLAR. NO PERMITS. 6027 S KEDZIE AVE COMPLAINT FAILED View
DEFECTIVE OUTLETS 25-33 DAMAGED, CORRODED SWITCHES AND RECEPTACLES VARIOUS AREAS. REPLACE WHERE REQUIRED. 6027 S KEDZIE AVE COMPLAINT FAILED View
VENT 5' WITHIN TRAP UNAPPROVED PVC PIPING USED THROUGHOUT PREMISES. PVC PENETRATIONS THROUGH FLOORS REQUIRING FIRE SEPARATIONS DANGEROUS AND HAZARDOUS. 6027 S KEDZIE AVE COMPLAINT FAILED View
ADD RECEPTACLES 25-33 ADD RECEPTACLES WHERE REQUIRED TO ELIMINATE THE USE OF VISIBLE EXTENSION CORDS. DANGREOUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
25-33 PROVIDE ANY REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT ,BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANSOUS ELECTRICAL WORK THROUGHOUT. NO PERMITS. SOUTH WEST SPACE BUILT OUT INTO MASSAGE PARLOR. NO PERMITS. (14A-5-505.2) 6027 S KEDZIE AVE COMPLAINT FAILED View
CORD TO FIXTURE 25-33 UNAPPROVED CORD WIRED LIGHT FIXTURES VARIOUS AREAS. 6027 S KEDZIE AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION 33 ALL EQUIPMENT USED IN MASSAGE ROOMS MUST BE IDENTIFIED AND SUITABLE FOR USE INCLUDING TABLES, TUBS, LAMPS, ETC. 6027 S KEDZIE AVE COMPLAINT FAILED View
INSTALL COVERS OPEN BOXES VARIOUS. CLOSE WHERE REQUIRED. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
DEFECTIVE SERVICE 25-33 SERVICE HEAD COMPLETELY DAMAGED. OVERHEAD SERVICE CABLES APPEAR DAMAGED AT HEAD. C/T CABINET HAS LARGE OPENING IN SIDE. MAIN DISCONNECT DETERIORATED / DAMAGED WITH EXPOSED LIVE PARTS. ASSOCIATED DISTRIBUTION DETERIORATED LIVE FRONT. SERVICE MODIFIED FROM ORIGINAL CONDITION NO PERMITS. ENSURE SERVICE IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
DEFECTIVE FIXTURES 25-33 DAMAGED, UNCOVRED LIGHT FIXTURES VARIOUS. REPAIR REPLACE WHERE REQUIRED. 6027 S KEDZIE AVE COMPLAINT FAILED View
SUPPORT FIXTURES 25-33 INSUFFICIENTLY SUPPORTED LIGHT FIXTURES VARIOUS AREAS THROUGHOUT. 6027 S KEDZIE AVE COMPLAINT FAILED View
SUBMIT PLANS FOR PLUMBING PRMT SUBMIT PLANS TO BUILDING, WATER AND SEWER DEPARTMENTS FOR APPROVAL AND PERMIT BEFORE CONSTRUCTING, ALTERING OR USING PLUMBING SYSTEM. SPECIFICALLY ENTIRE PLUMBING SYSTEM HAS BEEN MODIFIED FROM ORIGINAL STATE WITHOUT PLANS PERMITS OR INSPECTIONS. 6027 S KEDZIE AVE COMPLAINT FAILED View
INDIRECT CONN.FOR WATER SUPPLY WATER SUPPLIES TO SHOWERING TABLE WANDS AT 6033 FRONT UNIT USED AS SPA ARE DIRECTLY CONNECTED TO POTABLE WATER SYSTEM WITHOUT ANY MEANS OF CROSS CONTAMINATION PREVENTION. DANGEROUS AND HAZARDOUS. 6027 S KEDZIE AVE COMPLAINT FAILED View
EXPOSED WIRING 25-33 OPEN WIRING VARIOUS AEAS INTERIOR AND EXTERIOR. REMOVE WHERE REQUIRED. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
33 OBTAIN PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. SPACE WITHIN 25-33 BUILT OUT INTO MASSAGE PARLOR. NO PERMITS. (14A-4-404.6) 6027 S KEDZIE AVE COMPLAINT FAILED View
SECURE RACEWAY 25-33 UNAUPPORTED CONDUITS VARIOUS AREAS. SECURE WHERE REQUIRED. 6027 S KEDZIE AVE COMPLAINT FAILED View
LISTED FOR USE TEMP & LOCATION 25-33 ALL EXTERIOR LIGHT FIXTURES, BOXES, FITTINGS, RACEWAYS MUST BE SUITABLE FOR WET LOCATION. 6027 S KEDZIE AVE COMPLAINT FAILED View
PROPER SIZE GRD ELECTRODE COND 25-33 NO VISIBLE WATER GROUND. ENSURE SERVICE GROUNDE IN APPROVED MANNER. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
PANEL SCHEDULES 25-33 INSUFFICIENT PANEL SCHEDULES THROUGHOUT. 6027 S KEDZIE AVE COMPLAINT FAILED View
ENGAG LIC & BOND PLMBNG CNTRC 6027 S KEDZIE AVE COMPLAINT FAILED View
SEE INSPECTOR COMMENTS 25-33 PROVIDE ONE LINE DIAGRAM AND LOAD CALCULATION FOR ELECTRICAL SERVICE AND FEEDERS. (14E-2-215.5, 14E-2-220.40) 6027 S KEDZIE AVE COMPLAINT FAILED View
REPAIR OR REPLACE SUMP PIT MISSING COVER AT BASEMENT. DANGEROUS AND HAZARDOUS. 6027 S KEDZIE AVE COMPLAINT FAILED View
RESTORE EXIT AND EM 25-33 EXISTING EMERGENCY LIGHTING SYSTEM IS UNAPPROVED, INOPERABLE, UNMAINTAINED, INSUFFICIENT. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
33 PROVDE ALL REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. SPACE WITHING 25-33 BUILT OUT INTO MASSAGE PARLOR. NO PERMITS. (14-5-505.2) 6027 S KEDZIE AVE COMPLAINT FAILED View
PROVIDE OPEN FRONT TOILET SEAT UNAPPROVED ROUND BOWL TOILET WITH CLOSED FRONT SEAT. 6027 S KEDZIE AVE COMPLAINT FAILED View
INSTALL ILLUMINATION 25-33 INSTALL ILLUMINATION AT ALL EXTERIOR ENTRIES AND WHERE REQUIRED THROUGHOUT. 6027 S KEDZIE AVE COMPLAINT FAILED View
CLOSE BOX OPENINGS 25-33 MISSING BOX FILLERS, PANEL FILLERS THROUGHOUT. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
PROVIDE ADEQUATE SUPPORT INSUFFICIENT HANGER SUPPORT TO SUSPENDED CAST IRON PIPING AT BASEMENT. PIPING IS SUPPORTED USING BAND IRON AND DRYWALL SCREWS. SECTIONS OF PIPING HAVE BEEN REPLACED WITH PVC DUE TO COLLAPSING PREVIOUSLY PER OWNER. SUSPENDED CAST IRON SYSTEM IS SHOWING SIGNS OF FAILURE DUE TO LACK OF SUPPORT. DANGEROUS AND HAZARDOUS. 6027 S KEDZIE AVE COMPLAINT FAILED View
INSTALL GFCI'S 25-33 INSTALL GFCI RECEPTACLES BATH, KITCHEN AREAS, INDOOR WET LOCATIONS, GARAGE, EXTERIOR.SINKS 6027 S KEDZIE AVE COMPLAINT FAILED View
DEFECTIVE DISTRIBUTION 25-33 DAMAGED PANELS. PANELS WITH BROKEN / MISSING COVERS. PANELS WITH MISSING CIRCUIT BREAKERS. DETERIATED BROKEN DISCONNECTS AND FUSE BOXES. ENSURE DISTRIBUTION THROUGHOUT PREMISES IN APPROVED CONDITION. DANGEROUS AND HAZARDOUS 6027 S KEDZIE AVE COMPLAINT FAILED View
25-33 PROVIDE FULL ACCESS TO INSPECT DROP CEILING AREAS THROUGHOUT PREMISES. (14E-5-505.2) 6027 S KEDZIE AVE COMPLAINT FAILED View
PROVIDE MISSING MIXING VALVES AT LAVATORIES THROUGHOUT. (18-29-607) 6027 S KEDZIE AVE COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE MISSING DIE-ELECTRICAL CONNECTIONS WHERE COPPER CONNECTS TO GALVANIZED PIPING THROUGHOUT PREMISES. 6027 S KEDZIE AVE COMPLAINT FAILED View