Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
STOP RECIRC.AIR F/CONTAMT'D. R | STOP RECIRCULATING AIR FROM ROOM CONTAMINATED BY DUST (13-176-090D) SEVERAL UNITS INCLUDING #117 LARGE AMOUNTS DUST IN AIR FILTERING OUT INTO COMMON AREAS | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
DUST SEPARATOR OUTSIDE OF BLDG | LOCATE DUST SEPARATOR OUTSIDE OF BUILDING WITH EXHAUST DUCT LEADING TO SEPARATORS AS SHORT AS POSSIBLE (15-28-1210.1G) UNIT # 117 DUST COLLECTOR INSIDE OF SHOP AREA | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 5921 W DICKENS AVE | COMPLAINT | PASSED | View | |
GIVE VENT OPENINGS % FL. AREA | PROVIDE MECHANICAL EXHAUST VENTILATION AT CU. FT PER MINUTE EQUAL TO SQ. FT. OF FLOOR AREA TIMES FACTOR BASED ON USE (18-28-403.3) NO EXHAUST FANS FOR WASHRROOMS (METRO, SELF STORAGE) | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
MAINTAIN MECH. VENT SYSTEM | MAINTAIN MECHANICAL VENTILATION & HEATING SYSTEM IN GOOD REPAIR & OPERATE SAFELY DURING HOURS OF OCCUPANCY,(18-28-102.3) FLUE PIPE FOR OFFICE FURNACE & 1 UNIHEATER IN STORAGE AREA NEED TO BE REPLACES DETERIORATED WITH A POTENTIAL TO LEAK CARBON MONOXIDE | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
GIVE VENT OPENINGS % FL. AREA | PROVIDE MECHANICAL EXHAUST VENTILATION AT CU FT PER MINUTE EQUAL TO SQ FT OF FLOOR AREA TIMES FACTOR BASED ON USE,(18-28-403.3) NO EXHAUST FANS FOR INDIVIDUAL SHOP RENTALS IMAGE AMOUNT OF DUST IN AIR | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 5921 W DICKENS AVE | COMPLAINT | PASSED | View | |
ARRANGE PREMISE INSPECTION | 5921 W. / INTERIOR OF BUILDING / NO RESPONSE, UNVERIFIED DETECTORS, OCCUPANCY OR CONDITIONS. UNABLE TO VERIFY ANY WORK DONE WITHOUT PERMITS. | 5921 W DICKENS AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | 5921 W. / FRONT OF BUILDING / GLASS BLOCK - BROKEN, CRACKED. | 5921 W DICKENS AVE | COMPLAINT | FAILED | View |
STOP RECIRCULATING AIR | STOP RECIRCULATING AIR (13-176-090D), USING AIR INSIDE WASHROOMS FOR RETURN AIR | 5921 W DICKENS AVE | COMPLAINT | PASSED | View |
PROVIDE MINIMUM VENT QUANTITY | PROVIDE VENTILATION TO INSURE MINIMUM, AIR QUANTITIES (13-176-060,13-176-070).NO FRESH AIR INTAKE FOR METRO OFFICE | 5921 W DICKENS AVE | COMPLAINT | FAILED | View |