The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR | LEAKING CONDENSATE RETURN TANK. | 655 W 65TH ST | PERIODIC | PASSED | View |
SUPPORT FIXTURES | BALCONY 10 LOOSE LIGHT FIXTURE | 655 W 65TH ST | PERIODIC | PASSED | View |
STOP OPERATING BOILER - UNSAFE | #1 BOILER NB# 25041. | 655 W 65TH ST | PERIODIC | PASSED | View |
LICENSED CONTRACTOR | 655 W 65TH ST | PERIODIC | PASSED | View | |
LEAKING BOILER TUBES | #1 BOILER NB# 25041. | 655 W 65TH ST | PERIODIC | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE EXCESSIVE SCALE FROM WATER SIDE OF #1 BOILER. | 655 W 65TH ST | PERIODIC | PASSED | View |
HYDROSTATIC TEST | #1 BOILER NB# 25041. | 655 W 65TH ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 655 W 65TH ST | PERIODIC | PASSED | View | |
ADJUST BOILER BURNER | 32 OS SCOTCH MARINE BOILER BD# 25042. | 655 W 65TH ST | PERIODIC | PASSED | View |
ADJUST BOILER BURNER | #1 BOILER. | 655 W 65TH ST | PERIODIC | PASSED | View |
FOUND NO VIOLATIONS AS OF DATE | NO APPARENT VIOLATION AT TIME OF INSPECTION. | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE ROUGHING HOIST ROPES BOTH CAR. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL OR MAKE OPERATIONAL DOOR RESTRICTORS. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BUILD WALL BETWEEN WATER TANK AND EQUIMENT IN ELEVATOR MACHINE ROOM. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETURN CAR #2 NORTH TO SAFE AND PROPER WORKING ORDER. EV008226 | 655 W 65TH ST | PERIODIC | FAILED | View |
HEAT UNIT ADEQUATELY | 1ST FLR. / SENIORS' COMMON ROOM - 66F AND RECREATIONAL ROOM - 61F. HEATING SYSTEM IS ON AT TIME OF INSPECTION, INSUFICIENT HEAT SUPPLIED. | 655 W 65TH ST | COMPLAINT | FAILED | View |
SUPPLY HOT WTR MIN TEMP 120DEG | UNIT 1012 / KITCHEN - 85F AND UNIT 1013 / BATHROOM - 84.5F - INADEQUATE HOT WATER TEMPERATURES THRU-OUT. | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CITY OF CHICAGO COMPLAINT: CLOSE OPEN MODERNIZATION PERMIT #100870185 | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE KICK PLATES AROUND CABLE SLOTS/MACHINE FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CORRECT CAR CAPACITY PLATE INSIDE ELEVATOR #2. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL MAINLINE AND 110 VAC DISCONNECTS WITH CIRCUIT FEED LOCATION FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE "AVAILABLE FOR FIRE SERVICE" JEWEL IN LOBBY STATUS PANEL FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SUFFICIENT FIRE SERVICE KEYS IN KEY BOX FOR EACH ELEVATOR AND STATUS PANEL/EM POWER SWITCHES FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADDITIONAL MACHINE ROOM AND DOOR RELEASE KEYS IN EMERGENCY KEY BOX FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST EMERGENCY POWER WITH FULL LOAD FOR FINAL. CAR #1 FAILED TO SWITCH OVER. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | VERIFY EMERGENCY POWER SELECTOR SWITCH IN LOBBY STATUS PANEL. | 655 W 65TH ST | PERMIT | FAILED | View |
INT WALL/CEILING CHIP PLASTER | SECURITY GUARD STATION - WATER DAMAGED WALL , NEAR AIR CONDITIONER UNIT. | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROPERLY PROGRAM ELEVATOR EMERGENCY PHONE TO A 24 HOUR ANSWERING SOURCE | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BUILD WALL BETWEEN WATER TANK AND EQUIPMENT IN MACHINE ROOM (PREVIOUSLY CITED) | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 1ST FLOOR AT MANAGERS OFFICE, 3RD FLOOR AT ELEVATORS, 12TH AND 13 TH FLOORS STAIRWAY SIGNS - OUT OF SERVICE AT TIME OF INSPECTION. | 655 W 65TH ST | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | TRASH CHUTE DOORS AT MOST FLOORS - NOT LATCHING. BOILER ROOM EAST ENTRY DOOR - HITTING JAMB PREVENTING IT FROM CLOSING. | 655 W 65TH ST | COMPLAINT | FAILED | View |
HOLDOPEN DEVICE, STAIR 3+ FLRS | 1ST FLOOR WEST HALLWAY DOORS - TOE KICKS INSTALLED, DOORS HELD OPEN. LAUNDRY ROOM DOORS - HANGERS TIED BACK KEEPING DOORS OPEN. | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BUILD WALL BETWEEN WATER TANK AND EQUIMENT IN ELEVATOR MACHINE ROOM (PREVIOUSLY CITED) | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CAR STATION WITH CORRECT CAPACITY | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WHILE TESTING THE EMERGENCY PHONE DURING INSPECTION, THE SECURITY STAFF WAS UNABLE TO ANSWER. PROGRAM EMERGENCY PHONE TO 24HR MONITORING SERVICE. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE TOP OF CAR DATA PLATE TO GIVE CURRENT CABLE SIZE AND AMOUT OF CABLES | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CABLE TAGS FOR NEW GOVERNOR ROPE AND CAR CABLES | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FINISH CAB AND PROVIDE DOCUMENTATION OF WEIGHT OF NEW INTERIOR FOR CAB | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ELEVATOR IDENTIFICATION ON ELEVATOR JAMB OF EVERY LANDING | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | EXTEND HANDRAILS FOR SHIPS LADDER LEADING TO MACHINE ROOM | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE DAMAGED MACHINE ROOM STAIRS AND REPLACE WITH CODE COMPLIANT STAIRS | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE GFI IN MACHINE ROOM TO BE WITHIN REACH OF CONTROLLERS AND MACHINES | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BLANK OUT OLD EXHAUST FAN SWITCH IN MACHINE ROOM | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SELF-CLOSING/SELF-LOCKING MACHINE ROOM DOOR | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MACHINE ROOM DOOR SIGNAGE | 655 W 65TH ST | PERMIT | FAILED | View |
IDENTIFY ELEV POWER LINE DISC | PROVIDE DISCONNNECT SOURCE FEED LABEL FOR MAIN LINE & 110V FEEDS | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BEFORE FINAL INSPECTION: EMERGENCY POWER, FIRE ACTIVATED INITIATING DEVICES, PHASE II, AND LOSS OF COMMUNICATION. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MACHINE ROOM AND ACCESS DOOR KEY | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH HOISTWAY FOR BOTH ELEVATORS | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE KICK ANGLES AROUND MACHINE BED PLATE | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE UNUSED ELECTRICAL PIPE IN HOISTWAY | 655 W 65TH ST | PERMIT | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | AT ALL ELECTRICAL CLOSETS PROVIDE FIRE STOP ALL PIPE PENETRATIONS WITH AN APPROVED MATERIAL.OPENINGS AROUND EXPOSED PIPES OR POWER SHAFTING SHALL BE FILLED WITH APPROVED NONCOMBUSTIBLE MATERIAL, OR SHALL BE CLOSED OFF BY CLOSE-FITTING METAL CAPS AT THE CEILING AND FLOOR LINE, AND ON EACH SIDE OF A WALL, CEILING OR PARTITION.AS PER BUILDING CODE 15-8-640 | 655 W 65TH ST | COMPLAINT | FAILED | View |
REMOVE | REMOVE DANGEROUS AN HAZARDOUS FLUE PIPE FROM WATER HEATERS THAT ARE TAP INTO A VAN PACKER WALL FLUE THAT WAS RATED A 1400 DEGREE TEMP | 655 W 65TH ST | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | ARRANGE MECHANICAL VENTILATION FINAL INSPECTION WHEN WORK COMPLETED | 655 W 65TH ST | COMPLAINT | PASSED | View |
REPAIR OR REPLACE | REPAIR OR REPLACE STOVE PIPES FROM WATER HEATER THAT TAP INTO THE BOILER VAN PACKER CHIMNEY STACKS FLUES MUST BE DOUBLE WALL PIPE | 655 W 65TH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE HOIST ROPE DATA TAGS. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COVER FOR SUMP PUMP FOR FINAL. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLOSE ALL OPEN ELECTRICAL RACEWAY DUCTS FOR FINAL. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | VERIFY/ REPAIR EMERGENCY COMMUNICATION SIGNAL LOSS AUDIBLE AND VISUAL WARNING SIGNAL (1ST FLOOR HALL BUTTON) FOR FINAL. BOTH ELEVATORS. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #2, REPAIR EMERGENCY PHONE TO OPERATE ON BATTERY BACKUP FOR FINAL. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST CAR TOP OPERATION STATION ON PHASE I RECALL. BOTH ELEVATORS FAILED TO OPEN AT MAIN LANDING. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE DATA TAG ON CONTROLLER(S) FOR FINAL. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN MECH. VENT SYSTEM | MAINTAIN MECHANICAL VENTILATION SYSTEM CODE 13-176-070 | 655 W 65TH ST | COMPLAINT | PASSED | View |
PROVIDE | PROVIDE TOILET EXHAUST | 655 W 65TH ST | COMPLAINT | PASSED | View |
DISCHARGE EXHAUST OUTSIDE | DISCHARGE EXHAUST OUTSIDE 13-176-110 OUT OF A TOTAL OF 6 TOILET EXHAUST FANS ON THE ROOF ONLY 1 IS OPERABLE | 655 W 65TH ST | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | MOST UNITS - UNDER CONSTRUCTION AT TIME OF INSPECTION. SOME OTHER UNITS - NO RESPONSE. UNABLE TO VERIFY DETECTORS AND CONDITIONS. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 1ST FLOOR/ EAST STAIRWAY DOOR TO EXTERIOR / EXIT SIGN - NOT ILLUMINATED. | 655 W 65TH ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | MOST UNITS - UNDER CONSTRUCTION AT TIME OF INSPECTION. SOME OTHER UNITS - NO RESPONSE. UNABLE TO VERIFY DETECTORS AND CONDITIONS. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 1ST FLOOR/ EAST STAIRWAY DOOR TO EXTERIOR / EXIT SIGN - NOT ILLUMINATED. | 655 W 65TH ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | MOST UNITS - UNDER CONSTRUCTION AT TIME OF INSPECTION. SOME OTHER UNITS - NO RESPONSE. UNABLE TO VERIFY DETECTORS AND CONDITIONS. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 1ST FLOOR/ EAST STAIRWAY DOOR TO EXTERIOR / EXIT SIGN - NOT ILLUMINATED. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 1ST FLOOR/ EAST STAIRWAY DOOR TO EXTERIOR / EXIT SIGN - NOT ILLUMINATED. | 655 W 65TH ST | PERIODIC | FAILED | View |
REMOVE | EXCESSIVE SCALE BUILD UP IN WATER SIDE OF #2 BOILER NB# 25042. | 655 W 65TH ST | PERIODIC | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 655 W 65TH ST | PERMIT | PASSED | View | |
REPAIR OR REPLACE | REPAIR OR REPLACE 5 EXHAUST FAN | 655 W 65TH ST | COMPLAINT | PASSED | View |
REPAIR EXTERIOR DOOR | 1ST FLOOR REAR EXTERIOR DOOR NO DOOR CLOSER. 14 TH FLOOR ELEVATOR EXTERIOR DOOR DOUBLE DOOR DOES NOT LATCH | 655 W 65TH ST | PERIODIC | CLOSED | View |
FIRE EXTNGSHR RECHARGE & TAG | 14 STORY BUILDING /FIRE EXTINGUISHER - THOUGHOUT TAG 1/2020 | 655 W 65TH ST | PERIODIC | FAILED | View |
REPAIR FLOOR | APT 309 /KITCHEN FLOOR - WATER DAMAGE AND UNDER KITCHEN SINK CABINET DARK STAINS. ELEVATOR / FLOOR TILE - BROKEN AND MISSING TILE. | 655 W 65TH ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | WEST ELEVATION - 13 FL INTERIOR STAIRS INTERIOR DOOR NOT LATCH.TRASH CHUTTE 12,10TH,9TH,6TH AND 4TH FLOOR NOT LATCHING.1ST FLOOR BOILER DOOR INTERIOR DOOR NOT LATCH. | 655 W 65TH ST | PERIODIC | CLOSED | View |
KEEP FIXTUR CLEAN AND SANITARY | APT 307/309/ SEWER BACK UP - IN KITCHENS. | 655 W 65TH ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING OWNER ID NOT POSTED | 655 W 65TH ST | PERIODIC | CLOSED | View |
STOP ODORS RPR DFT SEWAGE SYS | APT 307/309 / SEWAGE SMELL - BY KITCHEN SINKS | 655 W 65TH ST | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 655 W 65TH ST | PERIODIC | PASSED | View | |
MAINTAIN MECH. VENT SYSTEM | MAINTAIN MECHANICAL VENTILATION SYSTEMS ALL TOILET EXHAUST FANS MUST BE UP AND RUNNING CODE 13-176-300 | 655 W 65TH ST | COMPLAINT | PASSED | View |
STOP LEAKING WATER | APT 309/07 / WATER LEAKING - KITCHEN FLOORS. | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE DIAGRAMMATIC REPRESENTATION OF ELEVATORS IN LOBBY AT LOBBY PANEL | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE SPRINKLERHEAD AND PIPES IN PIT | 655 W 65TH ST | PERMIT | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | EXTERIOR DOOR THROUGH OUT ALL BALCONY LEFT OPENING | 655 W 65TH ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR | 1ST FLOOR REAR EXTERIOR DOOR NO DOOR CLOSER. 14 TH FLOOR ELEVATOR EXTERIOR DOOR DOUBLE DOOR DOES NOT LATCH | 655 W 65TH ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | WEST ELEVATION - 13 FL INTERIOR STAIRS INTERIOR DOOR NOT LATCH.TRASH CHUTTE 12,10TH,9TH,6TH AND 4TH FLOOR NOT LATCHING.1ST FLOOR BOILER DOOR INTERIOR DOOR NOT LATCH. | 655 W 65TH ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING OWNER ID NOT POSTED | 655 W 65TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COUNTERWEIGHT RUNBY SIGNAGE | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE AND MOUNT ABC FIRE EXTINGUISHER IN MACHINE ROOM. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE STRIPING AROUND COMP CABLE IN PIT | 655 W 65TH ST | PERMIT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 655 W 65TH ST | PERIODIC | PASSED | View | |
REPAIR | REFRACTORY AROUND BURNER ON #2 BOILER NB#25042. | 655 W 65TH ST | PERIODIC | PASSED | View |
INSTALL | EXHAUSET FAN IN BOILER ROOM. | 655 W 65TH ST | PERIODIC | PASSED | View |
REPAIR | EXCESSIVE SCALE BUILD UP IN WATER SIDE OF #2 BOILER NB# 25042. | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 5 SAFET TEST - NO TAG | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE NON SLIP/ ANTI SKID COATING ON PIT LADDERS FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SEPERATE PHONE LINE FOR ELEVATOR #2 (PHONE NOT FUNCTIONING) FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COUNTERWEIGHT RUNBY SIGNS IN PIT. | 655 W 65TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | VERIFY PHONE LINE MONITORING/EMERGENCY COMMUNICATION LOSS AUDIBLE WARNING SIGNAL FOR FINAL. BOTH ELEVATORS. | 655 W 65TH ST | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | INSPECTION REQUIRED WHEN WORK IS COMPLETED CODE 18-28-106.1 | 655 W 65TH ST | COMPLAINT | PASSED | View |
OPEN TYPE VIOLATION | (VT 2031) WORKMANSHIP TO MEET INTENT OF BUILDING PROVISIONS OF THIS CODE CODE 13-16-060 | 655 W 65TH ST | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | MOST UNITS - UNDER CONSTRUCTION AT TIME OF INSPECTION. SOME OTHER UNITS - NO RESPONSE. UNABLE TO VERIFY DETECTORS AND CONDITIONS. | 655 W 65TH ST | PERIODIC | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | ARRANGE COMPLETED PERMIT INSPECTION CODE 13-12-100 | 655 W 65TH ST | COMPLAINT | PASSED | View |
REPAIR OR REPLACE | REPAIR OR REPLACE ALL CRAWL SPACE REGESTERS | 655 W 65TH ST | COMPLAINT | PASSED | View |
REPLACE | CRACKED HOUSING FOR PUMP ON LAARS HOT WATER BOILER BD # 243953. | 655 W 65TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SUFFICIENT COUNTERWEIGHT RUNBY CLEARANCE. CAR #1. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FAID'S AND EMENGENCY POWER FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CORRECT CROSSHEAD DATA TAG. CAR #2. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CITY OF CHICAGO COMPLAINT: REPAIR FIRE SERVICE PHASE I OPERATION. #1 DOES NOT RESET ONCE PHASE I IS TURNED OFF, SHUTTING DOWN ELEVATOR. | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CITY OF CHICAGO COMPLAINT: BOTH ELEVATORS: TEST FAIDS AND EMERGENCY POWER | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE EMERGENCY FIRE SPEAKERS/ EMERGENCY COMMIUNICATION MEANS FROM FIRE ALARM PANEL TO ELEVATORS FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLOSE OPEN MODERNIZATION PERMIT #100870185 | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR FIRE SERVICE PHASE I OPERATION. #1 DOES NOT RESET ONCE PHASE I IS TURNED OFF, SHUTTING DOWN ELEVATOR. | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BOTH ELEVATORS: TEST FAIDS AND EMERGENCY POWER | 655 W 65TH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR EMERGENCY PHONE INSIDE ELEVATORS FOR FINAL. PROVIDE SEPERATE PHONE LINES FOR EACH ELEVATOR. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST/VERIFY FIRE SERVICE ALTERNATE RECALL OPERATION WITH FULLY FUNCTIONAL LOBBY STATUS PANEL FOR FINAL. | 655 W 65TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST FAID'S FOR FINAL. ELEVATORS DID NOT RECALL TO MAIN EGRESS LANDING. | 655 W 65TH ST | PERMIT | FAILED | View |